| Func. |
| Name |
| Description |
|
| Code |
|
|
| ||
|
|
|
|
|
|
Run
Mode
Edit
Initialdata Units
| A072 | PID proportional gain | Proportional gain has a range of |
| 1.0 | − |
|
|
|
| 0.00 to 25.00 |
|
|
|
|
|
|
|
|
|
|
|
|
| A073 | PID integral time constant | Integral time constant has a |
| 1.0 | sec |
|
|
|
| range of 0.0 to 3600 seconds |
|
|
|
|
|
|
|
|
|
|
|
|
| A074 | PID derivative time constant | Derivative time constant has a |
| 0.00 | sec |
|
|
|
| range of 0.0 to 100 seconds |
|
|
|
|
|
|
|
|
|
|
|
|
| A075 | PV scale conversion | Process Variable (PV), scale |
| 1.00 | − |
|
|
|
| factor (multiplier), range of 0.01 |
|
|
|
|
|
|
| to 99.99 |
|
|
|
|
| A076 | PV source | Selects source of Process |
| 00 | − |
|
|
|
| Variable (PV), option codes: |
|
|
|
|
|
|
| 00…[OI] terminal (current in) |
|
|
|
|
|
|
| 01…[O] terminal (voltage in) |
|
|
|
|
|
|
| 02…Modbus network |
|
|
|
|
|
|
| 03…Pulse train input |
|
|
|
|
|
|
| 10…Calculate function output |
|
|
|
|
| A077 | Reverse PID action | Two option codes: |
| 00 | − |
|
|
|
| 00…PID input = |
|
|
|
|
|
|
| 01…PID input = |
|
|
|
|
| A078 | PID output limit | Sets the limit of PID output as |
| 0.0 | % |
|
|
|
| percent of full scale, |
|
|
|
|
|
|
| range is 0.0 to 100.0% |
|
|
|
|
| a079 | PID feed forward selection | Selects source of feed forward |
| 00 | − |
|
|
|
| gain, option codes: |
|
|
|
|
|
|
| 00…Disabled |
|
|
|
|
|
|
| 01…[O] terminal (voltage in) |
|
|
|
|
|
|
| 02…[OI] terminal (current in) |
|
|
|
|
| A081 | AVR function select | Automatic (output) voltage |
| 02 | − |
|
|
|
| regulation, selects from three |
|
|
|
|
|
| AVR function select, | type of AVR functions, three |
|
|
|
|
| a281 | option codes: |
| 02 | − |
| |
|
| 2nd motor | 00…AVR enabled |
|
|
|
|
|
|
| 01…AVR disabled |
|
|
|
|
|
|
| 02…AVR enabled except during |
|
|
|
|
|
|
| deceleration |
|
|
|
|
| A082 | AVR voltage select | 200V class inverter settings: |
| 200/ | V |
|
|
|
| ……200/215/220/230/240 |
| 400 |
|
|
|
| AVR voltage select, | 400V class inverter settings: |
|
| V |
|
| a282 | ……380/400/415/440/460/480 |
| 200/ |
| ||
| 2nd motor |
|
| 400 |
|
| |
|
|
|
|
|
|
|
|
| a083 | AVR filter time constant | Define the time constant of the |
| 0.300 | sec |
|
|
|
| AVR filter, range is 0 to 10 sec. |
|
|
|
|
|
|
|
|
|
|
|
|
| a084 | AVR deceleration gain | Gain adjustment of the braking |
| 100. | % |
|
|
|
| performance, range is 50 to |
|
|
|
|
|
|
| 200% |
|
|
|
|
| A085 | Two option codes: |
| 00 | − |
| |
|
|
| 00…Normal operation |
|
|
|
|
|
|
|
|
|
|
| |
| A086 | Range is 0.0 to 100 %. |
| 50.0 | % |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|