Standard Functions
NOTE:. Mark “ ” in b031=10 shows the accessible parameters when b031 is set “10”, high level access.
|
|
|
|
|
|
|
| Func. |
| Name |
| Description |
|
| Code |
|
|
| ||
|
|
|
|
|
|
Run
Mode
Edit
Initialdata Units
A001 | Frequency source | Eight options; select codes: |
|
| 02 | − | |
|
| 00 | …POT on ext. operator |
|
|
|
|
|
| 01 | …Control terminal |
|
|
|
|
A201 | Frequency source, | 02 | …Function F001 setting |
|
| 02 | − |
2nd motor | 03 | …Modbus network input |
|
|
|
| |
|
| 04 | …Option |
|
|
|
|
|
| 06 | …Pulse train input |
|
|
|
|
|
| 07 | …via EzSQ |
|
|
|
|
|
| 10 | …Calculate function output |
|
|
|
|
A002 | Run command source | Four options; select codes: |
|
| 02 | − | |
|
| 01 | …Control terminal |
|
|
|
|
| Run command source, | 02 | …Run key on keypad, or |
|
|
|
|
A202 |
| digital operator |
|
| 02 | − | |
2nd motor | 03 | …Modbus network input |
|
|
|
| |
|
| 04 | …Option |
|
|
|
|
A003 | Base frequency | Settable from 30 Hz to the |
|
| 60.0 | Hz | |
|
| maximum frequency(A004) |
|
|
|
| |
A203 | Base frequency, | Settable from 30 Hz to the 2nd |
|
|
| Hz | |
|
| 60.0 | |||||
2nd motor | maximum frequency(A204) |
|
|
| |||
|
|
|
|
|
| ||
A004 | Maximum frequency | Settable from the base |
| 60.0 | Hz | ||
|
| frequency to 400 Hz |
|
|
| ||
A204 | Maximum frequency, | Settable from the 2nd base |
|
| Hz | ||
60.0 | |||||||
2nd motor | frequency to 400 Hz |
|
|
| |||
|
|
|
|
|
| ||
A005 | [AT] selection | Three options; select codes: |
| 00 | − | ||
|
| 00...Select between [O] and [OI] |
|
|
| ||
|
|
| at [AT] (ON=OI, OFF=O) |
|
|
| |
|
| 02...Select between [O] and |
|
|
| ||
|
|
| external POT at [AT] |
|
|
| |
|
|
| (ON=POT, OFF=O) |
|
|
| |
|
| 03...Select between [OI] and |
|
|
| ||
|
|
| external POT at [AT] |
|
|
| |
|
|
| (ON=POT, OFF=OI) |
|
|
| |
A011 | [O] input active range start | The output frequency |
| 0.00 | Hz | ||
frequency | corresponding to the analog |
|
|
| |||
|
| input range starting point, |
|
|
| ||
|
| range is 0.00 to 400.0 |
|
|
| ||
A012 | [O] input active range end | The output frequency |
| 0.00 | Hz | ||
frequency | corresponding to the analog |
|
|
| |||
|
| input range ending point, |
|
|
| ||
|
| range is 0.0 to 400.0 |
|
|
| ||
A013 | [O] input active range start | The starting point (offset) for the |
| 0. | % | ||
voltage | active analog input range, |
|
|
| |||
|
| range is 0. to 100. |
|
|
| ||
A014 | [O] input active range end | The ending point (offset) for the |
| 100. | % | ||
voltage | active analog input range, |
|
|
| |||
|
| range is 0. to 100. |
|
|
|
50