Components to be combined

Followings are the example of the safety devices to be combined.

Series

Model

Norms to comply

Certification date

 

 

 

 

GS9A

301

ISO13849-2 cat4, SIL3

06.06.2007

 

 

 

 

G9SX

GS226-T15-RC

IEC61508 SIL1-3

04.11.2004

 

 

 

 

NE1A

SCPU01-V1

IEC61508 SIL3

27.09.2006

 

 

 

 

The configuration of and components used in any circuit other than an appropriately pre approved safety module that interfaces with the WJ200 GS1/GS2 and EDM ports MUST be at least equivalent to CAT 3 PLd under ISO 13849-1:2006 in order to be able to claim an overall CAT 3 PLd for the WJ200 and external circuit combination.

The EMI level that the external module has been assessed to must be at least equivalent to that of Appendix E IEC 62061.

Periodical check (proof test)

Proof test is essential to be able to reveal any dangerous undetected failures after a period of time, in this case 1 year. Carrying out this proof test at least one a year is the condition to comply the ISO13849-1 PLd.

- To activate (give current to) GS1 and GS2 simultaneously and separately to see output is allowed and EDM is conducting

Terminal

 

 

Status

 

GS1

current OFF

current ON

 

current OFF

current ON

GS2

current OFF

current OFF

 

current ON

current ON

EDM

conducted

not conducted

 

Not conducted

not conducted

(output)

forbidden

forbidden

 

forbidden

Allowed

- To activate (give current to) both GS1 and GS2 to see output is allowed and EDM is not conducting

- To activate (give current to) GS1, not to activate GS2 and see output is forbidden and EDM is not conducting - To activate (give current to) GS2, not to activate GS1 and see output is forbidden and EDM is not conducting - To deactivate (interrupt current to) both GS1 and GS2 to see output is forbidden and EDM is conducting

Precautions

1. To assure, that the Safe Disable function appropriately fulfills the safety requirements of the application, a throughout risk assessment for the whole safety system has to be carried out.

2.The Safe Disable function does not cut the power supply to the drive and does not provide electrical isolation. Before any installation or maintenance work is done, the drives power supply must be switched off and place a tag/lock-out.

3.The wiring distance for the Safe Disable inputs should be shorter than 30 m.

4.The time from opening the Safe Disable input until the drive output is switched off is less than 10 ms.

97

Image 99
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Basic System Description GFIInverter + Determining Wire and Fuse Sizes Motor OutputAllowable current T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Using the Front Panel Keypad Key and Indicator LegendPower LED Alarm LED Keys, Modes, and Parameters Keypad Navigation MapPRG LED Group a Group dGroup F SaveF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramOutput Input Control Logic Signal SpecificationsPulse TrainSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Using Intelligent Input Terminals Sink logic connectionSource logic connection Sinking Inputs, Internal Supply WJ200Sourcing Inputs, Internal Supply Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settingsTwo Stage Acceleration and Deceleration FW,RV2CH Option Terminal Function Name State Description Code Symbol Unattended Start ProtectionUSP Reset Inverter Option Terminal Function Name Using Intelligent Output TerminalsRun Signal Code SymbolFrequency Arrival Signals SettingsRequired FA3/FA5 FA2/FA4Alarm Signal StopTrip During normal operation Analog Input Operation AM H O OI LAM H O OI Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D009 D006D007 D008D060 D029D030 D050Main Profile Parameters Standard Functions A021 ~ A035 A015A220 A241A044 A242A043 A243A261 A058A059 A061A075 A072A073 A074A293 A092A292 A093A142 A131A132 A141A162 A156A157 A161Fine Tuning Functions B213 B012B212 B013B028 B025B026 B027B040 B037B038 B039B063 B060B061 B062B090 B087B088 B089B101 B096B097 B100B150 B133B134 B145Intelligent Terminal Functions C032 C028C030 C031C054 C047C052 C053C081 C076C077 C078C105 C102C103 C104C150 C147C148 C149DWN AnlgFWD, REV PidcSF4 SF1SF2 SF3255 Run Signal When the inverter is in Run Mode LOG1 LOG2LOG3 MO3 C039MO1 MO2Motor Constants Functions PM Motor Constants Functions H117 H112H113 H116Expansion Card Functions P046 P041P044 P045P077 P072P073 P075Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Restoring Factory Default Settings Error Name Descriptions CodeOther indication Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations How it works Functional Safety Certification in ProgressIntroduction Stop Category defined in EN60204-1Installation Wiring example OFF GS9A G9SXNE1A