| Run |
|
|
|
|
|
| Func. | Name |
| Description |
| Mode |
| Initialdata |
| Units |
|
| Code |
|
|
|
| Edit |
|
|
|
|
|
| B087 | STOP key enable |
| Select whether the STOP key on the |
|
|
| 00 |
| − |
|
|
|
|
| keypad is enabled, three option |
|
|
|
|
|
|
|
|
|
|
| codes: |
|
|
|
|
|
|
|
|
|
|
| 00…Enabled |
|
|
|
|
|
|
|
|
|
|
| 01…Disabled always |
|
|
|
|
|
|
|
|
|
|
| 02… Disabled for stop |
|
|
|
|
|
|
|
| B088 | Restart mode after FRS |
| Selects how the inverter resumes |
|
|
| 00 |
| − |
|
|
|
|
| operation when |
|
|
|
|
|
|
|
|
|
|
| is cancelled, three options: |
|
|
|
|
|
|
|
|
|
|
| 00…Restart from 0Hz |
|
|
|
|
|
|
|
|
|
|
| 01…Restart from frequency |
|
|
|
|
|
|
|
|
|
|
| detected from real speed of |
|
|
|
|
|
|
|
|
|
|
| motor (freq. matching) |
|
|
|
|
|
|
|
|
|
|
| 02…Restart from frequency |
|
|
|
|
|
|
|
|
|
|
| detected from real speed of |
|
|
|
|
|
|
|
|
|
|
| motor (active freq. matching) |
|
|
|
|
|
|
|
| b089 | Automatic carrier frequency |
| Three option codes: |
|
|
| 01 |
| - |
|
|
| reduction |
| 00…Disabled |
|
|
|
|
|
|
|
|
|
|
| 01…Enabled, depending on the |
|
|
|
|
|
|
|
|
|
|
| output current |
|
|
|
|
|
|
|
|
|
|
| 02…Enabled, depending on the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| b090 | Dynamic braking usage ratio |
| Selects the rate of use (in %) of the |
|
|
| 0.0 |
| % |
|
|
|
|
| regenerative braking resistor per |
|
|
|
|
|
|
|
|
|
|
| 100 sec. intervals, range is 0.0 to |
|
|
|
|
|
|
|
|
|
|
| 100%. |
|
|
|
|
|
|
|
|
|
|
| 0%: Function disabled |
|
|
|
|
|
|
|
|
|
|
| >0%: Enabled, per value |
|
|
|
|
|
|
|
| B091 | Stop mode selection |
| Select how the inverter stops the |
|
|
| 00 |
| − |
|
|
|
|
| motor, two option codes: |
|
|
|
|
|
|
|
|
|
|
| 00…DEC (decelerate to stop) |
|
|
|
|
|
|
|
|
|
|
| 01…FRS |
|
|
|
|
|
|
|
| B092 | Cooling fan control |
| Selects when the fan is ON during |
|
|
| 01 |
| - |
|
|
|
|
| inverter operation, three options: |
|
|
|
|
|
|
|
|
|
|
| 00…Fan is always ON |
|
|
|
|
|
|
|
|
|
|
| 01…Fan is ON during run, OFF |
|
|
|
|
|
|
|
|
|
|
| during stop (5 minute delay |
|
|
|
|
|
|
|
|
|
|
| from ON to OFF) |
|
|
|
|
|
|
|
|
|
|
| 02…Fan is temperature controlled |
|
|
|
|
|
|
|
| B093 | Clear elapsed time of cooling |
| Two option codes: |
|
|
| 00 |
| - |
|
|
| fan |
| 00…Count |
|
|
|
|
|
|
|
|
|
|
| 01…Clear |
|
|
|
|
|
|
|
| b094 | Initialization target data |
| Select initialized parameters, four |
|
|
| 00 |
| - |
|
|
|
|
| option codes: |
|
|
|
|
|
|
|
|
|
|
| 00…All parameters |
|
|
|
|
|
|
|
|
|
|
| 01…All parameters except in/output |
|
|
|
|
|
|
|
|
|
|
| terminals and communication. |
|
|
|
|
|
|
|
|
|
|
| 02…Only registered parameters in |
|
|
|
|
|
|
|
|
|
|
| Uxxx. |
|
|
|
|
|
|
|
|
|
|
| 03…All parameters except |
|
|
|
|
|
|
|
|
|
|
| registered parameters in Uxxx |
|
|
|
|
|
|
|
|
|
|
| and b037. |
|
|
|
|
|
|
|
| b095 | Dynamic braking control |
| Three option codes: |
|
|
| 01 |
| - |
|
|
| (BRD) selection |
| 00…Disable |
|
|
|
|
|
|
|
|
|
|
| 01…Enable during run only |
|
|
|
|
|
|
|
|
|
|
| 02…Enable always |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
63