Run

 

 

 

 

 

 

Func.

Name

 

Description

 

Mode

 

Initialdata

 

Units

 

 

Code

 

 

 

 

Edit

 

 

 

 

 

 

B087

STOP key enable

 

Select whether the STOP key on the

 

 

 

00

 

 

 

 

 

 

keypad is enabled, three option

 

 

 

 

 

 

 

 

 

 

 

codes:

 

 

 

 

 

 

 

 

 

 

 

00Enabled

 

 

 

 

 

 

 

 

 

 

 

01Disabled always

 

 

 

 

 

 

 

 

 

 

 

02Disabled for stop

 

 

 

 

 

 

 

 

B088

Restart mode after FRS

 

Selects how the inverter resumes

 

 

 

00

 

 

 

 

 

 

operation when free-run stop (FRS)

 

 

 

 

 

 

 

 

 

 

 

is cancelled, three options:

 

 

 

 

 

 

 

 

 

 

 

00Restart from 0Hz

 

 

 

 

 

 

 

 

 

 

 

01Restart from frequency

 

 

 

 

 

 

 

 

 

 

 

detected from real speed of

 

 

 

 

 

 

 

 

 

 

 

motor (freq. matching)

 

 

 

 

 

 

 

 

 

 

 

02Restart from frequency

 

 

 

 

 

 

 

 

 

 

 

detected from real speed of

 

 

 

 

 

 

 

 

 

 

 

motor (active freq. matching)

 

 

 

 

 

 

 

 

b089

Automatic carrier frequency

 

Three option codes:

 

 

 

01

 

-

 

 

 

reduction

 

00Disabled

 

 

 

 

 

 

 

 

 

 

 

01Enabled, depending on the

 

 

 

 

 

 

 

 

 

 

 

output current

 

 

 

 

 

 

 

 

 

 

 

02Enabled, depending on the

 

 

 

 

 

 

 

 

 

 

 

heat-sink temperature

 

 

 

 

 

 

 

 

b090

Dynamic braking usage ratio

 

Selects the rate of use (in %) of the

 

 

 

0.0

 

%

 

 

 

 

 

regenerative braking resistor per

 

 

 

 

 

 

 

 

 

 

 

100 sec. intervals, range is 0.0 to

 

 

 

 

 

 

 

 

 

 

 

100%.

 

 

 

 

 

 

 

 

 

 

 

0%: Function disabled

 

 

 

 

 

 

 

 

 

 

 

>0%: Enabled, per value

 

 

 

 

 

 

 

 

B091

Stop mode selection

 

Select how the inverter stops the

 

 

 

00

 

 

 

 

 

 

motor, two option codes:

 

 

 

 

 

 

 

 

 

 

 

00DEC (decelerate to stop)

 

 

 

 

 

 

 

 

 

 

 

01FRS (free-run to stop)

 

 

 

 

 

 

 

 

B092

Cooling fan control

 

Selects when the fan is ON during

 

 

 

01

 

-

 

 

 

 

 

inverter operation, three options:

 

 

 

 

 

 

 

 

 

 

 

00Fan is always ON

 

 

 

 

 

 

 

 

 

 

 

01Fan is ON during run, OFF

 

 

 

 

 

 

 

 

 

 

 

during stop (5 minute delay

 

 

 

 

 

 

 

 

 

 

 

from ON to OFF)

 

 

 

 

 

 

 

 

 

 

 

02Fan is temperature controlled

 

 

 

 

 

 

 

 

B093

Clear elapsed time of cooling

 

Two option codes:

 

 

 

00

 

-

 

 

 

fan

 

00Count

 

 

 

 

 

 

 

 

 

 

 

01Clear

 

 

 

 

 

 

 

 

b094

Initialization target data

 

Select initialized parameters, four

 

 

 

00

 

-

 

 

 

 

 

option codes:

 

 

 

 

 

 

 

 

 

 

 

00All parameters

 

 

 

 

 

 

 

 

 

 

 

01All parameters except in/output

 

 

 

 

 

 

 

 

 

 

 

terminals and communication.

 

 

 

 

 

 

 

 

 

 

 

02Only registered parameters in

 

 

 

 

 

 

 

 

 

 

 

Uxxx.

 

 

 

 

 

 

 

 

 

 

 

03All parameters except

 

 

 

 

 

 

 

 

 

 

 

registered parameters in Uxxx

 

 

 

 

 

 

 

 

 

 

 

and b037.

 

 

 

 

 

 

 

 

b095

Dynamic braking control

 

Three option codes:

 

 

 

01

 

-

 

 

 

(BRD) selection

 

00Disable

 

 

 

 

 

 

 

 

 

 

 

01Enable during run only

 

 

 

 

 

 

 

 

 

 

 

02Enable always

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63

Image 65
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Inverter + Basic System DescriptionGFI Allowable current Determining Wire and Fuse SizesMotor Output T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Power LED Alarm LED Using the Front Panel KeypadKey and Indicator Legend PRG LED Keys, Modes, and ParametersKeypad Navigation Map Group F Group dSave Group aF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramPulse Control Logic Signal SpecificationsTrain Output InputSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Source logic connection Using Intelligent Input TerminalsSink logic connection Sourcing Inputs, Internal Supply Sinking Inputs, Internal SupplyWJ200 Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settings2CH Two Stage Acceleration and DecelerationFW,RV USP Option Terminal Function Name State Description Code SymbolUnattended Start Protection Reset Inverter Run Signal Using Intelligent Output TerminalsCode Symbol Option Terminal Function NameRequired Frequency Arrival SignalsSettings FA3/FA5 FA2/FA4Trip Alarm SignalStop During normal operation AM H O OI Analog Input OperationAM H O OI L Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D007 D006D008 D009D030 D029D050 D060Main Profile Parameters Standard Functions A220 A015A241 A021 ~ A035A043 A242A243 A044A059 A058A061 A261A073 A072A074 A075A292 A092A093 A293A132 A131A141 A142A157 A156A161 A162Fine Tuning Functions B212 B012B013 B213B026 B025B027 B028B038 B037B039 B040B061 B060B062 B063B088 B087B089 B090B097 B096B100 B101B134 B133B145 B150Intelligent Terminal Functions C030 C028C031 C032C052 C047C053 C054C077 C076C078 C081C103 C102C104 C105C148 C147C149 C150FWD, REV AnlgPidc DWNSF2 SF1SF3 SF4255 Run Signal When the inverter is in Run Mode LOG3 LOG1LOG2 MO1 C039MO2 MO3Motor Constants Functions PM Motor Constants Functions H113 H112H116 H117Expansion Card Functions P044 P041P045 P046P073 P072P075 P077Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Other indication Restoring Factory Default SettingsError Name Descriptions Code Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations Introduction Functional Safety Certification in ProgressStop Category defined in EN60204-1 How it worksInstallation Wiring example OFF NE1A GS9AG9SX