Hitachi hitachi series inverter B133, B134, B145, B150, B160, B161, B163, B164, B165, B166, B171

Page 67

 

 

 

 

Run

 

 

 

 

Func.

Name

 

Description

Mode

 

Initialdata

 

Units

Code

 

 

 

Edit

 

 

 

 

B133

Decel. overvolt. suppress

 

Proportional gain when b130=01.

 

 

0.20

 

 

proportional gain

 

Range is: 0.00 to 5.00

 

 

 

 

 

B134

Decel. overvolt. suppress

 

Integration time when b130=01.

 

 

1.0

 

sec

 

integral time

 

Range is: 0.00 to 150.0

 

 

 

 

 

b145

GS input mode

 

Two option codes:

 

 

00

 

-

 

 

 

00No trip (Hardware shutoff only)

 

 

 

 

 

 

 

 

01Trip

 

 

 

 

 

b150

Display ex.operator connected

 

When an external operator is

 

 

001

 

 

 

 

connected via RS-422 port, the

 

 

 

 

 

 

 

 

built-in display is locked and shows

 

 

 

 

 

 

 

 

only one "d" parameter configured

 

 

 

 

 

 

 

 

in:

 

 

 

 

 

 

 

 

d001 ~ d030

 

 

 

 

 

b160

1st parameter of Dual Monitor

 

Set any two "d" parameters in b160

 

 

001

 

 

 

 

and b161, then they can be

 

 

 

 

 

 

 

 

monitored in d050. The two

 

 

 

 

 

 

 

 

parameters are switched by

 

 

 

 

 

 

 

 

up/down keys.

 

 

 

 

 

 

 

 

Set range: d001 ~ d030

 

 

 

 

 

b161

2nd parameter of Dual Monitor

 

 

 

 

002

 

 

 

 

 

 

 

 

 

 

b163

Frequency set in monitoring

 

Two option codes:

 

 

00

 

-

 

 

 

00Freq. set disabled

 

 

 

 

 

 

 

 

01Freq. set enabled

 

 

 

 

 

b164

Automatic return to the initial

 

10 min. after the last key operation,

 

 

00

 

-

 

display

 

display returns to the initial

 

 

 

 

 

 

 

 

parameter set by b038. Two option

 

 

 

 

 

 

 

 

codes:

 

 

 

 

 

 

 

 

00Disable

 

 

 

 

 

 

 

 

01Enable

 

 

 

 

 

b165

Ex. operator com. loss action

 

Five option codes:

 

 

02

 

-

 

 

 

00Trip

 

 

 

 

 

 

 

 

01Trip after deceleration to a stop

 

 

 

 

 

 

 

 

02Ignore

 

 

 

 

 

 

 

 

03Coasting (FRS)

 

 

 

 

 

 

 

 

04Decelerates to a stop

 

 

 

 

 

b166

Data Read/Write select

 

00Read/Write OK

 

 

00

 

-

 

 

 

01Protected

 

 

 

 

 

b171

Inverter mode selection

 

Three option codes:

 

 

00

 

-

 

 

 

00No function

 

 

 

 

 

 

 

 

01Std. IM (Induction Motor)

 

 

 

 

 

 

 

 

03PM (Permanent Magnet Motor)

 

 

 

 

 

b180

Initialization trigger

 

This is to perform initialization by

 

 

00

 

-

 

(*)

 

parameter input with b084, b085 and

 

 

 

 

 

 

 

 

b094. Two option codes:

 

 

 

 

 

 

 

 

00Initialization disable

 

 

 

 

 

 

 

 

01Perform initialization

 

 

 

 

 

b190

Password Settings A

 

0000(Invalid Password)

 

 

0000

 

-

 

 

 

0001-FFFF(Password)

 

 

 

 

 

b191

Password authentication A

 

0000-FFFF

 

 

0000

 

-

 

 

 

 

 

 

 

 

 

b192

Password Settings B

 

0000(Invalid Password)

 

 

0000

 

-

 

 

 

0001-FFFF(Password)

 

 

 

 

 

b193

Password authentication B

 

0000-FFFF

 

 

0000

 

-

 

 

 

 

 

 

 

 

 

65

Image 67
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating GFI Basic System DescriptionInverter + Motor Output Determining Wire and Fuse SizesAllowable current T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Key and Indicator Legend Using the Front Panel KeypadPower LED Alarm LED Keypad Navigation Map Keys, Modes, and ParametersPRG LED Group a Group dGroup F SaveF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramOutput Input Control Logic Signal SpecificationsPulse TrainSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Sink logic connection Using Intelligent Input TerminalsSource logic connection WJ200 Sinking Inputs, Internal SupplySourcing Inputs, Internal Supply Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settingsFW,RV Two Stage Acceleration and Deceleration2CH Unattended Start Protection Option Terminal Function Name State Description Code SymbolUSP Reset Inverter Option Terminal Function Name Using Intelligent Output TerminalsRun Signal Code SymbolSettings Frequency Arrival SignalsRequired FA3/FA5 FA2/FA4Stop Alarm SignalTrip During normal operation AM H O OI L Analog Input OperationAM H O OI Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D009 D006D007 D008D060 D029D030 D050Main Profile Parameters Standard Functions A021 ~ A035 A015A220 A241A044 A242A043 A243A261 A058A059 A061A075 A072A073 A074A293 A092A292 A093A142 A131A132 A141A162 A156A157 A161Fine Tuning Functions B213 B012B212 B013B028 B025B026 B027B040 B037B038 B039 B063 B060 B061 B062B090 B087B088 B089B101 B096B097 B100B150 B133B134 B145Intelligent Terminal Functions C032 C028C030 C031C054 C047C052 C053C081 C076C077 C078C105 C102C103 C104C150 C147C148 C149DWN AnlgFWD, REV PidcSF4 SF1SF2 SF3255 Run Signal When the inverter is in Run Mode LOG2 LOG1LOG3 MO3 C039MO1 MO2Motor Constants Functions PM Motor Constants Functions H117 H112H113 H116Expansion Card Functions P046 P041P044 P045P077 P072P073 P075Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Error Name Descriptions Code Restoring Factory Default SettingsOther indication Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations How it works Functional Safety Certification in ProgressIntroduction Stop Category defined in EN60204-1Installation Wiring example OFF G9SX GS9ANE1A