Hitachi hitachi series inverter C047, C052, C053, C054, C055, C056, C057, C058, C059, C061, C063

Page 70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Run

 

 

 

 

 

 

 

 

 

 

Func.

 

 

 

Name

 

 

 

Description

 

 

 

 

Mode

 

 

 

Initialdata

 

 

 

Units

 

 

Code

 

 

 

 

 

 

 

 

 

 

Edit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C047

 

 

Pulse train input/output

 

 

 

If EO terminal is configured as

 

 

 

 

 

 

 

 

1.00

 

 

 

 

 

 

 

 

 

 

scale conversion

 

 

 

pulse train input (C027=15), scale

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

conversion is set in C047.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulse-out = Pulse-in (C047)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set range is 0.01 to 99.99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C052

 

 

PID FBV output

 

 

 

When the PV exceeds this value,

 

 

 

 

 

 

 

 

100.0

 

 

%

 

 

 

 

 

 

high limit

 

 

 

the PID loop turns OFF the PID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

second stage output, range is 0.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to 100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C053

 

 

PID FBV output

 

 

 

When the PV goes below this

 

 

 

 

 

 

 

 

0.0

 

 

%

 

 

 

 

 

 

low limit

 

 

 

value, the PID loop turns ON the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PID second stage output, range is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0 to 100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C054

 

 

Over-torque/under-torque

 

 

 

Two option codes:

 

 

 

 

 

 

 

 

00

 

 

-

 

 

 

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00 Over-torque

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Under-torque

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C055

 

 

Over/under-torque level

 

 

 

Set range is 0 to 200%

 

 

 

 

 

 

 

 

100.

 

 

%

 

 

 

 

 

 

(Forward powering mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C056

 

 

Over/under-torque level

 

 

 

Set range is 0 to 200%

 

 

 

 

 

 

 

 

100.

 

 

%

 

 

 

 

 

 

(Reverse regen. mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C057

 

 

Over/under-torque level

 

 

 

Set range is 0 to 200%

 

 

 

 

 

 

 

 

100.

 

 

%

 

 

 

 

 

 

(Reverse powering mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C058

 

 

Over/under-torque level

 

 

 

Set range is 0 to 200%

 

 

 

 

 

 

 

 

100.

 

 

%

 

 

 

 

 

 

(Forward regen. mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C059

 

 

Signal output mode of

 

 

 

Two option codes:

 

 

 

 

 

 

 

 

01

 

 

-

 

 

 

 

 

 

Over/under-torque

 

 

 

00During accel., decel. and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

constant speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01During constant speed only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C061

 

 

Electronic thermal warning

 

 

 

Set range is 0 to 100%

 

 

 

 

 

 

 

 

90

 

 

%

 

 

 

 

 

 

level

 

 

 

Setting 0 means disabled.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C063

 

 

Zero speed detection level

 

 

 

Set range is 0.0 to 100.0Hz

 

 

 

 

 

 

 

 

0.00

 

 

 

Hz

 

C064

 

 

Heat sink overheat warning

 

 

 

Set range is 0 to 110 °C

 

 

 

 

 

 

 

 

100.

 

 

 

°C

 

C071

 

 

Communication speed

 

 

 

Eight option codes:

 

 

 

 

 

 

 

 

05

 

 

 

baud

 

 

 

 

 

 

 

 

 

 

032,400 bps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

044,800 bps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

059,600 bps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0619,200 bps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0738,400 bps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0857,600 bps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0976,800 bps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10115,200 bps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C072

 

 

Modbus address

 

 

 

Set the address of the inverter on

 

 

 

 

 

 

 

 

1.

 

 

 

 

 

 

 

 

 

 

 

 

 

the network. Range is 1 to 247

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C074

 

 

Communication parity

 

 

Three option codes:

 

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

 

 

00No parity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Even parity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02Odd parity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C075

 

 

Communication stop bit

 

 

 

Two option codes:

 

 

 

 

 

 

 

 

1

 

 

 

bit

 

 

 

 

 

 

 

 

 

 

11 bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22 bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

68

Image 70
Contents WJ200 Series Inverter Quick Reference Guide Page Marking Requirements UL→ Cautions, Warnings and InstructionsTerminal symbols and Screw size Fuse Sizes Inverter Specification Label 5AT 123 45A-001 1005WJ200 Inverter Specifications Model-specific tables for 200V and 400V class invertersWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating GFI Basic System DescriptionInverter + Motor Output Determining Wire and Fuse SizesAllowable current Wire the Inverter Input to a Supply T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3RB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Key and Indicator Legend Using the Front Panel KeypadPower LED Alarm LED Keypad Navigation Map Keys, Modes, and ParametersPRG LED Save Group dGroup F Group aF001 Key Connecting to PLCs and Other Devices GNDExample Wiring Diagram MotorTrain Control Logic Signal SpecificationsPulse Output InputWiring sample of control logic terminal sink logic SP, SNWire size for control and relay terminals Sink/source logic of intelligent input terminalsRecommended ferrule Intelligent Terminal Listing Intelligent InputsIntelligent Outputs Sink logic connection Using Intelligent Input TerminalsSource logic connection WJ200 Sinking Inputs, Internal SupplySourcing Inputs, Internal Supply Sinking Inputs, External Supply Sourcing Inputs, External SupplyInserting OFFForward Run/Stop and Reverse Run/Stop Commands Option Terminal Code Symbol Function Name State DescriptionRequired settings Multi-Speed Select ~Binary OperationFW,RV Two Stage Acceleration and Deceleration2CH Unattended Start Protection Option Terminal Function Name State Description Code SymbolUSP Reset Inverter Code Symbol Using Intelligent Output TerminalsRun Signal Option Terminal Function NameSettings Frequency Arrival SignalsRequired FA2/FA4 FA3/FA5Stop Alarm SignalTrip During normal operation AM H O OI L Analog Input OperationAM H O OI Other Analog Input-related topics Pulse Train Input Operation SN 7 6 5 4 3 2 1 L PLC P24Analog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D008 D006D007 D009D050 D029D030 D060Main Profile Parameters Standard Functions A241 A015A220 A021 ~ A035A243 A242A043 A044A061 A058A059 A261A074 A072A073 A075A093 A092A292 A293A141 A131A132 A142A161 A156A157 A162Fine Tuning Functions B013 B012B212 B213B027 B025B026 B028B039 B037B038 B040B062 B060B061 B063B089 B087B088 B090B100 B096B097 B101B145 B133B134 B150Intelligent Terminal Functions C031 C028C030 C032C053 C047C052 C054C078 C076C077 C081C104 C102C103 C105C149 C147C148 C150Pidc AnlgFWD, REV DWNSF3 SF1SF2 SF4255 Run Signal When the inverter is in Run Mode LOG2 LOG1LOG3 MO2 C039MO1 MO3Motor Constants Functions PM Motor Constants Functions H116 H112H113 H117Expansion Card Functions P045 P041P044 P046P075 P072P073 P077Monitoring Trip Events, History, & Conditions Trip History and Inverter StatusError Codes Error Name Causes CodeE37 Error Name Descriptions Code Restoring Factory Default SettingsOther indication CE-EMC Installation Guidelines Important notesPage Page Installation for WJ200 series example of SF models Metal plate earthHitachi EMC Recommendations Stop Category defined in EN60204-1 Functional Safety Certification in ProgressIntroduction How it worksInstallation Wiring example OFF G9SX GS9ANE1A