Hitachi hitachi series inverter user manual Anlg, Fwd, Rev, Pidc, Dwn

Page 74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Option

 

 

Terminal

 

 

Function Name

 

 

 

Description

 

 

 

 

Code

 

 

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-stage Acceleration

 

ON

Frequency output

uses

2nd-stage

acceleration

and

 

 

09

 

 

2CH

 

 

deceleration values

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and Deceleration

 

OFF

Frequency output

uses

standard

acceleration

and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

deceleration values

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

Causes output to turn OFF, allowing motor to free run

 

 

11

 

 

FRS

Free-run Stop

 

(coast) to stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Output operates normally, so controlled deceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

stop motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

When assigned input transitions OFF to ON, inverter

 

 

12

 

 

EXT

 

External Trip

 

 

 

latches trip event and displays E 12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No trip event for ON to OFF, any recorded trip events

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remain in history until reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unattended Start

 

ON

On powerup, the

inverter will not

resume a

Run

 

 

13

 

 

USP

 

 

command (mostly used in the US)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protection

 

 

 

OFF

On powerup, the inverter will resume a Run command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

that was active before power loss

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

CS

 

Commercial

power

 

ON

Motor can be driven by commercial power

 

 

 

 

 

 

source switchover

 

OFF

Motor is driven via the inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

The keypad and

remote programming devices

are

 

 

15

 

 

SFT

 

Software Lock

 

prevented from changing parameters

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The parameters may be edited and stored

 

 

 

16

 

 

AT

 

Analog Input

 

 

 

ON

Refer to “Analog Input Operation” on page 41.

 

 

 

 

 

 

Voltage/Current Select

 

OFF

 

 

 

 

 

 

 

 

 

 

The trip condition is reset, the motor output is turned

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

18

 

 

RS

 

Reset Inverter

 

OFF, and powerup reset is asserted

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal power-ON operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When a thermistor is connected to terminal [5] and [L],

 

 

 

 

 

 

 

 

PTC

thermistor

 

ANLG

the inverter checks for over-temperature and will cause

 

 

19

 

 

PTC

 

Thermal Protection

 

 

trip event and turn OFF output to motor

 

 

 

 

 

 

 

 

 

(C005 only)

 

 

 

OPEN

A disconnect of the thermistor causes a trip event, and

 

 

 

 

 

 

 

 

 

 

 

 

 

the inverter turns OFF the motor

 

 

 

 

20

 

 

STA

 

Start

 

 

 

ON

Starts the motor rotation

 

 

 

 

 

 

 

 

 

 

 

(3-wire interface)

 

OFF

No change to present motor status

 

 

 

 

21

 

 

STP

Stop

 

 

 

ON

Stops the motor rotation

 

 

 

 

 

 

 

 

 

 

 

(3-wire interface)

 

OFF

No change to present motor status

 

 

 

 

22

 

 

F/R

FWD, REV

 

 

 

ON

Selects the direction of motor rotation: ON = FWD.

 

 

 

 

 

 

 

 

 

(3-wire interface)

 

 

While the motor is rotating, a change of F/R will start a

 

 

 

 

 

 

 

 

 

 

 

 

 

deceleration, followed by a change in direction

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Selects the direction of motor rotation: OFF = REV.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

While the motor is rotating, a change of F/R will start a

 

 

 

 

 

 

 

 

 

 

 

 

 

deceleration, followed by a change in direction

 

 

 

23

 

 

PID

PID Disable

 

 

 

ON

Temporarily disables PID loop control. Inverter output

 

 

 

 

 

 

 

 

 

 

 

 

 

turns OFF as long as PID Enable is active (A071=01)

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Has no effect on PID loop operation, which operates

 

 

 

 

 

 

 

 

 

 

 

 

 

normally if PID Enable is active (A071=01)

 

 

 

24

 

 

PIDC

 

PID Reset

 

 

 

ON

Resets the PID loop controller. The main consequence

 

 

 

 

 

 

 

 

 

 

 

 

 

is that the integrator sum is forced to zero

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No effect on PID controller

 

 

 

 

27

 

 

UP

 

Remote Control UP

 

ON

Accelerates (increases output frequency) motor from

 

 

 

 

 

 

 

 

Function (motorized

 

 

current frequency

 

 

 

 

 

 

 

 

 

 

 

 

speed pot.)

 

 

 

OFF

Output to motor operates normally

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

 

 

DWN

Remote Control Down

 

ON

Decelerates (decreases output frequency) motor from

 

 

 

 

 

 

 

 

Function (motorized

 

 

current frequency

 

 

 

 

 

 

 

 

 

 

 

 

speed pot.)

 

 

 

OFF

Output to motor operates normally

 

 

 

72

Image 74
Contents WJ200 Series Inverter Quick Reference Guide Page Marking Requirements UL→ Cautions, Warnings and InstructionsTerminal symbols and Screw size Fuse Sizes Inverter Specification Label 5AT 123 45A-001 1005WJ200 Inverter Specifications Model-specific tables for 200V and 400V class invertersWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Inverter + Basic System DescriptionGFI Allowable current Determining Wire and Fuse SizesMotor Output Wire the Inverter Input to a Supply T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3RB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Power LED Alarm LED Using the Front Panel KeypadKey and Indicator Legend PRG LED Keys, Modes, and ParametersKeypad Navigation Map Save Group dGroup F Group aF001 Key Connecting to PLCs and Other Devices GNDExample Wiring Diagram MotorTrain Control Logic Signal SpecificationsPulse Output InputWiring sample of control logic terminal sink logic SP, SNWire size for control and relay terminals Sink/source logic of intelligent input terminalsRecommended ferrule Intelligent Terminal Listing Intelligent InputsIntelligent Outputs Source logic connection Using Intelligent Input TerminalsSink logic connection Sourcing Inputs, Internal Supply Sinking Inputs, Internal SupplyWJ200 Sinking Inputs, External Supply Sourcing Inputs, External SupplyInserting OFFForward Run/Stop and Reverse Run/Stop Commands Option Terminal Code Symbol Function Name State DescriptionRequired settings Multi-Speed Select ~Binary Operation2CH Two Stage Acceleration and DecelerationFW,RV USP Option Terminal Function Name State Description Code SymbolUnattended Start Protection Reset Inverter Code Symbol Using Intelligent Output TerminalsRun Signal Option Terminal Function NameRequired Frequency Arrival SignalsSettings FA2/FA4 FA3/FA5Trip Alarm SignalStop During normal operation AM H O OI Analog Input OperationAM H O OI L Other Analog Input-related topics Pulse Train Input Operation SN 7 6 5 4 3 2 1 L PLC P24Analog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D008 D006D007 D009D050 D029D030 D060Main Profile Parameters Standard Functions A241 A015A220 A021 ~ A035A243 A242A043 A044A061 A058A059 A261A074 A072A073 A075A093 A092A292 A293A141 A131A132 A142A161 A156A157 A162Fine Tuning Functions B013 B012B212 B213B027 B025B026 B028B039 B037B038 B040B062 B060B061 B063B089 B087B088 B090B100 B096B097 B101B145 B133B134 B150Intelligent Terminal Functions C031 C028C030 C032C053 C047C052 C054C078 C076C077 C081C104 C102C103 C105C149 C147C148 C150Pidc AnlgFWD, REV DWNSF3 SF1SF2 SF4255 Run Signal When the inverter is in Run Mode LOG3 LOG1LOG2 MO2 C039MO1 MO3Motor Constants Functions PM Motor Constants Functions H116 H112H113 H117Expansion Card Functions P045 P041P044 P046P075 P072P073 P077Monitoring Trip Events, History, & Conditions Trip History and Inverter StatusError Codes Error Name Causes CodeE37 Other indication Restoring Factory Default SettingsError Name Descriptions Code CE-EMC Installation Guidelines Important notesPage Page Installation for WJ200 series example of SF models Metal plate earthHitachi EMC Recommendations Stop Category defined in EN60204-1 Functional Safety Certification in ProgressIntroduction How it worksInstallation Wiring example OFF NE1A GS9AG9SX