Hitachi hitachi series inverter user manual Run Signal When the inverter is in Run Mode

Page 77

Output Function Summary Table – This table shows all functions for the logical outputs (terminals [11], [12] and [AL]) at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Output Terminals” on page 36.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Option

 

 

Terminal

 

 

Function Name

 

 

 

Description

 

 

 

 

 

Code

 

 

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

 

 

RUN

 

Run Signal

 

ON

When the inverter is in Run Mode

 

 

 

 

 

 

 

 

 

 

 

 

OFF

When the inverter is in Stop Mode

 

 

 

 

01

 

 

FA1

 

Frequency Arrival Type

 

ON

When output to motor is at the set frequency

 

 

 

 

 

 

 

 

1–Constant Speed

 

OFF

When output to motor is OFF, or in any

 

 

 

 

 

 

 

 

 

 

 

acceleration or deceleration ramp

 

 

 

 

02

 

 

FA2

 

Frequency Arrival Type

 

ON

When output to motor is at or above the set freq,

 

 

 

 

 

 

 

 

2–Over frequency

 

 

 

C042

 

C043

) ramps

 

 

 

 

 

 

 

 

 

 

 

even if in accel (

 

) or decel (

 

 

 

 

 

 

 

 

 

 

 

OFF

When output to motor is OFF,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or at a level below the set frequency

 

 

 

03

 

 

OL

Overload Advance

 

ON

When output current is more than the set

 

 

 

 

 

 

 

 

Notice Signal 1

 

 

threshold (C041) for the overload signal

 

 

 

 

 

 

 

 

 

 

OFF

When output current is less than the set threshold

 

 

 

 

 

 

 

 

 

 

 

for the deviation signal

 

 

 

 

 

04

 

 

OD

Output Deviation

 

ON

When PID error is more than the set threshold for

 

 

 

 

 

 

 

 

for PID Control

 

 

the deviation signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

When PID error is less than the set threshold for

 

 

 

 

 

 

 

 

 

 

 

the deviation signal

 

 

 

 

 

 

05

 

 

AL

 

Alarm Signal

 

ON

When an alarm signal has occurred and has not

 

 

 

 

 

 

 

 

 

 

 

been cleared

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

When no alarm has occurred since the last

 

 

 

 

 

 

 

 

 

 

 

cleaning of alarm(s)

 

 

 

 

 

 

06

 

 

FA3

 

Frequency Arrival Type

 

ON

When output to motor is at the set frequency,

 

 

 

 

 

 

 

 

3–Set frequency

 

 

during accel (

C042

) and decel (

C043

).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

When output to motor is OFF,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or is not at a level of the set frequency

 

 

07

 

 

OTQ

 

Over/under Torque

 

ON

Estimated motor torque exceeds

 

 

 

 

 

 

 

 

 

 

Signal

 

 

the specified level

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Estimated motor torque is lower than

 

 

 

 

 

 

 

 

 

 

 

the specified level

 

 

 

 

 

 

 

09

 

 

UV

Undervoltage

 

ON

Inverter is in Undervoltage

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Inverter is not in Undervoltage

 

 

 

 

 

10

 

 

TRQ

Torque Limited Signal

 

ON

Torque limit function is executing

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Torque limit function is not executing

 

 

 

11

 

 

RNT

 

Run Time Expired

 

ON

Total running time of the inverter exceeds

 

 

 

 

 

 

 

 

 

 

 

the specified value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Total running time of the inverter does not exceed

 

 

 

 

 

 

 

 

 

 

 

the specified value

 

 

 

 

 

 

12

 

 

ONT

 

Power ON time Expired

 

ON

Total power ON time of the inverter exceeds

 

 

 

 

 

 

 

 

 

 

 

the specified value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Total power ON time of the inverter does not

 

 

 

 

 

 

 

 

 

 

 

exceed the specified value

 

 

 

 

 

13

 

 

THM

Thermal Warning

 

ON

Accumulated thermal count exceeds

 

 

 

 

 

 

 

 

 

 

 

 

the C061 set value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Accumulated thermal count does not exceed the

 

 

 

 

 

 

 

 

 

 

 

C061 set value

 

 

 

 

 

 

 

19

 

 

BRK

Brake Release Signal

 

ON

Output for brake release

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No action for brake

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

BER

Brake Error Signal

 

ON

Brake error has occurred

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Brake performance is normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

Image 77
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Inverter + Basic System DescriptionGFI Allowable current Determining Wire and Fuse SizesMotor Output T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Power LED Alarm LED Using the Front Panel KeypadKey and Indicator Legend PRG LED Keys, Modes, and ParametersKeypad Navigation Map Group F Group dSave Group aF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramPulse Control Logic Signal SpecificationsTrain Output InputSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Source logic connection Using Intelligent Input TerminalsSink logic connection Sourcing Inputs, Internal Supply Sinking Inputs, Internal SupplyWJ200 Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settings2CH Two Stage Acceleration and DecelerationFW,RV USP Option Terminal Function Name State Description Code SymbolUnattended Start Protection Reset Inverter Run Signal Using Intelligent Output TerminalsCode Symbol Option Terminal Function NameRequired Frequency Arrival SignalsSettings FA3/FA5 FA2/FA4Trip Alarm SignalStop During normal operation AM H O OI Analog Input OperationAM H O OI L Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D007 D006D008 D009D030 D029D050 D060Main Profile Parameters Standard Functions A220 A015A241 A021 ~ A035A043 A242A243 A044A059 A058A061 A261A073 A072A074 A075A292 A092A093 A293A132 A131A141 A142A157 A156A161 A162Fine Tuning Functions B212 B012B013 B213B026 B025B027 B028B038 B037B039 B040B061 B060B062 B063B088 B087B089 B090B097 B096B100 B101B134 B133B145 B150Intelligent Terminal Functions C030 C028C031 C032C052 C047C053 C054C077 C076C078 C081C103 C102C104 C105C148 C147C149 C150FWD, REV AnlgPidc DWNSF2 SF1SF3 SF4255 Run Signal When the inverter is in Run Mode LOG3 LOG1LOG2 MO1 C039MO2 MO3Motor Constants Functions PM Motor Constants Functions H113 H112H116 H117Expansion Card Functions P044 P041P045 P046P073 P072P075 P077Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Other indication Restoring Factory Default SettingsError Name Descriptions Code Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations Introduction Functional Safety Certification in ProgressStop Category defined in EN60204-1 How it worksInstallation Wiring example OFF NE1A GS9AG9SX