Page 73

 

 

 

 

 

 

 

 

 

 

 

Run

 

 

 

 

 

 

 

 

 

 

Func.

 

 

Name

 

 

Description

 

 

 

Mode

 

 

 

Initialdata

 

 

 

Units

 

 

Code

 

 

 

 

 

 

 

Edit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C147

 

Logic output 2 operator

 

 

Applies a logic function to calculate

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

[LOG] output state,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three options:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00[LOG] = A AND B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01[LOG] = A OR B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02[LOG] = A XOR B

 

 

 

 

 

 

 

 

 

 

 

 

 

C148

 

Logic output 3 operand A

 

 

All the programmable functions

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

available for logic (discrete) outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

C149

 

Logic output 3 operand B

 

 

 

 

 

 

 

 

 

01

 

 

 

 

 

 

 

except LOG1 to LOG3, OPO, no

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C150

 

Logic output 3 operator

 

 

Applies a logic function to calculate

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

[LOG] output state,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three options:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00[LOG] = A AND B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01[LOG] = A OR B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02[LOG] = A XOR B

 

 

 

 

 

 

 

 

 

 

 

 

 

C160

 

Input [1] response time

 

 

Sets response time of each input

 

 

 

 

 

 

 

1.

 

 

 

 

 

 

 

 

 

 

 

terminal, set range:

 

 

 

 

 

 

 

 

 

 

 

 

 

C161

 

Input [2] response time

 

 

 

 

 

 

 

 

 

1.

 

 

 

 

 

 

 

0 (x 2 [ms]) to 200 (x 2 [ms])

 

 

 

 

 

 

 

 

 

 

 

C162

 

Input [3] response time

 

 

 

 

 

 

 

 

 

1.

 

 

 

 

 

 

 

(0 to 400 [ms])

 

 

 

 

 

 

 

 

 

 

 

C163

 

Input [4] response time

 

 

 

 

 

 

 

 

 

 

1.

 

 

 

 

C164

 

Input [5] response time

 

 

 

 

 

 

 

 

 

 

1.

 

 

 

 

C165

 

Input [6] response time

 

 

 

 

 

 

 

 

 

 

1.

 

 

 

 

C166

 

Input [7] response time

 

 

 

 

 

 

 

 

 

 

1.

 

 

 

 

C169

 

Multistage speed/position

 

 

Set range is 0. to 200. (x 10ms)

 

 

 

 

 

 

 

0.

 

 

 

ms

 

 

 

 

 

determination time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Function Summary Table – This table shows all thirty-one intelligent input functions at a glance. Detailed description of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Input Terminals” on page 27.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Option

 

 

Terminal

 

 

Function Name

 

 

 

Description

 

 

Code

 

 

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

 

 

FW

FORWARD Run/Stop

 

ON

Inverter is in Run Mode, motor runs forward

 

 

 

 

OFF

Inverter is in Stop Mode, motor stops

 

 

 

 

 

 

 

 

 

 

 

 

01

 

 

RV

 

Reverse Run/Stop

 

ON

Inverter is in Run Mode, motor runs reverse

 

 

 

 

 

OFF

Inverter is in Stop Mode, motor stops

 

 

 

 

 

 

 

 

 

 

 

 

02

 

 

CF1

 

Multi-speed Select,

 

ON

Binary encoded speed select, Bit 0, logical 1

 

 

 

 

Bit 0 (LSB)

 

OFF

Binary encoded speed select, Bit 0, logical 0

 

 

 

 

 

 

 

 

 

 

03

 

 

CF2

 

Multi-speed Select,

 

ON

Binary encoded speed select, Bit 1, logical 1

 

 

 

 

Bit 1

 

OFF

Binary encoded speed select, Bit 1, logical 0

 

 

 

 

 

 

 

 

 

 

04

 

 

CF3

 

Multi-speed Select,

 

ON

Binary encoded speed select, Bit 2, logical 1

 

 

 

 

Bit 2

 

OFF

Binary encoded speed select, Bit 2, logical 0

 

 

 

 

 

 

 

 

 

 

05

 

 

CF4

 

Multi-speed Select,

 

ON

Binary encoded speed select, Bit 3, logical 1

 

 

 

 

Bit 3 (MSB)

 

OFF

Binary encoded speed select, Bit 3, logical 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

Inverter is in Run Mode, output to motor runs at

 

06

 

 

JG

Jogging

 

jog parameter frequency

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

Inverter is in Stop Mode

 

07

 

 

DB

External DC braking

 

ON

DC braking will be applied during deceleration

 

 

 

 

OFF

DC braking will not be applied

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set (select) 2nd Motor

 

ON

The inverter uses 2nd motor parameters for

 

08

 

 

SET

 

 

generating frequency output to motor

 

 

 

 

Data

 

OFF

The inverter uses 1st (main) motor parameters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for generating frequency output to motor

 

 

 

 

 

 

 

 

 

 

 

 

 

71

Image 73
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating GFI Basic System DescriptionInverter + Motor Output Determining Wire and Fuse SizesAllowable current T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Key and Indicator Legend Using the Front Panel KeypadPower LED Alarm LED Keypad Navigation Map Keys, Modes, and ParametersPRG LED Group F Group dSave Group aF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramPulse Control Logic Signal SpecificationsTrain Output InputSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Sink logic connection Using Intelligent Input TerminalsSource logic connection WJ200 Sinking Inputs, Internal SupplySourcing Inputs, Internal Supply Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settingsFW,RV Two Stage Acceleration and Deceleration2CH Unattended Start Protection Option Terminal Function Name State Description Code SymbolUSP Reset Inverter Run Signal Using Intelligent Output TerminalsCode Symbol Option Terminal Function NameSettings Frequency Arrival SignalsRequired FA3/FA5 FA2/FA4Stop Alarm SignalTrip During normal operation AM H O OI L Analog Input OperationAM H O OI Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D007 D006D008 D009D030 D029D050 D060Main Profile Parameters Standard Functions A220 A015A241 A021 ~ A035A043 A242A243 A044A059 A058A061 A261A073 A072A074 A075A292 A092A093 A293A132 A131A141 A142A157 A156A161 A162Fine Tuning Functions B212 B012B013 B213B026 B025B027 B028B038 B037B039 B040B061 B060B062 B063B088 B087B089 B090B097 B096B100 B101B134 B133B145 B150Intelligent Terminal Functions C030 C028C031 C032C052 C047C053 C054C077 C076C078 C081C103 C102C104 C105C148 C147C149 C150FWD, REV AnlgPidc DWNSF2 SF1SF3 SF4255 Run Signal When the inverter is in Run Mode LOG2 LOG1LOG3 MO1 C039MO2 MO3Motor Constants Functions PM Motor Constants Functions H113 H112H116 H117Expansion Card Functions P044 P041P045 P046P073 P072P075 P077Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Error Name Descriptions Code Restoring Factory Default SettingsOther indication Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations Introduction Functional Safety Certification in ProgressStop Category defined in EN60204-1 How it worksInstallation Wiring example OFF G9SX GS9ANE1A