Hitachi hitachi series inverter user manual Unattended Start Protection, Usp

Page 36

Unattended Start Protection

If the Run command is already set when power is turned ON, the inverter starts running immediately after powerup. The Unattended Start Protection (USP) function prevents that automatic startup, so that the inverter will not run without outside intervention. When USP is active and you need to reset an alarm and resume running, either turn the Run command OFF, or perform a reset operation by the terminal [RS] input or the keypad Stop/reset key.

In the figure below, the [USP] feature is enabled. When the inverter power turns ON, the motor does not start, even though the Run command is already active. Instead, it enters

the USP trip state, and displays E 13 error code. This requires outside intervention to reset the alarm by turning OFF the Run command per this example (or applying a reset). Then the Run command can turn ON again and start the inverter output.

 

Run command [FW,RV]

1

 

 

 

 

 

 

 

0

 

 

 

 

 

[USP] terminal

1

 

 

 

 

 

 

 

0

 

 

 

 

 

Alarm output terminal

1

 

 

 

 

 

 

 

0

 

 

 

 

 

Inverter output frequency

0

 

 

 

 

 

 

 

 

 

 

 

 

Inverter power supply

1

 

 

 

 

 

 

 

0

 

 

 

t

 

 

Events:

 

E13

Alarm

Run

 

 

 

 

 

 

 

cleared

command

 

 

 

 

 

 

 

Option

Terminal

Function Name

State

 

Description

 

Code

Symbol

 

 

 

 

 

 

 

 

13

USP

Unattended Start

 

ON

On powerup, the inverter will not resume a Run

 

 

 

Protection

 

 

command (mostly used in the US)

 

 

 

 

 

OFF

On powerup, the inverter will resume a Run

 

 

 

 

 

 

command that was active before power loss

 

 

 

C001 C007

 

Example (default input configuration shown see

 

 

 

~

 

 

page 66):

 

 

 

(none)

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

USP

 

Note that when a USP error occurs and it is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

canceled by a reset from a [RS] terminal input, the

 

7

6

5

4

3

2

1

L

PLC

P24

 

 

inverter restarts running immediately.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Even when the trip state is canceled by turning

the terminal [RS] ON and OFF after an under

 

 

 

 

voltage protection E09 occurs, the USP function

 

 

will be performed.

See I/O specs on page 21,22.

When the running command is active immediately

 

 

after the power is turned ON, a USP error will

 

 

occur. When this function is used, wait for at least

 

 

three (3) seconds after the powerup to generate a

 

 

Run command.

 

 

34

Image 36
Contents WJ200 Series Inverter Quick Reference Guide Page Marking Requirements UL→ Cautions, Warnings and InstructionsTerminal symbols and Screw size Fuse Sizes Inverter Specification Label 5AT 123 45A-001 1005WJ200 Inverter Specifications Model-specific tables for 200V and 400V class invertersWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Basic System Description GFIInverter + Determining Wire and Fuse Sizes Motor OutputAllowable current Wire the Inverter Input to a Supply T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3RB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Using the Front Panel Keypad Key and Indicator LegendPower LED Alarm LED Keys, Modes, and Parameters Keypad Navigation MapPRG LED Group d Group FSave Group aF001 Key Connecting to PLCs and Other Devices GNDExample Wiring Diagram MotorControl Logic Signal Specifications PulseTrain Output InputWiring sample of control logic terminal sink logic SP, SNWire size for control and relay terminals Sink/source logic of intelligent input terminalsRecommended ferrule Intelligent Terminal Listing Intelligent InputsIntelligent Outputs Using Intelligent Input Terminals Sink logic connectionSource logic connection Sinking Inputs, Internal Supply WJ200Sourcing Inputs, Internal Supply Sinking Inputs, External Supply Sourcing Inputs, External SupplyInserting OFFForward Run/Stop and Reverse Run/Stop Commands Option Terminal Code Symbol Function Name State DescriptionRequired settings Multi-Speed Select ~Binary OperationTwo Stage Acceleration and Deceleration FW,RV2CH Option Terminal Function Name State Description Code Symbol Unattended Start ProtectionUSP Reset Inverter Using Intelligent Output Terminals Run SignalCode Symbol Option Terminal Function NameFrequency Arrival Signals SettingsRequired FA2/FA4 FA3/FA5Alarm Signal StopTrip During normal operation Analog Input Operation AM H O OI LAM H O OI Other Analog Input-related topics Pulse Train Input Operation SN 7 6 5 4 3 2 1 L PLC P24Analog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D006 D007D008 D009D029 D030D050 D060Main Profile Parameters Standard Functions A015 A220A241 A021 ~ A035A242 A043A243 A044A058 A059A061 A261A072 A073A074 A075A092 A292A093 A293A131 A132A141 A142A156 A157A161 A162Fine Tuning Functions B012 B212B013 B213B025 B026B027 B028B037 B038B039 B040B060 B061B062 B063B087 B088B089 B090B096 B097B100 B101B133 B134B145 B150Intelligent Terminal Functions C028 C030C031 C032C047 C052C053 C054C076 C077C078 C081C102 C103C104 C105C147 C148C149 C150Anlg FWD, REVPidc DWNSF1 SF2SF3 SF4255 Run Signal When the inverter is in Run Mode LOG1 LOG2LOG3 C039 MO1MO2 MO3Motor Constants Functions PM Motor Constants Functions H112 H113H116 H117Expansion Card Functions P041 P044P045 P046P072 P073P075 P077Monitoring Trip Events, History, & Conditions Trip History and Inverter StatusError Codes Error Name Causes CodeE37 Restoring Factory Default Settings Error Name Descriptions CodeOther indication CE-EMC Installation Guidelines Important notesPage Page Installation for WJ200 series example of SF models Metal plate earthHitachi EMC Recommendations Functional Safety Certification in Progress IntroductionStop Category defined in EN60204-1 How it worksInstallation Wiring example OFF GS9A G9SXNE1A