Hitachi hitachi series inverter user manual LOG1, LOG2, LOG3

Page 78

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Option

 

 

Terminal

 

 

Function Name

 

 

 

 

Description

 

 

 

 

 

Code

 

 

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

 

 

ZS

 

 

Zero Hz Speed

 

ON

Output frequency falls below the threshold

 

 

 

 

 

 

 

 

Detection Signal

 

 

specified in C063

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Output frequency is higher than the threshold

 

 

 

 

 

 

 

 

 

 

 

 

specified in C063

 

 

 

 

 

 

 

22

 

 

DSE

Speed Deviation

 

ON

Deviation of speed command and actual speed

 

 

 

 

 

 

 

 

Excessive

 

 

exceeds the specified value P027.

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Deviation of speed command and actual speed

 

 

 

 

 

 

 

 

 

 

 

 

does not exceed the specified value P027.

 

 

23

 

 

POK

Positioning Completion

 

ON

Positioning is completed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Positioning is not completed

 

 

 

 

 

24

 

 

FA4

 

Frequency Arrival Type

 

ON

When output to motor is at or above the set freq.,

 

 

 

 

 

 

 

 

4–Over frequency

 

 

 

C045

) or decel (

C046

) ramps

 

 

 

 

 

 

 

 

 

 

 

 

even if in accel (

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

When output to motor is OFF, or at a level below

 

 

 

 

 

 

 

 

 

 

 

 

the set frequency

 

 

 

 

 

 

 

25

 

 

FA5

 

Frequency Arrival Type

 

ON

When output to motor is at the set frequency,

 

 

 

 

 

 

 

 

5–Set frequency

 

 

during accel (

C045

 

C046

).

 

 

 

 

 

 

 

 

 

 

 

 

 

) and decel (

 

 

 

 

 

 

 

 

 

 

 

 

OFF

When output to motor is OFF, or is not at a level of

 

 

 

 

 

 

 

 

 

 

 

 

the set frequency

 

 

 

 

 

 

 

26

 

 

OL2

 

Overload Advance

 

ON

When output current is more than the set

 

 

 

 

 

 

 

 

Notice Signal 2

 

 

threshold (C111) for the overload signal

 

 

 

 

 

 

 

 

 

 

 

OFF

When output current is less than the set threshold

 

 

 

 

 

 

 

 

 

 

 

 

for the deviation signal

 

 

 

 

 

27

 

 

ODc

Analog Voltage Input

 

ON

When the [O] input value < B070 setting (signal

 

 

 

 

 

 

 

 

Disconnect Detection

 

 

loss detected)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

When no signal loss is detected

 

 

 

 

 

28

 

 

OIDc

Analog Current input

 

ON

When the [OI] input value < B071 setting (signal

 

 

 

 

 

 

 

 

Disconnect Detection

 

 

loss detected)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

When no signal loss is detected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31

 

 

FBV

PID Second Stage

 

ON

Transitions to ON when the inverter is in RUN

 

 

 

 

 

 

 

 

Output

 

 

Mode and the PID Process Variable (PV) is less

 

 

 

 

 

 

 

 

 

 

 

 

than the Feedback Low Limit (C053)

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Transitions to OFF when the PID Process Variable

 

 

 

 

 

 

 

 

 

 

 

 

(PV) exceeds the PID High Limit (C052), and

 

 

 

 

 

 

 

 

 

 

 

 

transitions to OFF when the inverter goes from

 

 

 

 

 

 

 

 

 

 

 

 

Run Mode to Stop Mode

 

 

 

 

 

32

 

 

NDc

 

Network Disconnect

 

ON

When the communications watchdog timer (period

 

 

 

 

 

 

 

 

Detection

 

 

specified by C077) has time out

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

When the communications watchdog timer is

 

 

 

 

 

 

 

 

 

 

 

 

satisfied by regular communications activity

 

 

33

 

 

LOG1

Logic Output Function 1

 

ON

When the Boolean operation specified by C143

 

 

 

 

 

 

 

 

 

 

 

OFF

has a logical “1” result

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the Boolean operation specified by C143

 

 

 

 

 

 

 

 

 

 

 

 

has a logical “0” result

 

 

 

 

 

34

 

 

LOG2

Logic Output Function 2

 

ON

When the Boolean operation specified by C146

 

 

 

 

 

 

 

 

 

 

 

OFF

has a logical “1” result

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the Boolean operation specified by C146

 

 

 

 

 

 

 

 

 

 

 

 

has a logical “0” result

 

 

 

 

 

35

 

 

LOG3

Logic Output Function 3

 

ON

When the Boolean operation specified by C149

 

 

 

 

 

 

 

 

 

 

 

OFF

has a logical “1” result

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the Boolean operation specified by C149

 

 

 

 

 

 

 

 

 

 

 

 

has a logical “0” result

 

 

 

 

 

39

 

 

WAC

 

Capacitor Life Warning

 

ON

Lifetime of internal capacitor has expired.

 

 

 

 

 

 

 

 

Signal

 

OFF

Lifetime of internal capacitor has not expired.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

76

Image 78
Contents WJ200 Series Inverter Quick Reference Guide Page Marking Requirements UL→ Cautions, Warnings and InstructionsTerminal symbols and Screw size Fuse Sizes Inverter Specification Label 5AT 123 45A-001 1005WJ200 Inverter Specifications Model-specific tables for 200V and 400V class invertersWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Basic System Description GFIInverter + Determining Wire and Fuse Sizes Motor OutputAllowable current Wire the Inverter Input to a Supply T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3RB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Using the Front Panel Keypad Key and Indicator LegendPower LED Alarm LED Keys, Modes, and Parameters Keypad Navigation MapPRG LED Save Group dGroup F Group aF001 Key Connecting to PLCs and Other Devices GNDExample Wiring Diagram MotorTrain Control Logic Signal SpecificationsPulse Output InputWiring sample of control logic terminal sink logic SP, SNWire size for control and relay terminals Sink/source logic of intelligent input terminalsRecommended ferrule Intelligent Terminal Listing Intelligent InputsIntelligent Outputs Using Intelligent Input Terminals Sink logic connectionSource logic connection Sinking Inputs, Internal Supply WJ200Sourcing Inputs, Internal Supply Sinking Inputs, External Supply Sourcing Inputs, External SupplyInserting OFFForward Run/Stop and Reverse Run/Stop Commands Option Terminal Code Symbol Function Name State DescriptionRequired settings Multi-Speed Select ~Binary OperationTwo Stage Acceleration and Deceleration FW,RV2CH Option Terminal Function Name State Description Code Symbol Unattended Start ProtectionUSP Reset Inverter Code Symbol Using Intelligent Output TerminalsRun Signal Option Terminal Function NameFrequency Arrival Signals SettingsRequired FA2/FA4 FA3/FA5Alarm Signal StopTrip During normal operation Analog Input Operation AM H O OI LAM H O OI Other Analog Input-related topics Pulse Train Input Operation SN 7 6 5 4 3 2 1 L PLC P24Analog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D008 D006D007 D009D050 D029D030 D060Main Profile Parameters Standard Functions A241 A015A220 A021 ~ A035A243 A242A043 A044A061 A058A059 A261A074 A072A073 A075A093 A092A292 A293A141 A131A132 A142A161 A156A157 A162Fine Tuning Functions B013 B012B212 B213B027 B025B026 B028B039 B037B038 B040B062 B060B061 B063B089 B087B088 B090B100 B096B097 B101B145 B133B134 B150Intelligent Terminal Functions C031 C028C030 C032C053 C047C052 C054C078 C076C077 C081C104 C102C103 C105C149 C147C148 C150Pidc AnlgFWD, REV DWN SF3 SF1 SF2 SF4255 Run Signal When the inverter is in Run Mode LOG1 LOG2LOG3 MO2 C039MO1 MO3Motor Constants Functions PM Motor Constants Functions H116 H112H113 H117Expansion Card Functions P045 P041P044 P046P075 P072P073 P077Monitoring Trip Events, History, & Conditions Trip History and Inverter StatusError Codes Error Name Causes CodeE37 Restoring Factory Default Settings Error Name Descriptions CodeOther indication CE-EMC Installation Guidelines Important notesPage Page Installation for WJ200 series example of SF models Metal plate earthHitachi EMC Recommendations Stop Category defined in EN60204-1 Functional Safety Certification in ProgressIntroduction How it worksInstallation Wiring example OFF GS9A G9SXNE1A