Hitachi hitachi series inverter C102, C103, C104, C105, C106, C109, C111, C130, C131, C132, C133

Page 72

 

 

 

 

 

 

 

 

 

 

Run

 

 

 

 

 

 

 

 

 

 

Func.

 

 

Name

 

 

Description

 

 

Mode

 

 

 

Initialdata

 

 

 

Units

 

 

Code

 

 

 

 

 

 

Edit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C102

 

Reset selection

 

Determines response to Reset

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

input [RS].

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Four option codes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00Cancel trip state at input signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON transition, stops inverter if

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in Run Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Cancel trip state at signal OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transition, stops inverter if in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Run Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02Cancel trip state at input ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transition, no effect if in Run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03Clear the memories only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

related to trip status

 

 

 

 

 

 

 

 

 

 

 

 

C103

 

Restart mode after reset

 

 

Determines the restart mode after

 

 

 

 

 

 

00

 

 

-

 

 

 

 

 

 

 

 

reset is given, three option codes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00Start with 0 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Start with freq. matching

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02Start with active freq. matching

 

 

 

 

 

 

 

 

 

 

 

 

C104

 

UP/DWN clear mode

 

 

Freq. set value when UDC signal is

 

 

 

 

 

 

00

 

 

-

 

 

 

 

 

 

 

 

given to the input terminal, two

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

option codes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

000 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Original setting (in the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EEPROM memory at power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on)

 

 

 

 

 

 

 

 

 

 

 

 

C105

 

EO gain adjustment

 

 

Set range is 50 to 200%

 

 

 

 

 

 

100.

 

 

%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C106

 

AM gain adjustment

 

 

Set range is 50 to 200%

 

 

 

 

 

 

100.

 

 

%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C109

 

AM bias adjustment

 

 

Set range is 0 to 100%

 

 

 

 

 

 

0.

 

 

%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C111

 

Overload warning level 2

 

Sets the overload warning signal

 

 

 

 

 

 

Rated current

 

 

 

A

 

 

 

 

 

 

 

 

level between 0% and 200% (from

 

 

 

 

 

 

x 1.15

 

 

 

 

 

 

 

 

 

 

 

 

0 to two time the rated current of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the inverter)

 

 

 

 

 

 

 

 

 

 

 

 

C130

 

Output [11] on delay

 

 

Set range is 0.0 to 100.0 sec.

 

 

 

 

 

 

0.0

 

 

 

Sec.

 

C131

 

Output [11] off delay

 

 

 

 

 

 

 

 

 

0.0

 

 

 

Sec.

 

C132

 

Output [12] on delay

 

 

Set range is 0.0 to 100.0 sec.

 

 

 

 

 

 

0.0

 

 

 

Sec.

 

C133

 

Output [12] off delay

 

 

 

 

 

 

 

 

 

0.0

 

 

 

Sec.

 

C140

 

Relay output on delay

 

 

Set range is 0.0 to 100.0 sec.

 

 

 

 

 

 

0.0

 

 

 

Sec.

 

C141

 

Relay output off delay

 

 

 

 

 

 

 

 

 

0.0

 

 

 

Sec.

 

C142

 

Logic output 1 operand A

 

 

All the programmable functions

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

available for logic (discrete) outputs

 

 

 

 

 

 

 

 

 

 

 

 

C143

 

Logic output 1 operand B

 

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

except LOG1 to LOG3, OPO, no

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C144

 

Logic output 1 operator

 

 

Applies a logic function to calculate

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

[LOG] output state,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three options:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00[LOG] = A AND B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01[LOG] = A OR B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02[LOG] = A XOR B

 

 

 

 

 

 

 

 

 

 

 

 

C145

 

Logic output 2 operand A

 

 

All the programmable functions

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

available for logic (discrete) outputs

 

 

 

 

 

 

 

 

 

 

 

 

C146

 

Logic output 2 operand B

 

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

except LOG1 to LOG3, OPO, no

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

Image 72
Contents WJ200 Series Inverter Quick Reference Guide Page Marking Requirements UL→ Cautions, Warnings and InstructionsTerminal symbols and Screw size Fuse Sizes Inverter Specification Label 5AT 123 45A-001 1005WJ200 Inverter Specifications Model-specific tables for 200V and 400V class invertersWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Basic System Description GFIInverter + Determining Wire and Fuse Sizes Motor OutputAllowable current Wire the Inverter Input to a Supply T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3RB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Using the Front Panel Keypad Key and Indicator LegendPower LED Alarm LED Keys, Modes, and Parameters Keypad Navigation MapPRG LED Group d Group FSave Group aF001 Key Connecting to PLCs and Other Devices GNDExample Wiring Diagram MotorControl Logic Signal Specifications PulseTrain Output InputWiring sample of control logic terminal sink logic SP, SNWire size for control and relay terminals Sink/source logic of intelligent input terminalsRecommended ferrule Intelligent Terminal Listing Intelligent InputsIntelligent Outputs Using Intelligent Input Terminals Sink logic connectionSource logic connection Sinking Inputs, Internal Supply WJ200Sourcing Inputs, Internal Supply Sinking Inputs, External Supply Sourcing Inputs, External SupplyInserting OFFForward Run/Stop and Reverse Run/Stop Commands Option Terminal Code Symbol Function Name State DescriptionRequired settings Multi-Speed Select ~Binary OperationTwo Stage Acceleration and Deceleration FW,RV2CH Option Terminal Function Name State Description Code Symbol Unattended Start ProtectionUSP Reset Inverter Using Intelligent Output Terminals Run SignalCode Symbol Option Terminal Function NameFrequency Arrival Signals SettingsRequired FA2/FA4 FA3/FA5Alarm Signal StopTrip During normal operation Analog Input Operation AM H O OI LAM H O OI Other Analog Input-related topics Pulse Train Input Operation SN 7 6 5 4 3 2 1 L PLC P24Analog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D006 D007D008 D009D029 D030D050 D060Main Profile Parameters Standard Functions A015 A220A241 A021 ~ A035A242 A043A243 A044A058 A059A061 A261A072 A073A074 A075A092 A292A093 A293A131 A132A141 A142A156 A157A161 A162Fine Tuning Functions B012 B212B013 B213B025 B026B027 B028B037 B038B039 B040B060 B061B062 B063B087 B088B089 B090B096 B097B100 B101B133 B134B145 B150Intelligent Terminal Functions C028 C030C031 C032C047 C052C053 C054C076 C077C078 C081C102 C103C104 C105C147 C148C149 C150Anlg FWD, REVPidc DWNSF1 SF2SF3 SF4255 Run Signal When the inverter is in Run Mode LOG1 LOG2LOG3 C039 MO1MO2 MO3Motor Constants Functions PM Motor Constants Functions H112 H113H116 H117Expansion Card Functions P041 P044P045 P046P072 P073P075 P077Monitoring Trip Events, History, & Conditions Trip History and Inverter StatusError Codes Error Name Causes CodeE37 Restoring Factory Default Settings Error Name Descriptions CodeOther indication CE-EMC Installation Guidelines Important notesPage Page Installation for WJ200 series example of SF models Metal plate earthHitachi EMC Recommendations Functional Safety Certification in Progress IntroductionStop Category defined in EN60204-1 How it worksInstallation Wiring example OFF GS9A G9SXNE1A