Hitachi hitachi series inverter Using Intelligent Output Terminals, Run Signal, Code Symbol

Page 38

Using Intelligent Output Terminals

 

Run Signal

 

 

 

 

 

When the [RUN] signal is selected as an

 

1

 

intelligent output terminal, the inverter outputs [FW,RV]

 

a signal on that terminal when it is in Run

 

0

 

 

 

 

Mode. The output logic is active low, and is

Output

B082

 

the open collector type (switch to ground).

start freq.

frequency

 

 

 

 

 

 

 

 

 

 

 

Run

 

ON

 

 

 

 

signal

 

t

 

 

 

 

 

 

Option

Terminal

Function Name

State

 

Description

Code

Symbol

 

 

 

 

 

 

00

RUN

Run Signal

ON

when inverter is in Run Mode

 

 

 

OFF

when inverter is in Stop Mode

 

 

11, 12, AL0 – AL2

 

Example for terminal [11] (default output

 

 

(none)

 

configuration shown see page 66):

Notes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The inverter outputs the [RUN] signal whenever

Inverter output

 

RUN

 

 

the inverter output exceeds the start frequency

terminal circuit

 

 

 

 

 

specified by parameter B082. The start frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is the initial inverter output frequency when it turns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CM2

 

 

 

 

11

 

The example circuit for terminal [11] drives a relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

coil. Note the use of a diode to prevent the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

negative going turn-off spike generated by the coil

 

 

 

 

 

 

 

RY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from damaging the inverter’s output transistor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example for terminal [AL0], [AL1], [AL2] (requires output configuration see page 66):

Inverter logic

RUN

circuit board

 

AL0

AL1 AL2

 

 

 

 

 

Power

 

 

 

 

Load

supply

 

 

 

 

 

 

 

 

 

See I/O specs on page 21,22.

36

Image 38
Contents WJ200 Series Inverter Quick Reference Guide Page Marking Requirements UL→ Cautions, Warnings and InstructionsTerminal symbols and Screw size Fuse Sizes Inverter Specification Label 5AT 123 45A-001 1005WJ200 Inverter Specifications Model-specific tables for 200V and 400V class invertersWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Inverter + Basic System DescriptionGFI Allowable current Determining Wire and Fuse SizesMotor Output Wire the Inverter Input to a Supply T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3RB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Power LED Alarm LED Using the Front Panel KeypadKey and Indicator Legend PRG LED Keys, Modes, and ParametersKeypad Navigation Map Save Group dGroup F Group aF001 Key Connecting to PLCs and Other Devices GNDExample Wiring Diagram MotorTrain Control Logic Signal SpecificationsPulse Output InputWiring sample of control logic terminal sink logic SP, SNWire size for control and relay terminals Sink/source logic of intelligent input terminalsRecommended ferrule Intelligent Terminal Listing Intelligent InputsIntelligent Outputs Source logic connection Using Intelligent Input TerminalsSink logic connection Sourcing Inputs, Internal Supply Sinking Inputs, Internal SupplyWJ200 Sinking Inputs, External Supply Sourcing Inputs, External SupplyInserting OFFForward Run/Stop and Reverse Run/Stop Commands Option Terminal Code Symbol Function Name State DescriptionRequired settings Multi-Speed Select ~Binary Operation2CH Two Stage Acceleration and DecelerationFW,RV USP Option Terminal Function Name State Description Code SymbolUnattended Start Protection Reset Inverter Code Symbol Using Intelligent Output TerminalsRun Signal Option Terminal Function NameRequired Frequency Arrival SignalsSettings FA2/FA4 FA3/FA5Trip Alarm SignalStop During normal operation AM H O OI Analog Input OperationAM H O OI L Other Analog Input-related topics Pulse Train Input Operation SN 7 6 5 4 3 2 1 L PLC P24Analog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D008 D006D007 D009D050 D029D030 D060Main Profile Parameters Standard Functions A241 A015A220 A021 ~ A035A243 A242A043 A044A061 A058A059 A261A074 A072A073 A075A093 A092A292 A293A141 A131A132 A142A161 A156A157 A162Fine Tuning Functions B013 B012B212 B213B027 B025B026 B028B039 B037B038 B040B062 B060B061 B063B089 B087B088 B090B100 B096B097 B101B145 B133B134 B150Intelligent Terminal Functions C031 C028C030 C032C053 C047C052 C054C078 C076C077 C081C104 C102C103 C105C149 C147C148 C150Pidc AnlgFWD, REV DWNSF3 SF1SF2 SF4255 Run Signal When the inverter is in Run Mode LOG3 LOG1LOG2 MO2 C039MO1 MO3Motor Constants Functions PM Motor Constants Functions H116 H112H113 H117Expansion Card Functions P045 P041P044 P046P075 P072P073 P077Monitoring Trip Events, History, & Conditions Trip History and Inverter StatusError Codes Error Name Causes CodeE37 Other indication Restoring Factory Default SettingsError Name Descriptions Code CE-EMC Installation Guidelines Important notesPage Page Installation for WJ200 series example of SF models Metal plate earthHitachi EMC Recommendations Stop Category defined in EN60204-1 Functional Safety Certification in ProgressIntroduction How it worksInstallation Wiring example OFF NE1A GS9AG9SX