Conair GB/ WSB manual Normal Operating Sequence

Page 82

NORMAL OPERATING SEQUENCE

This section tells you how the system is supposed to work. If your system is not operating correctly, this description may help you spot exactly where the system is failing, providing a clue to the problem.

Turn POWER ON:

The following displays occur for 1 second each: Program version date (V=21031A), the check sum number (CKS XXXX), ROM check (ROM OK ), RAM size, (RAM = 8K), Model number

(MODEL220), display of (

0.0), actual

weight in

the bin

is displayed last. It should be close to

0.0, plus

or minus

several grams.

 

 

 

BEGIN operation:

The unit will begin to operate if both switches on the left side are UP in the CONTINUE position and the SENSOR in the mix chamber is UNCOVERED. The sensor must be plugged into the right side of the controller. If it is not, this has the same effect as the sensor being covered; the unit will not run. If the sensor LED (on the sensor) is on, the sensor thinks it is covered. If it is sensing incorrectly, adjust the sensitivity. See ADJUSTMENTS.

If the WEIGH BIN DUMP Flap opens and closes repeatedly:

If initial empty bin TARE weight is 100 grams or more, the weigh bin dump valve will operate in an attempt to empty the bin and bring the starting weight closer to zero. If the bin is empty but the weight reading is greater than 100 grams then something is wrong. See TESTING the LOAD CELLS and LOAD CELL CALIBRATION.

If the ALARM flashes:

If the initial TARE weight is below -50 grams the Alarm will flash and the unit will not operate. go to TESTING of LOAD CELLS and LOAD CELL CALIBRATION.

The DISPENSE sequence begins:

If initial tare weight is within limits, between -50 and +100, the sequence will begin.

DISPLAY during dispenses:

During all dispenses, the letter R, N, C, or A will be displayed indicating which component is being dispensed. The INITIAL display is the tare weight of the bin. This will not change during the dispense. Tree seconds after each dispense, the new total weight of the material in the bin is updated and displayed.

REGRIND first:

If REGRIND has been requested the REGRIND dispense will occur first. The letter "R" will appear in the display. After this dispense an exact weight is taken to determine the space remaining in the weigh bin for the remaining dispenses. The weight of REGRIND dispensed will appear in the display 3 seconds AFTER the dispense has ended.

Page 83

Image 82
Contents Gravimetric Blenders Date Manual Number UGB006/1103 Serial numbers Model numbers Four Component Software Part Troubleshooting / SoftwarePart Hardware Maintenance Part OperationSpecial Features Assembly InstructionsCheck OUT Procedure Proceed to Safety Hazards NextProceed to Assembly Next Safety Hazards MIX BladesSafety Features Safety Interlock Switch Additional MIX Blade HazardDisclaimers Please Be Careful Part AssemblyLoad Cells are Easily Damaged On the NextPage Wiring Considerations Proceed to Check OUT Procedure NextAT this Point Procedure What should Happen Plug in ControllerTurn Power on Touch Weigh BIN Very LightlyLED # Press Alarm KEYPress REG KEY Press NAT KEYPage Password ExitCAL OFF Part Operation Load Cell CalibrationBe Sure CALOperate Proceed to Normal Operation NextOper COLGB/WSB MB Selected Models Special InstructionsMicro Pulse GB/WSB 240RPower on If Problems DevelopPower OFF Instructions for Normal OperationNormal Operating Sequence Each Cycle Exit Regrind Eight Character Display ROM OKAlarm Silence Right Column AlarmsStrobe Light and Beeper Alarms LED LightsMixer Motor Outlet Mixer Motor ON/OFF/TIMED SwitchMixer Motor Fuse Internal Fuses KeypadDate RUN Keypad Automatic Operation ModeRecipe RCPBtch SaveTABLE, FLG Page Fast TAGKeypad Manual Mode ALLTimed Time ADDPage Keypad Program Mode Star Functions ParaYLD Ctrl Page Page Page Page Page Page Page Page Parameter List Brief Explanations ParametersMIX Time XXX RLO Page CPL Full Explanation of Parameters No ALARM, no Retries MPOMIX KDF / WDF BERPage ROV Page Example RHL is Set 10 percent Page Setting SETPage Page Page Page Page TCV + TRC XCV + XRCXTP XAL XULLIQ PTDMCT Page APO Parameter Default Settings Four SoftwareFLG RPO NPO CPO MPO RAL NAL CAL AAL MIX JOGNWT NPT CPT APT RWTRTI NTIChanging Parameters REG Natural COL Prnt OFFPrnt TotalFinal DISP,% What to Check for Page Page Page Time Natural Special TestsTime Calibrate NaturalDate Time Totals Grand PCT Current Material Usage InformationPARAMETER, PRT Cycles Last Printed 11/01/90Part IV Troubleshooting What to do Increasing Throughput Typical Problems Page Normal Operating Sequence Material Runs OUT Verifying Load Cell Function CNT OFF Load Cell RAW Signal ReadoutCNT Results to Expect Clear ALL Restart Clear RoutineCore Dump Weigh BIN Dump Valve Soft Close Clean OUT Issues MIX Problems Page Wait Recalibration of Load CellsZero FullLoad Cells Blender Preventive MaintenanceDispense Gates Weigh BinsThese Instructions for Totalizers only Blender Special Totalizer FunctionStop END of Cycle TotalizeComputer Outputs Wiring Supplement Call Appendix A-2 Specifications Gravimetric Batch Blenders Autoweigh GBM Series ModelsGravimetric Batch Blenders AutoWeigh GB100 Series Models TOP View Front View Side View120V/1 phase/50-60 Hz 240V/1 phase/50-60 Hz Gravimetric Batch Blenders GB 220 and 420 ModelsGravimetric Batch Blenders AutoWeigh GB240 and GB440 Models TOP View Mounting InterfaceGravimetric Batch Blenders AutoWeigh GB900 Series Models 2124Gravimetric Batch Blenders AutoWeigh GB1840 and 1860 Models GB1840 GB1860Gravimetric Batch Blenders Wsbm Series models Control Remote Mounted Models WSBM22 WSBM131 WSBM140Gravimetric Batch Blenders WSB 100 and 100R Models Side View Front View Side View, R Model Front View, R ModelGravimetric Batch Blenders WSB 220 and 420 Models 24.4Gravimetric Batch Blenders WSB 240/440 and 240/440R Models WSB442Gravimetric Batch Blenders WSB 1840, 1850 and 1860 Models Appendix C Appendix C Appendix C Appendix C Appendix C Appendix C Appendix C Appendix C