Available Power (Continued)

Accessory Connector (J2)

The D128 Dual Phone Line Switcher connects to J2.

Expansion Port (J4)

The Expansion Port is reserved for future use.

Continuous Power Outputs

Terminals

3

24

J2

Continuous Current Draw

32

J4

The continuous current draw for powered devices connected to terminals 3, 8, 24, and 32, the Expansion Port (J4), and the Accessory Connector (J2) must not exceed 1.4A . Devices powered from these outputs must operate over a range of 10.2 VDC to 13.9 VDC.

Power restricted for fire and combined fire/burglary systems: Use the Fire System Power Formula to calculate the current available for fire and combined fire/burglary systems. See Programmable Power Outputs.

 