Line Termination

If there is no D8125 POPEX module connected to ZONEX 1, terminals 27 and 28, set switch 12 on only one OctoPOPIT connected to those terminals to the on position.

If there is a D8125 POPEX module connected to ZONEX 1, terminals 27 and 28, set switch 12 on all OctoPOPITs connected to those terminals to the off position.

If there is no D8125 POPEX module connected to ZONEX 2, terminals 26 and 25, set switch 12 on only one OctoPOPIT connected to those terminals to the on position.

If there is a D8125 POPEX module connected to ZONEX 2, terminals 26 and 25, set switch 12 on all OctoPOPITs connected to those terminals to the off position.

See Figure 16 for the location of the switches on the OctoPOPIT.

 

D9112 Operation & Installation Manual

 

74-06144-000-C 2/96

Page 44

© 1993-1996 Radionics

Page 44
Image 44
Bosch Appliances D9112 installation manual Line Termination