Current Rating Chart for Standby Battery Calculations
|
| AC Power On | AC Power Off | In Alarm |
| ||
|
| Normal Current | Minimum Current | Maximum Current | |||
Model | Number | Each | Each | Each |
| ||
Number | Used | Unit | Total | Unit | Total | Unit | Total |
D9112 | ____ |
| 250 x 1 = 250 |
| 250 x 1 = 250 | 500 x 1 = 500 | |
D125B | ____ | 20 X Quan.= ____ | 19 x Quan.= ____ | 123 x Quan.= ____ | |||
D127 | ____ | 13 x Quan.= ____ | 12 x Quan.= ____ | 45 x Quan.= ____ | |||
D128 | ____ | 14 x Quan.= ____ | 14 x Quan.= ____ | 45 x Quan.= ____ | |||
D129 | ____ | 25 x Quan.= ____ | 25 x Quan.= ____ | 26 x Quan.= ____ | |||
D192C | ____ | 15 x Quan.= ____ | 26 x Quan.= ____ | 50 x Quan.= ____ | |||
D1255 | ____ | 104 x Quan.= ____ | 106 x Quan.= ____ | 206 x Quan.= ____ | |||
D720 | ____ | 55 x Quan.= ____ | 20 x Quan.= ____ | 75 x Quan.= ____ | |||
D8125 | ____ | 48 x Quan.= ____ | 48 x Quan.= ____ | 48 x Quan.= ____ | |||
D8127 | ____ | 3 x Quan.= ____ | 3 x Quan.= ____ | 4 x Quan.= ____ | |||
D8128A | ____ | 50 x Quan.= ____ | 50 x Quan.= ____ | 50 x Quan.= ____ | |||
D8129 | ____ | 20 x Quan.= ____ | 20 x Quan.= ____ | 20 x Quan. + 25 x | |||
|
|
|
|
|
| # relays = ____ | |
D8130 | ____ | 5 x Quan.= ____ | 5 x Quan.= ____ | 54 x Quan.= ____ | |||
D9131 | ____ | 24 x Quan.= ____ | 22 x Quan.= ____ | 36 x Quan.= ____ | |||
Ratings of other devices in the system which are not shown above: |
|
| |||||
____ | ____ | ___ x Quan.= ____ | ___ x Quan.= ____ | ___ x Quan.= ____ | |||
____ | ____ | ___ x Quan.= ____ | ___ x Quan.= ____ | ___ x Quan.= ____ | |||
____ | ____ | ___ x Quan.= ____ | ___ x Quan.= ____ | ___ x Quan.= ____ | |||
____ | ____ | ___ x Quan.= ____ | ___ x Quan.= ____ | ___ x Quan.= ____ | |||
|
| Total A = ____ | Total B = ____ | Total C1= ____ |
Currents shown in milliamperes (1 ampere=1000 milliamperes).
1If the column C total exceeds 1900 mA, a D8132 is required to provide an additional 1400 mA. You may also use a UL listed external power supply for this purpose.
| D9112 Operation & Installation Manual |
|