Quick Reference Terminal Description
| Terminal | Name | Description |
|
| 1, 2 | CLASS 2 | Connect 16.5 VAC, 40 VA transformer for primary power supply. |
|
|
| TRANSFORMER |
|
|
|
|
|
|
|
| 3 | +AUX POWER | Supplies up to 1.4A at 10.0 VDC to powered devices. Use terminal 9 for common. |
|
| Shares circuit breaker with terminal 24 and the Expansion Port (J4). |
| ||
|
|
|
| |
| 4 | BATTERY | Connect 12V, 7Ah rechargeable lead acid type battery’s negative terminal |
|
| NEGATIVE ONLY | terminal 4. |
| |
|
|
| ||
|
|
|
| |
| 5 (+) | BATTERY | Connect 12V, 7Ah rechargeable lead acid type battery’s positive terminal (+). |
|
| POSITIVE ONLY |
| ||
| 6 (+) | + STEADY OR | Supplies up to 2 A at 10.0 VDC to 13.9 VDC for steady or pulsed alarm output. |
|
| Use terminal 9 for common. Programmed as Relay A. |
| ||
|
| PULSED |
| |
|
| Shares circuit breaker with terminals 7 and 8. |
| |
|
|
|
| |
|
| + ALTERNATE | Supplies up to 2 A at 10.0 VDC to 13.9 VDC for steady or pulsed alarm output. |
|
| 7(+) | Use terminal 9 for common. Programmed as Relay B. |
| |
|
|
| ||
|
|
| Shares circuit breaker with terminals 6 and 8. |
|
|
|
| D136 |
|
|
| + SWITCHED | Supplies up to 1.4 Amps at 10.0 VDC to 13.9 VDC . Use terminal 9 for common. |
|
|
| Programmed as Relay C |
| |
| 8 (+) | AUX POWER |
| |
|
| Continuous output interruptedby CMD 47 or alarm verification. |
| |
|
|
|
| |
|
|
| Shares circuit breaker with terminals 6 and 7. |
|
|
|
| D136 |
|
|
|
| 8. |
|
| 9 | COMMON | Terminal 9 is common for Auxilliary Power, Alternate Alarm Power, and Switched |
|
| Aux Power (terminals 3, 6, 7 and 8). |
| ||
|
|
|
| |
| 10 | EARTH GROUND | Connect to earth ground. A cold water pipe or grounding rod is preferred. |
|
|
| Do not connect to telephone or electrical ground. |
| |
|
|
|
| |
| 11, 13, 14, 16, 17, | Connect normally open and/or normally closed detection devices to loop wiring. |
| |
| 19, 20, 22 | POINTS (inputs) | 1 k Ω resistor required at end of loop. |
|
|
|
| ||
| 12, 15, 18, 21 | Loop returns for |
| |
| POINTS |
| ||
|
| (common) |
|
|
| 23 | ZONEX COMMON | Use terminals 23 and 24 to power ZONEX modules such as the D8125 POPEX |
|
| 24 (+) | module, the D8128A OctoPOPIT, and the D8129 OctoRelay. Shares circuit |
| |
| ZONEX POWER + |
| ||
|
| breaker with terminal 3 and the Expansion Port (J4). |
| |
|
|
|
| |
| 25 | ZONEX IN 2 | Connect ZONEX modules for points 73 to 135 and relays 65 to 128 to these |
|
| 26 | ZONEX OUT 2 | terminals. |
|
|
|
| ||
| 27 | ZONEX IN 1 | Connect ZONEX modules for points 9 to 71 and relays 1 to 64 to these terminals. |
|
| 28 | ZONEX OUT 1 |
|
|
| 29 | COMMON | Common terminal for SDI devices |
|
| 30 | DATA BUS B | Terminals 30 and 31 are a two wire bus that drives the command centers, printer |
|
| 31 | DATA BUS A | interface, and other SDI devices. |
|
|
|
| ||
|
|
| Power for command centers, printer interface and other SDI devices. This |
|
| 32 (+) | POWER + | separate protected power output for SDI devices is not affected by shorts on any |
|
|
|
| other terminal. |
|
| D9112 Operation & Installation Manual |
|
Page 60 | © |