D9112 Operation & Installation Manual
Page 874-06144-000-C 2/96 © 1993-1996 Radionics
Areas and Accounts
The D9112 supports up to eight separate areas. You can assign all points to a single
area or spread them out over up to eight areas.
You arm and disarm the D9112 panel by area. You can arm and disarm several areas
with one menu function. You can also assign a passcode an authority level that allows a
user to arm an area from a remote command center in another area. Assigning each
area its own account number creates eight separate accounts in one D9112 panel.
Assigning the same account number to different areas, groups them together in a single
account.
Area options include: exit tone and delay, separate fire and burglary outputs, and multiple
opening and closing windows.
Communicator
The Radionics D9112 Control/Communicator panel uses a built-in digital communicator
to send reports to the receiver. The panel transmits reports in either the Modem II or
BFSK format. Your D6500 receiver's MPU and line cards must have software revision
6.00 (or greater) installed to accept Modem II reports from the D9112. Power your
receiver down and up to print the software revision numbers.
The D9112 connects to an RJ31X jack for phone line seizure. Connection to the RJ31X
complies with FCC regulations for using the public telephone network. You can program
the panel to direct reports to four separate phone numbers. Adding the D128 Dual Phone
Line Switcher module allows you to connect and supervise a second phone line.
D1255 Alpha III Command Center
The D1255 Alpha III Command Center offers complete system control and annunciation.
The D1255 features an illuminated keypad, a 16-character English language display, and
a built-in speaker that offers several distinct warning tones. Switches on the D1255
assign an address (1 to 8) to the command center. You assign addresses to areas in the
Command Center Assignments section of the program.
You can connect a maximum of 32 command centers to the D9112. The available power,
number of supervised command centers, and number of areas you intend to use, affect
the total number of command centers you can connect to the D9112.
The D9112 can supervise up to 8 command centers. The panel transmits a serial device
trouble report, SDI FAILURE in the Modem II format or TROUBLE ZN D in the BFSK
format, if it loses communication with a supervised command center. You can add more
command centers but only eight can be supervised. See Command Center in the D9112
Program Entry Guide (74-06145-000) for complete details on command center options.
Keyswitch
You can arm and disarm any of the eight available areas with maintained or momentary
closure devices such as keyswitches. Keyswitches connect to points. Point programming
determines which area a keyswitch controls. See Options in the Point Index Parameters
module of the D9112 Program Entry Guide (74-06145-000).