Standby Battery Requirements

Household Burglary and Commercial Burglary

Four hours of standby battery capacity required.

Central Station or Local Fire Alarm

24 hours of standby plus 5 minutes of alarm operation required. See
Central Station or Local
Systems Ampere-Hour Calculation Formula
in the
Standby Battery Calculation for NFPA 72
Fire Alarm Applications
section.

Remote Station or Auxiliary Fire Alarm

60 hours of standby plus 5 minutes of alarm operation required. See
Remote Station or
Auxiliary System Ampere-Hour Calculation Formula
in the
Standby Battery Calculation for
NFPA 72 Fire Alarm Applications
section.

Household Fire Warning Equipment

24 hours of standby plus 4 minutes of alarm operation required. See
Household Fire Ampere-
Hour Calculation Formula
in the
Standby Battery Calculation for NFPA 72 Fire Alarm
Applications
section.