Standby Battery Requirements

Household Burglary and Commercial Burglary

Four hours of standby battery capacity required.

Central Station or Local Fire Alarm

24 hours of standby plus 5 minutes of alarm operation required. See Central Station or Local Systems Ampere-Hour Calculation Formula in the Standby Battery Calculation for NFPA 72 Fire Alarm Applications section.

Remote Station or Auxiliary Fire Alarm

60 hours of standby plus 5 minutes of alarm operation required. See Remote Station or Auxiliary System Ampere-Hour Calculation Formula in the Standby Battery Calculation for NFPA 72 Fire Alarm Applications section.

Household Fire Warning Equipment

24 hours of standby plus 4 minutes of alarm operation required. SeeHousehold Fire Ampere- Hour Calculation Formula in the Standby Battery Calculation for NFPA 72 Fire Alarm Applications section.

 