Programmable Power Outputs

Terminals

6

7

8

Programming

The power outputs at terminals 6, 7, and 8 are programmed as relays A, B, and C. All relays are programmed in the Relays module of the program. Relays are assigned a relay type, Fire Bell for example, when they are assigned to an area. Relays can be assigned to one or more areas.

The Radionics defaults set relay A (terminal 6) as an Alarm Bell output, relay B (terminal

7)as a Fire Bell output, and relay C (terminal 8) as a Verification/Reset output. The D9112 Program Entry Guide (74-06145-000) contains complete instructions for programming relays. Descriptions of the functional characteristics of each terminal appear on the next page.

See the Bell Parameters section of the program to set the Fire Bell, Alarm Bell output responses for relays. Four annunciation patterns: Steady, Pulsed, California Standard, and Temporal Code 3 are available.

Unexpected Output at Terminals 6, 7 and 8: If terminals 6, 7, and 8 don’t provide the output you expect:

Check the programming for relays A, B, and C in the Relays module of the program.

Check the Bell Parameters section of the program to verify the Alarm and Fire Bell responses are programmed for the duration and pattern you expect.

Check the Point Assignments to verify each point is programmed for the local response you expect.

Optional Relays Required

Install an optional D136 plug-in relay into socket J1 to enable the output at terminal 7. Install a D136 in socket J9 to enable the output at terminal 8. The relay sockets are under the faceplate as shown in Figure 5.

Relay Installation

Power down the D9112 before inserting the D136 relays. The plug- in relays are shorter than the sockets they plug into. See Figure

5.You can install them in either the left or right end of the socket.

Don’t rely on relay labelling: You shouldn’t rely on the labelling to install D136 relays. Check for the side with three pins. The three pins go on the top side.

Incorrect insertion does not damage the relay or the D9112, however the related circuits do not function properly.

M Aromat

DS2E-M-DC12V

K6

M Aromat

DS2E-M-DC12V

J1

J9

M Aromat

DS2E-M-DC12V

GND START

J1

J9

Figure 5: Relays for Terminals 7 and 8

 

D9112

Operation & Installation Manual

 

 

© 1993 Radionics

74-06144-000-C 2/96

Page 25

Page 25
Image 25
Bosch Appliances D9112 Programmable Power Outputs Terminals, Programming, Optional Relays Required, Relay Installation