Programmer and Accessory Connections
Programmer Connector (J7)
The procedure below shows you how to connect and disconnect the programmer. Refer to D5200 Programmer Operation Manual
1.Panel is operational during programming: Except when the programmer is sending or receiving, the D9112 is functional while the programmer is connected to it. It will transmit reports as programmed.
Locking Reset Speeds Programming: If you have supervised command centers or other supervised devices connected to the Data Bus (terminals
30 and 31), locking the Reset Pin will speed communication between the panel and the D5200.
Radionics recommends that you lock the Reset Pin in the DISABLE position to prevent
reports from being transmitted while you are programming. See Figure 21.
GRN
RESET PIN
LOCKED (CLOSED)
Reset Pin
Disable All Except Battery
Charging And Local Programming
SDI DEVICE WIRING |
| |
RED | POWER + | 32 |
YELLOW | DATA BUS A | 31 |
GREEN | DATA BUS B | 30 |
BLACK | COMMON - | 29 |
RESET PIN
NORMAL (OPEN)
Figure 21: Reset Pin
2.Plug the D5200 Data/Power cord into the programmer connector (J7).
3.Advance the D5200 display to a D9112 product handler. See D5200 Programmer Operation Manual
Troubles after 30 seconds: If you don’t enter the D9112 handler within 30 seconds of connecting the programmer, supervised SDI devices (command centers, printer interface, etc.) connected to the D9112 generate SDI trouble reports.
Once the panel generates the SDI trouble reports all command centers, both supervised and unsupervised, stop responding to key strokes. Entering the D9112 handler or disconnecting the programmer returns the command centers to normal operation.
4.Perform the desired programming function (send or receive program).
| D9112 | Operation & Installation Manual |
|
|
| ||
Page 57 | © |