Keyswitch
Description
You can connect a maintained or momentary contact arming station (keyswitch) to master arm/disarm any of the areas in the D9112. The keyswitch is connected to an on- board or
Programming
See the Point Assignments section of the D9112 Program Entry Guide
Installation
For maintained switches, connect the
For momentary switches, connect the
Keyswitch Operation
Maintained Contact
If you program the point the keyswitch is connected to for a maintained contact, an open on the arming circuit arms the area. All faulted points are force armed, regardless of the entry in the FA Bypass Max program item. Returning the circuit to normal disarms the area. See Area Wide Parameters and Point Assignments in the D9112 Program Entry Guide
Momentary Contact
If you program the point the keyswitch is connected to for a momentary contact, shorting the arming circuit toggles the area’s arming state between armed and disarmed. All faulted points are force armed, regardless of the entry in the FA Bypass Max program item. See Point Assignments in the D9112 Program Entry Guide
Silencing the Bell
To silence the bell (stop Alarm Bell output ) if the system is armed, operate the keyswitch to disarm the area. If the area is disarmed, operate the keyswitch once to start the arming process and silence the bell. Operate it a second time to stop the arming process.
COMMON |
|
|
| COMMON |
|
| ||
1K | Ω | OPEN ON | 1K | Ω | SHORT ON | |||
CIRCUIT | ||||||||
or |
| or |
| |||||
| CIRCUIT ARMS |
| TOGGLES | |||||
33 K Ω | 33 K Ω | |||||||
AREA | ARMING STATE | |||||||
POINT INPUT |
| POINT INPUT |
| |||||
|
|
|
|
| ||||
|
|
| Figure 20: Keyswitch Wiring |
|
| |||
|
|
| D9112 Operation & Installation Manual |
|
|
| ||
|
|
|
|
|
| |||
|
|
| Page 56 |
| © |