Service Walk Test

The Service Walk Test differs from the standard Walk Test in that POPITs whose switches are set for a point number not programmed in the panel appear in the test.

Service Walk Test only available at command centers with panel wide scope: See Command Center in the D9112 Control/Communicator Program Entry Guide (74-06145- 000) for a description of command center scope.

Warning, fire and other 24-hour points do not transmit reports during Service Walk Test!

The steps below outline a simple Service Walk Test procedure. The flow chart on the next page shows all the Service Walk Test options.

1.Choose a command center with panel wide scope to conduct the test. Be certain the display shows the idle disarmed text.

2.Press 9 9 ENT to display the first item in the Service Menu.

3.Press NEXT to step through the menu items until SERVICE WALK? appears in the display.

4.Press ENT.

5.ENTER PASSCODE appears in the display if you programmed Service Walk Test access to be restricted by authority level.

Enter a passcode assigned an authority level with access to the Service Walk Test function. Press ENT.

6.The display shows ### PTS TO TEST . Test the first detection device.

7.As you fault the detection devices, the command center emits a brief tone, briefly displays the point text for the point tested, and returns to the points to test display.

Extra Points display default text: If you incorrectly set the switches on a POPIT to a point number that is not in your program for the panel, the default text for that point number (POINT ###) displays when you fault the point. The D9112 Program Record Sheet shows the default text for all points.

Faulting the point a second time produces the tone and displays thepoint text, but does not reduce the PTS TO TEST count.

8.During the Service Walk Test you may want to see the points that remain untested. When point text is displayed, press ESC. The display shows ## PTS TO TEST. Press the ESC key. VIEW UNTESTED ? is displayed. Press ENT. ## PTS UNTESTED is displayed. Press NEXT to see a list of the points that have not yet been tested. Move through this list by pressing the NEXT key. To resume the Fire Test, press ESC. ## PTS UNTESTED is displayed. Press ESC. ## PTS TO TEST is displayed. Resume testing points. To end the Service Walk Test, press ESC twice.

9.After testing the last point, 0 PTS TO TEST displays. Press ESC. The display momentarily shows ALL PTS TESTED before returning to idle text.

Automatic time-out returns the system to idle text: If there is no point or command center activity for 20 minutes, the walk test ends automatically. The command center returns to idle text.

 

D9112

Operation & Installation Manual

 

 

 

74-06144-000-C 2/96