5. CHILLED WATER PUMP STARTER INTERLOCKED WITH CHILLER.

YES

NO

6. CHILLED WATER FLOW SWITCH IS OPERATIONAL.

YES

NO

7. WATER LOOP VOLUME GREATER THAN MINIMUM REQUIREMENTS. (See Table 40).

YES

NO

8. PROPER LOOP FREEZE PROTECTION PROVIDED TO _____ °F (°C).

YES

NO

ANTIFREEZE TYPE _____________________ CONCENTRATION __________%.

 

 

IF OUTDOOR AMBIENT IS BELOW 32 F (0° C) THEN ITEMS 9-11 HAVE TO BE

 

 

COMPLETED TO PROVIDE COOLER FREEZE PROTECTION TO –20 F (–29 C). (REFER

 

 

TO WINTER SHUTDOWN FOR PROPER COOLER WINTERIZATION PROCEDURE.)

 

 

9. OUTDOOR PIPING WRAPPED WITH ELECTRIC HEATER TAPE,

YES

NO

INSULATED AND OPERATIONAL.

 

 

10. COOLER HEATERS INSTALLED AND OPERATIONAL.

YES

NO

11. CHILLED WATER PUMP CONTROLLED BY CHILLER.

YES

NO

III. Unit Start-Up

1. COMPRESSOR OIL LEVEL IS CORRECT.

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

NO

2. VERIFY COMPRESSOR MOUNTING BOLT TORQUE IS 7-10 FT-LB. (9.5-13.5 N-M).

YES

NO

3. LEAK CHECK UNIT. LOCATE, REPAIR AND REPORT ANY REFRIGERANT LEAKS.

YES

NO

4. VOLTAGE IS WITHIN UNIT NAMEPLATE RANGE.

 

 

 

 

YES

NO

5. CONTROL TRANSFORMER PRIMARY CONNECTION SET FOR PROPER VOLTAGE.

YES

NO

6. CONTROL TRANSFORMER SECONDARY VOLTAGE =

 

 

 

 

 

 

 

 

7. CHECK VOLTAGE IMBALANCE:

A-B

 

 

 

A-C

 

 

B-C

 

 

 

 

AVERAGE VOLTAGE =

 

 

 

 

(A-B + A-C + B-C)/3

 

 

 

 

 

 

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =

 

 

 

 

 

 

 

VOLTAGE IMBALANCE = ____________% (MAX. DEVIATION/AVERAGE VOLTAGE) X 100

 

 

VOLTAGE IMBALANCE LESS THAN 2%.

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

NO

(DO NOT START CHILLER IF VOLTAGE IMBALANCE IS GREATER THAN 2%.

 

 

CONTACT LOCAL UTILITY FOR ASSISTANCE.)

 

 

 

 

 

 

8. VERIFY COOLER FLOW RATE.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

NO

PRESSURE ENTERING COOLER

 

________ psig (kPa)

 

 

 

 

 

 

PRESSURE LEAVING COOLER

 

________ psig (kPa)

 

 

 

 

 

 

COOLER PRESSURE DROP

 

________ psig (kPa)

 

 

 

 

 

 

Psig X 2.31 ft./psi =

 

________ ft of water

 

 

 

 

 

 

kPa X 0.334 m/psi

 

________ m of water

 

 

 

 

 

 

COOLER FLOW RATE

 

________ gpm (l/s) (See Cooler Pressure

 

 

 

 

 

 

 

 

 

 

 

 

Drop Curves from

 

 

 

 

 

 

 

 

 

 

 

 

Installation Instructions)

 

 

Start and Operate Machine. Complete the Following:

 

 

 

 

 

 

1. COMPLETE COMPONENT TEST.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

NO

2. CHECK REFRIGERANT AND OIL CHARGE.

 

 

 

 

YES

NO

3. RECORD COMPRESSOR MOTOR CURRENT.

 

 

 

 

YES

NO

4. RECORD CONFIGURATION SETTINGS.

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

NO

5. RECORD OPERATING TEMPERATURES AND PRESSURES.

 

 

 

 

YES

NO

6. PROVIDE OPERATING INSTRUCTIONS TO OWNER’S PERSONNEL.

Instruction Time ________ hours.

CL-2

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINECUT ALONG DOTTED LINE

Page 116
Image 116
Carrier 30RAP010-060 specifications III. Unit Start-Up, Start and Operate Machine. Complete the Following

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.