CAUTION
Never charge liquid into
Operating Limitations
TEMPERATURES (See Table 29 for 30RAP standard tem- perature limits).
CAUTION
Do not operate with cooler leaving chiller water (fluid) temperature (LCWT) below 40 F (4.4 C) for the standard units, or below 15 F
High Cooler Leaving Chilled Water (Fluid) Temperatures (LCWT) — During
Low Cooler LCWT — For standard units, the LCWT must be no lower than 40 F (4.4 C). If the unit is the
Table 29 — Temperature Limits for
Standard 30RAP Units
UNIT SIZE 30RA | |||||
Temperature | F | C | F | C | |
Maximum Ambient | 120 | 49 | 120 | 49 | |
Temperature | |||||
|
|
|
| ||
Minimum Ambient | 45 | 7 | 32 | 0 | |
Temperature | |||||
|
|
|
| ||
Maximum Cooler EWT* | 95 | 35 | 95 | 35 | |
Maximum Cooler LWT | 70 | 21 | 70 | 21 | |
Minimum Cooler LWT† | 40 | 4.4 | 40 | 4.4 |
LEGEND
EWT — Entering Fluid (Water) Temperature
LWT — Leaving Fluid (Water) Temperature
*For sustained operation, EWT should not exceed 85 F (29.4 C). †Unit requires modification below this temperature.
CAUTION
Brine duty application (below 40 F [4.4 C] LCWT) for chiller normally requires factory modification. Contact your Carrier representative for applicable LCWT range for standard
VOLTAGE — ALL UNITS
Main Power Supply — Minimum and maximum acceptable supply voltages are listed in the Installation Instructions.
Unbalanced
| max voltage deviation | |
% Voltage Imbalance = 100 x | from avg voltage | |
average voltage | ||
|
The maximum voltage deviation is the largest difference between a voltage measurement across 2 legs and the average across all 3 legs.
Example: Supply voltage is
BC = 236 v AC = 238 v
1. Determine average voltage:
Averagevoltage = 243 + 236 + 238 3
=7173
=239
2.Determine maximum deviation from average voltage:
(AB) 243 – 239 = 4 v (BC) 239 – 236 = 3 v (AC) 239 – 238 = 1 v Maximum deviation is 4 v.
3.Determine percent voltage imbalance:
% Voltage Imbalance = 100 x | 4 |
239 | |
= 1.7% |
|
This voltage imbalance is satisfactory as it is below the maximum allowable of 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. Do not operate unit until imbalance condition is corrected.
Control Circuit Power — Power for the control circuit is supplied from the main incoming power through a factory- installed control power transformer (TRAN1) for all models. Field wiring connections are made to the LVT.
OPERATION SEQUENCE
During unit off cycle, the control monitors the outdoor air temperature. If the ambient temperature drops below 40 F (4.4 C), cooler and hydronic system heaters (if either are facto- ry installed) are energized. If power is maintained to the chiller and the EMERGENCY ON/OFF switch is left in the OFF po- sition, these heaters are also energized.
The unit is started by putting the ENABLE/OFF/REMOTE CONTACT switch in the ENABLE or REMOTE CONTACT position. When the unit receives a call for cooling (either from the internal control or CCN network command or remote con- tact closure), the unit stages up in capacity to maintain the leav- ing fluid set point. The first compressor starts 11/2 to 3 minutes after the call for cooling.
The lead circuit can be specifically designated on all models or selected based on compressor run hours and starts depend- ing on field configuration. The unit control will override this selection under certain starting conditions to properly maintain oil return to the compressors. In general, on dual compressor
46