Carrier 30RAP010-060 specifications APPENDIX A — DISPLAY TABLES cont, Cir A Exv Configuration

Models: 30RAP010-060

1 124
Download 124 pages 40.33 Kb
Page 81
Image 81

APPENDIX A — DISPLAY TABLES (cont)

Configuration Mode and Sub-Mode Directory (cont)

SUB-MODE

ITEM

DISPLAY

 

ITEM DESCRIPTION

COMMENT

 

 

 

CIR A EXV CONFIGURATION

 

 

STR.A

XXX

 

EXV CIrc.A Start Pos

Default: 50

 

 

0 to 100

 

 

 

 

 

 

MIN.A

XXX

 

EXV Circ.A Min Position

Default: 8

 

 

0 to 100

 

 

 

 

 

 

RNG.A

XXXXX

 

EXVA Steps In Range

0 to 65535

 

SPD.A

XXXXX

 

EXVA STeps Per Second

Default: 200

 

 

0 to 65535

 

 

 

 

 

 

POF.A

XXX

 

EXVA Fail Position In %

Default: 0

 

 

0 to 100

 

 

 

 

 

 

MIN.A

XXXXX

 

EXVA Minimum Steps

Default: 0

 

 

0 to 65535

 

 

 

 

 

 

MAX.A

XXXXX

 

EXVA Maximum Steps

0 to 65535

 

OVR.A

XXX

 

EXVA Overrun Steps

Default: 167

 

 

0 to 65535

 

 

 

 

 

EXV.A

TYP.A

0,1

 

EXVA Stepper Type

Default: 1

 

 

0 = UNIPOLAR

 

 

 

 

 

1 = BIPOLAR

 

H.SCT

XXX

 

High SCT Threshold

Default: 115

 

 

50 to 140

 

 

 

 

 

 

X.PCT

XX

 

Open EXV X% On 2nd Comp

Default: 10

 

 

0 to 30

 

 

 

 

 

 

X.PER

XX

 

Move EXV X% On DISCRSOL

Default: 5

 

 

0 to 30

 

 

 

 

 

 

A.PCT

XXX

 

Pre-open EXV - Fan Adding

Default: 10

 

 

0 to 100

 

 

 

 

 

 

M.PCT

XXX

 

Pre-close EXV - Fan Sub

Default: 10

 

 

0 to 100

 

 

 

 

 

 

S.PCT

XXX

 

Pre-close EXV - Lag Shut

Default: 10

 

 

0 to 100

 

 

 

 

 

 

DELY

XXX

 

Lag Start Delay

Default: 10

 

 

0 to 100

 

 

 

 

 

 

 

 

CIR B EXV CONFIGURATION

 

 

STR.B

XXX

 

EXV CIrc.B Start Pos

Default: 50

 

 

0 to 100

 

 

 

 

 

 

MIN.B

XXX

 

EXV Circ.B Min Position

Default: 8

 

 

0 to 100

 

 

 

 

 

 

RNG.B

XXXXX

 

EXVB Steps In Range

0 to 65535

 

SPD.B

XXXXX

 

EXVB STeps Per Second

Default: 200

 

 

0 to 65535

 

 

 

 

 

EXV.B

POF.B

XXX

 

EXVB Fail Position In %

Default: 0

 

 

 

 

 

0 to 100

 

MIN.B

XXXXX

 

EXVB Minimum Steps

Default: 0

 

 

0 to 65535

 

 

 

 

 

 

MAX.B

XXXXX

 

EXVB Maximum Steps

0 to 65535

 

OVR.B

XXX

 

EXVB Overrun Steps

Default: 167

 

 

0 to 65535

 

 

 

 

 

 

 

 

 

 

Default: 1

 

TYP.B

0,1

 

EXVB Stepper Type

0 = UNIPOLAR

 

 

 

 

 

1 = BIPOLAR