Carrier 30RAP010-060 To 20 mA Reset, Menu Configuration of 4 to 20 mA Cooling Set Point Control

Models: 30RAP010-060

1 124
Download 124 pages 40.33 Kb
Page 40
Image 40

Table 24 — 4 to 20 mA Reset

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

 

COMMENT

ENTRY

EXPANSION

 

 

 

 

 

 

 

 

 

 

 

 

 

0

= no reset

 

 

 

 

 

 

COOLING RESET

1

= 4 to 20 mA input

 

 

ENTER

 

CRST

1

2

= Outdoor air temp

 

 

 

 

TYPE

RSET

 

 

 

 

 

3

= Return Fluid

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

= Space Temperature

 

 

 

 

MA.DG

5.0 F

DEGREES COOL

Default: 0° F (0° C) Reset at 20 mA

 

 

 

 

(2.8 C)

RESET

Range: –30 to 30 F (–16.7 to 16.7 C)

 

 

 

 

 

NOTE: The example above shows how to configure the chiller for 4 to 20 mA reset. No reset will occur at 4.0 mA input, and a 5.0 F reset will occur at 20.0 mA. An EMM is required.

Table 25 — Menu Configuration of 4 to 20 mA Cooling Set Point Control

MODE

KEYPAD

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

COMMENT

(RED LED)

ENTRY

 

ENTRY

 

 

EXPANSION

 

 

ENTER

DISP

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

OPT1

 

 

 

 

 

 

 

OPT2

 

 

 

 

 

 

 

HP.A

 

 

 

 

 

 

 

HP.B

 

 

 

 

 

 

 

EXV.A

 

 

 

 

 

CONFIGURATION

 

EXV.B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M.MST

 

 

 

 

 

 

 

RSET

 

 

 

 

 

 

 

DMDC

 

 

 

 

 

 

 

SLCT

ENTER

CLSP

0

COOLING SETPOINT SELECT

 

 

 

 

 

 

 

 

ENTER

 

0

 

Scrolling Stops

 

 

 

 

 

 

 

 

 

ENTER

 

0

 

Flashing ‘0’

 

 

 

 

 

 

 

 

 

 

 

4

 

Select ‘4’

 

 

 

ENTER

 

4

 

Change Accepted

 

 

 

 

 

 

IMPORTANT: Care should be taken when interfacing with other control systems due to possible power supply differ- ences: full wave bridge versus half wave rectification. Con- nection of control devices with different power supplies may result in permanent damage. ComfortLink™ controls incorporate power supplies with half wave rectification. A signal isolation device should be utilized if the signal gen- erator incorporates a full wave bridge rectifier.

To use outdoor air or space temperature reset, four variables must be configured. In the Configuration mode under the sub- mode RSET, items (ConfigurationOPT1CRST), (Con-

figurationOPT1RM.NO), (ConfigurationOPT1 RM.F), and (ConfigurationOPT1RT.DG) must be properly set. See Table 26A — Configuring Outdoor Air and Space Temperature Reset. The outdoor air reset example pro- vides 0° F (0° C) chilled water set point reset at 85.0 F (29.4 C) outdoor-air temperature and 15.0 F (8.3 C) reset at 55.0 F (12.8 C) outdoor-air temperature. The space temperature reset example provides 0° F (0° C) chilled water set point reset at

72.0F (22.2 C) space temperature and 6.0 F (3.3 C) reset at

68.0F (20.0 C) space temperature. The variable CRST should

be configured for the type of reset desired. The variable RM.NO should be set to the temperature that no reset should occur. The variable RM.F should be set to the temperature that maximum reset is to occur. The variable RM.DG should be set to the maximum amount of reset desired. Figures 18 and 19 are examples of outdoor air and space temperature resets.

To use return reset, four variables must be configured. In the Configuration mode under the sub-mode RSET, items CRST, RT.NO, RT.F and RT.DG must be properly set. See Table 26B

Configuring Return Temperature Reset. This example pro- vides 5.0 F (2.8 C) chilled water set point reset at 2.0 F (1.1 C) cooler ΔT and 0° F (0° C) reset at 10.0 F (5.6 C) cooler ΔT. The variable RT.NO should be set to the cooler temperature differ- ence (ΔT) where no chilled water temperature reset should oc- cur. The variable RT.F should be set to the cooler temperature difference where the maximum chilled water temperature reset should occur. The variable RM.DG should be set to the maxi- mum amount of reset desired.

To verify that reset is functioning correctly proceed to Run Status mode, sub-mode VIEW, and subtract the active set point (Run StatusVIEWSETP) from the control point (Run StatusVIEWCTPT) to determine the degrees reset.

40

Page 40
Image 40
Carrier 30RAP010-060 specifications To 20 mA Reset, Menu Configuration of 4 to 20 mA Cooling Set Point Control

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.