Energy Management Module (Fig. 12) — This
•4 to 20 mA leaving fluid temperature reset (requires field-supplied 4 to 20 mA generator)
•4 to 20 mA cooling set point reset (requires field- supplied 4 to 20 mA generator)
•Discrete inputs for
•4 to 20 mA demand limit (requires
•Discrete input for Ice Done switch (requires field- supplied dry contacts capable of handling a 24 vac, 50 mA load)
See Demand Limit and Temperature Reset sections on pages 41 and 37 for further details.
CAUTION
Care should be taken when interfacing with other manufac- turer’s control systems due to possible power supply differences, full wave bridge versus half wave rectification. The two different power supplies cannot be mixed. ComfortLink™ controls use half wave rectification. A signal isolation device should be utilized if a full wave bridge signal generating device is used.
Electronic Expansion Valves (EXV) — All units are equipped from the factory with EXVs. Each refrigeration cir- cuit is also supplied with a
The EXV is set at the factory to maintain 9° F (5.0° C) suc- tion superheat leaving the cooler by metering the proper amount of refrigerant into the cooler. The superheat set point is adjustable, but should not be adjusted unless absolutely necessary.
The EXV is designed to limit the cooler saturated suction temperature to 50 F (12.8 C). This makes it possible for unit to start at high cooler fluid temperatures without overloading the compressor.
Capacity Control — The control system cycles com- pressors, digital scroll modulting solenoid (if equipped), and minimum load valve solenoids (if equipped) to maintain the
The standard control has an automatic
compressor to start next. If no compressors have been running for more than 30 minutes and the leaving fluid temperature is greater than the saturated condensing temperature, the wear factor is still used to determine which compressor to start next. If the leaving fluid temperature is less than the saturated con- densing temperature, then the control will start either compres- sor A1 or compressor B1 first, depending on the
The EXVs will provide a controlled
If a circuit is to be stopped, the compressor with the lowest wear factor will be shut off first except when a digital compres- sor is used. The digital compressor is always the last compres- sor to shut off.
The capacity control algorithm runs every 30 seconds. The algorithm attempts to maintain the Control Point at the desired set point. Each time it runs, the control reads the entering and leaving fluid temperatures. The control determines the rate at which conditions are changing and calculates 2 variables based on these conditions. Next, a capacity ratio is calculated using the 2 variables to determine whether or not to make any changes to the current stages of capacity. This ratio value ranges from
MINUTES LEFT FOR START — This value is displayed only in the network display tables (using Service Tool, ComfortVIEW™ or ComfortWORKS® software) and represents the amount of time to elapse before the unit will start its initialization routine. This value can be zero without the machine running in many situations. This can include being unoccupied, ENABLE/OFF/REMOTE CONTACT switch in the OFF position, CCN not allowing unit to start, Demand Limit in effect, no call for cooling due to no load, and alarm or alert conditions present. If the machine should be running and none of the above are true, a minimum off time (DELY, see below) may be in effect. The machine should start normally once the time limit has expired.
MINUTES OFF TIME (Configuration→OPT2→ DELY) — This
29