APPENDIX B — CCN TABLES (cont)

CCN CONFIGURATION TABLES — OPTIONS2 (Options 2 Configuration)

DESCRIPTION

 

VALUE

DEFAULT

UNITS

POINT NAME

Control Method

0

= Switch

0

 

CONTROL

 

2

= Occupancy

 

 

 

 

3

= CCN

 

 

 

Loading Sequence Select

1

= Equal Loading

1

 

SEQ_TYP

 

2

= Staged Loading

 

 

 

Lead/Lag Circuit Select

1

= Automatic

1

 

LEAD_TYP

 

2

= Circuit A Leads

 

 

 

 

3

= Circuit B Leads

 

 

 

Cooling Setpoint Select

0

= Single

0

 

CLSP_TYP

 

1

= Dual, remote switch controlled

 

 

 

 

2

= Dual CCN occupancy

 

 

 

 

3

= 4-20 mA input

 

 

 

Ramp Load Select

Enable/Dsable

Enable

 

RAMP_EBL

Heat Cool Select

Cool/Heat

Cool

 

HEATCOOL

High LCW Alert Limit

2 to 60

60.0

ΔF

LCW_LMT

Minutes off time

0 to 15

0

min

DELAY

Deadband Multiplier

1.0 to 4.0

1.0

 

Z_GAIN

Ice Mode Enable

Enable/Dsable

Dsable

 

ICE_CNFG

Low Sound Mode Select

0

= Disabled

0

 

LS_MODE

 

1

= Fan only

 

 

 

 

2

= Capacity/Fans

 

 

 

Low Sound Start Time

00:00 to 23:59

00:00

 

LS_START

Low Sound End Time

00:00 to 23:59

00:00

 

LS_END

Low Sound Capacity Limit

0 to 100

100

%

LS_LIMIT

CCN CONFIGURATION TABLES — SCHEDOVR (Timed Override Setup)

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

Schedule Number

0 to 99

1

 

SCHEDNUM

Override Time Limit

0 to 4

0

hours

OTL

Timed Override Hours

0 to 4

0

hours

OVR_EXT

Timed Override

No/Yes

No

 

TIMEOVER

CCN CONFIGURATION TABLES — RESETCON (Temperature Reset and Demand Limit)

DESCRIPTION

 

VALUE

DEFAULT

UNITS

POINT NAME

COOLING RESET

 

 

 

 

 

Cooling Reset Type

0

= No Reset

0

 

CRST_TYP

 

1

= 4-20 mA input

 

 

 

 

2

= External temp – OAT

 

 

 

 

3

= Return Fluid

 

 

 

 

4

= External temp - SPT

 

 

 

4-20 MA RESET

 

 

 

 

 

4-20 – Degrees Reset

–30 to 30

0.0

ΔF

420_DEG

 

 

 

 

 

 

REMOTE RESET

 

 

 

 

 

Remote – No Reset Temp

0 to 125

125.0

°F

REM_NO

Remote – Full Reset Temp

0 to 125

0.0

°F

REM_FULL

Remote – Degrees Reset

–30 to 30

0.0

ΔF

REM_DEG

 

 

 

 

 

 

RETURN TEMPERATURE RESET

 

 

 

 

 

Return – No Reset Temp

0 to 125

10.0

ΔF

RTN_NO

Return – Full Reset Temp

0 to 125

0.0

ΔF

RTN_FULL

Return – Degrees Reset

–30 to 30

0.0

ΔF

RTN_DEG

 

 

 

 

 

 

DEMAND LIMIT

 

 

 

 

 

Demand Limit Select

0

= None

0

 

DMD_CTRL

 

1

= External switch input

 

 

 

 

2

= 4-20 mA input

 

 

 

 

3

= Loadshed

 

 

 

Demand Limit at 20 mA

0 to 100

100

%

DMT20MA

Loadshed Group Number

0 to 99

0

 

SHED_NUM

Loadshed Demand Delta

0 to 60

0

%

SHED_DEL

Maximum Loadshed Time

0 to 120

60

minutes

SHED_TIM

Demand Limit Switch 1

0 to 100

80

%

DLSWSP1

Demand Limit Switch 2

0 to 100

50

%

DLSWSP2

93

Page 93
Image 93
Carrier 30RAP010-060 specifications CCN Configuration Tables OPTIONS2 Options 2 Configuration

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.