Table 42 — Alarm and Alert Codes (cont)
ALARM/ | ALARM |
| WHY WAS THIS | ACTION TAKEN | RESET | PROBABLE | |
ALERT | OR | DESCRIPTION | ALARM | ||||
BY CONTROL | METHOD | CAUSE | |||||
CODE | ALERT |
| GENERATED? | ||||
|
|
|
| ||||
|
|
|
|
|
|
| |
|
|
|
| Occupancy schedule | Automatic when | Time/Date/Month/ | |
T153 |
| Real Time Clock |
| will not be used. Chiller | |||
Alert | Internal clock on MBB fails | correct clock control | Day/Year not | ||||
Hardware Failure | defaults to Local On | ||||||
|
|
| restarts. | properly set. | |||
|
|
|
| mode. | |||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
A154 | Alarm | Serial EEPROM | Hardware failure with MBB | Chiller is unable | Manual | Main Base Board | |
Hardware Failure | to run. | failure. | |||||
|
|
|
| ||||
|
|
|
|
|
|
| |
|
|
|
|
|
| Potential failure of | |
|
|
|
|
|
| MBB. Download | |
T155 | Alert | Serial EEPROM | Configuration/storage | No Action | Manual | current operating | |
Storage Failure | failure with MBB | software. Replace | |||||
|
|
|
| ||||
|
|
|
|
|
| MBB if error occurs | |
|
|
|
|
|
| again. | |
|
|
|
|
|
|
| |
A156 | Alarm | Critical Serial EEPROM | Configuration/storage | Chiller is not allowed | Manual | Main Base Board | |
Storage Failure | failure with MBB | to run. | failure. | ||||
|
|
| |||||
|
|
|
|
|
|
| |
A157 | Alarm | A/D Hardware Failure | Hardware failure with | Chiller is not allowed | Manual | Main Base Board | |
peripheral device | to run. | failure. | |||||
|
|
|
| ||||
|
|
|
|
|
|
| |
A172 |
| Loss of Communication | MBB loses communication | Chiller is not allowed |
| Wiring error, faulty | |
Alarm | Automatic | wiring or failed | |||||
with EXV Board | with EXV board | to run. | |||||
|
|
| EXV board. | ||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
|
| 4 to 20 mA |
|
| |
|
|
|
| temperature reset |
| Wiring error, faulty | |
T173 | Alert | Loss of Communication | MBB loses communication | disabled. Demand | Automatic | wiring or failed | |
with EMM | with EMM | Limit set to 100%. 4 to | Energy Manage- | ||||
|
|
| |||||
|
|
|
| 20 mA set point |
| ment Module (EMM). | |
|
|
|
| disabled. |
|
| |
|
|
|
|
|
|
| |
T174 | Alert | 4 to 20 mA Cooling Set | If configured with EMM and | Set point function |
| Faulty signal | |
input less than 2 mA or | disabled. Chiller | Automatic | generator, wiring | ||||
Point Input Failure | |||||||
|
| greater than 22 mA | controls to CSP1. |
| error, or faulty EMM. | ||
|
|
|
| ||||
|
|
|
|
|
|
| |
T175 |
| Loss of Communication | MBB loses communication |
|
| Wiring error, faulty | |
Alert |
| Automatic | wiring or failed | ||||
with the AUX Board | with AUX Board. |
| |||||
|
|
|
| AUX board. | |||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
| 4 to 20 mA | If configured with EMM | Reset function |
| Faulty signal | |
T176 |
| disabled. Chiller |
| ||||
Alert | Temperature Reset | and input less than 2 mA or | Automatic | generator, wiring | |||
returns to normal set | |||||||
|
| Input Failure | greater than 22 mA |
| error, or faulty EMM. | ||
|
| point control. |
| ||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
|
| Demand limit function |
|
| |
T177 |
| 4 to 20 mA Demand | If configured with EMM and | disabled. Chiller |
| Faulty signal | |
Alert | input less than 2 mA or | returns to 100% | Automatic | generator, wiring | |||
Limit Input Failure | |||||||
|
| greater than 22 mA | demand limit |
| error, or faulty EMM. | ||
|
|
|
| ||||
|
|
|
| control. |
|
| |
|
|
|
|
|
|
| |
|
|
| Pump 1 Auxiliary Contacts |
|
|
| |
|
|
| are closed when Pump 2 |
|
| Wiring error, faulty | |
A189 |
| Cooler Pump Auxiliary | output is energized or if | Both pump outputs |
| ||
Alarm | Manual | pump contactor | |||||
Contact Inputs Miswired | Pump 2 Auxiliary Contacts | are turned off. | |||||
|
|
| auxiliary contacts. | ||||
|
|
| are closed when Pump 1 |
|
| ||
|
|
|
|
|
| ||
|
|
| output is energized. |
|
|
| |
|
|
|
|
|
|
| |
|
| Cooler Pump 1 Aux | Pump 1 Auxiliary Contacts | Pump 1 turned off. |
| Wiring error, faulty | |
T190 |
| did not close within |
| ||||
Alert | Contacts Failed to Close | Pump 2 will be started | Manual | contacts on pump | |||
26 seconds after pump | |||||||
|
| at | if available. |
| contactor | ||
|
| was started |
| ||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
| Cooler Pump 2 Aux | Pump 2 Auxiliary Contacts | Pump 2 turned off. |
| Wiring error, faulty | |
T191 |
| did not close within |
| ||||
Alert | Contacts Failed to Close | Pump 1 will be started | Manual | contacts on pump | |||
26 seconds after pump | |||||||
|
| at | if available. |
| contactor | ||
|
| was started |
| ||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
| Cooler Pump 1 Failed | Pump 1 did not provide | Pump 1 turned off. |
| Wiring error, pump | |
T192 |
|
| circuit breaker | ||||
Alert | to Provide Flow at | flow to close flow switch | Pump 2 will be started | Manual | |||
tripped, contactor | |||||||
|
| within 60 seconds | if available. |
| |||
|
|
| failure | ||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
| Cooler Pump 2 Failed | Pump 2 did not provide | Pump 1 turned off. |
| Wiring error, pump | |
T193 |
|
| circuit breaker | ||||
Alert | to Provide Flow at | flow to close flow switch | Pump 2 will be started | Manual | |||
tripped, contactor | |||||||
|
| within 60 seconds | if available. |
| |||
|
|
| failure | ||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
| Cooler Pump 1 Aux | Pump 1 Auxiliary Contacts | Pump 2 will be started |
|
| |
|
| open for 26 seconds after | if available. Chiller |
| Wiring error, faulty | ||
T194 |
| Contacts Opened |
| ||||
Alert | initially made. All | allowed to run if | Manual | contacts on pump | |||
During Normal | |||||||
|
| compressors shut down. | Pump 2 successfully |
| contactor | ||
|
| Operation |
| ||||
|
| Pump 1 turned off. | starts. |
|
| ||
|
|
|
|
| |||
|
|
|
|
|
|
| |
|
| Cooler Pump 2 Aux | Pump 2 Auxiliary Contacts | Pump 1 will be started |
|
| |
|
| open for 26 seconds after | if available. Chiller |
| Wiring error, faulty | ||
T195 |
| Contacts Opened |
| ||||
Alert | initially made. All | allowed to run if | Manual | contacts on pump | |||
During Normal | |||||||
|
| compressors shut down. | Pump 1 successfully |
| contactor | ||
|
| Operation |
| ||||
|
| Pump 2 turned off. | starts. |
|
| ||
|
|
|
|
| |||
|
|
|
|
|
|
| |
|
|
|
| All compressors |
|
| |
|
|
|
| shut down. Pump 1 |
|
| |
|
|
| Cooler flow switch contacts | turned off. Pump 2 will |
| Wiring error, pump | |
T196 |
| Flow Lost While Pump 1 | be started if available. | Manual | circuit breaker | ||
Alert | open for 3 seconds after | ||||||
Running | Chiller allowed to run if | tripped, contactor | |||||
|
| initially made |
| ||||
|
|
| Pump 2 successfully |
| failure | ||
|
|
|
|
| |||
|
|
|
| starts and flow switch |
|
| |
|
|
|
| is closed. |
|
|