Table 42 — Alarm and Alert Codes (cont)

ALARM/

ALARM

 

WHY WAS THIS

ACTION TAKEN

RESET

PROBABLE

ALERT

OR

DESCRIPTION

ALARM

BY CONTROL

METHOD

CAUSE

CODE

ALERT

 

GENERATED?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Strainer Service

 

 

 

 

 

Strainer Blowdown

Countdown (S.T.DN)

 

 

Routine strainer

T302

 

expired. Complete strainer

 

 

Alert

Scheduled

None

Automatic

maintenance

blowdown and enter 'YES'

 

 

Maintenance Due

 

 

required

 

 

for Strainer Maintenance

 

 

 

 

 

 

 

 

 

 

 

Done (S.T.MN) item.

 

 

 

 

 

 

 

 

 

 

 

 

 

Coil Service Countdown

 

 

 

 

 

 

(C.L.DN) expired.

 

 

Routine condenser

T303

 

Condenser Coil

Complete condenser coil

 

 

Alert

None

Automatic

coil maintenance

Maintenance Due

cleaning and enter 'YES'

 

 

 

 

required

 

 

 

for Coil Maintenance Done

 

 

 

 

 

 

 

 

 

 

 

(C.L.MN) item.

 

 

 

 

 

 

 

 

 

 

T500

Alert

Current Sensor Board

Alert occurs when CSB out-

Compressor A1 shut

Automatic

CSB failure.

A1 Failure

put is a constant high value

down

Wiring error.

 

 

 

 

 

 

 

 

 

 

T501

Alert

Current Sensor Board

Alert occurs when CSB out-

Compressor A2 shut

Automatic

CSB failure.

A2 Failure

put is a constant high value

down

Wiring error.

 

 

 

 

 

 

 

 

 

 

T502

Alert

Current Sensor Board

Alert occurs when CSB out-

Compressor A3 shut

Automatic

CSB failure.

A3 Failure

put is a constant high value

down

Wiring error.

 

 

 

 

 

 

 

 

 

 

T503

Alert

Current Sensor Board

Alert occurs when CSB out-

Compressor B1 shut

Automatic

CSB failure.

B1 Failure

put is a constant high value

down

Wiring error.

 

 

 

 

 

 

 

 

 

 

T504

Alert

Current Sensor Board

Alert occurs when CSB out-

Compressor B2 shut

Automatic

CSB failure.

B2 Failure

put is a constant high value

down

Wiring error.

 

 

 

 

 

 

 

 

 

 

T505

Alert

Current Sensor Board

Alert occurs when CSB out-

Compressor B3 shut

Automatic

CSB failure.

B3 Failure

put is a constant high value

down

Wiring error.

 

 

 

T950

Alert

Loss of Communication

No communications have

WSM forces removed.

Automatic

Failed module, wiring

 

 

with Water System

been received by the MBB

Chiller runs under own

 

error, failed

 

 

Manager

within 5 minutes of last

control

 

transformer, loose

 

 

 

transmission

 

 

connection plug,

 

 

 

 

 

 

wrong address

 

 

 

 

 

 

 

T951

Alert

Loss of Communication

No communications have

CSM forces removed.

Automatic

Failed module, wiring

 

 

with Chillervisor System

been received by the MBB

Chiller runs under own

 

error, failed

 

 

Manager

within 5 minutes of last

control

 

transformer, loose

 

 

 

transmission

 

 

connection plug,

 

 

 

 

 

 

wrong address

 

 

 

 

 

 

 

T952

Alert

Loss of Communication

No communications have

HSM forces removed.

Automatic

Failed module, wiring

 

 

with Hydronic System

been received by the MBB

Chiller runs under own

 

error, failed

 

 

Manager

within 5 minutes of last

control

 

transformer, loose

 

 

 

transmission

 

 

connection plug,

 

 

 

 

 

 

wrong address

 

LEGEND FOR TABLE 42

 

 

 

 

CCN

Carrier Comfort Network

 

 

 

 

CSB

Current Sensor Board

 

 

 

 

EEPROM — Electronic Eraseable Programmable Read Only Memory

 

 

 

EMM

Energy Management Module

 

 

 

 

EWT

Entering Fluid Temperature

 

 

 

 

EXV

Electronic Expansion Valve

 

 

 

 

HSM

Hydronic System Manager

 

 

 

 

LCW

Leaving Chilled Water

 

 

 

 

LWT

Leaving Fluid Temperature

 

 

 

 

MBB

Main Base Board

 

 

 

 

OAT

Outdoor-Air Temperature

 

 

 

 

SCT

Saturated Condensing Temperature

 

 

 

 

WSM

Water System Manager

 

 

 

 

COMPRESSOR FAILURE ALERTS

T051, T052 (Circuit A Compresser Failures)

T055, T056 (Circuit B Compressor Failures) — Alert codes 051, 052, 055, and 056 are for compressors A1, A2, B1, and B2 respectively. These alerts occur when the current sensor (CS) does not detect compressor current during compressor op- eration. When this occurs, the control turns off the compressor.

If the current sensor board reads OFF while the compressor relay has been commanded ON, an alert is generated.

POSSIBLE CAUSES

Compressor Overload — Either the compressor internal over- load protector is open or the external overload protector (Kri- wan module) has activated. The external overload protector modules are mounted in the compressor wiring junction box. Temperature sensors embedded in the compressor motor wind- ings are the inputs to the module. The module is powered with 24 vac from the units main control box. The module output is a normally closed contact that is wired in series with the com- pressor contactor coil. In a compressor motor overload condi- tion, contact opens, deenergizing the compressor contactor.

Low Refrigerant Charge — If the compressor operates for an extended period of time with low refrigerant charge, the com- pressor ASTP device will open, which will cause the compres- sor to trip on its overload protection device.

Circuit Breaker Trip — The compressors are protected from short circuit by a breaker in the control box.

Wiring Error — A wiring error might not allow the compres- sor to start.

To check out alerts T051-T056:

1.Turn on the compressor in question using Service Test mode. If the compressor does not start, then most likely the problem is one of the following: HPS open, open in- ternal protection, circuit breaker trip, incorrect safety wir- ing, or incorrect compressor wiring.

2.If the compressor does start, verify it is rotating in the cor- rect direction.

IMPORTANT: Prolonged operation in the wrong direction can damage the compressor. Correct rotation can be veri- fied by a gage set and looking for a differential pressure rise on start-up.

71

Page 71
Image 71
Carrier 30RAP010-060 specifications Alert GENERATED?, Ccn, Csb, Emm, Ewt, Exv, Hsm, Lcw, Lwt, Mbb, Oat

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.