Table 36 — 10K Thermistor Temperature (°C) vs. Resistance/Voltage Drop

(For SPT)

TEMP

VOLTAGE

RESISTANCE

 

TEMP

VOLTAGE

RESISTANCE

 

TEMP

VOLTAGE

RESISTANCE

DROP

 

DROP

 

DROP

(C)

(Ohms)

 

(C)

(Ohms)

 

(C)

(Ohms)

(V)

 

(V)

 

(V)

 

 

 

 

 

 

 

 

–32

4.762

200,510

 

15

3.056

15,714

 

62

0.940

2,315

–31

4.748

188,340

16

3.000

15,000

63

0.913

2,235

–30

4.733

177,000

17

2.944

14,323

64

0.887

2,157

–29

4.716

166,342

18

2.889

13,681

65

0.862

2,083

–28

4.700

156,404

19

2.833

13,071

66

0.837

2,011

–27

4.682

147,134

20

2.777

12,493

67

0.813

1,943

–26

4.663

138,482

21

2.721

11,942

68

0.790

1,876

–25

4.644

130,402

22

2.666

11,418

69

0.767

1,813

–24

4.624

122,807

23

2.610

10,921

70

0.745

1,752

–23

4.602

115,710

24

2.555

10,449

71

0.724

1,693

–22

4.580

109,075

25

2.500

10,000

72

0.703

1,637

–21

4.557

102,868

26

2.445

9,571

73

0.683

1,582

–20

4.533

97,060

27

2.391

9,164

74

0.663

1,530

–19

4.508

91,588

28

2.337

8,776

75

0.645

1,480

–18

4.482

86,463

29

2.284

8,407

76

0.626

1,431

–17

4.455

81,662

30

2.231

8,056

77

0.608

1,385

–16

4.426

77,162

31

2.178

7,720

78

0.591

1,340

–15

4.397

72,940

32

2.127

7,401

79

0.574

1,297

–14

4.367

68,957

33

2.075

7,096

80

0.558

1,255

–13

4.335

65,219

34

2.025

6,806

81

0.542

1,215

–12

4.303

61,711

35

1.975

6,530

82

0.527

1,177

–11

4.269

58,415

36

1.926

6,266

83

0.512

1,140

–10

4.235

55,319

37

1.878

6,014

84

0.497

1,104

–9

4.199

52,392

38

1.830

5,774

85

0.483

1,070

–8

4.162

49,640

39

1.784

5,546

86

0.470

1,037

–7

4.124

47,052

40

1.738

5,327

87

0.457

1,005

–6

4.085

44,617

41

1.692

5,117

88

0.444

974

–5

4.044

42,324

42

1.648

4,918

89

0.431

944

–4

4.003

40,153

43

1.605

4,727

90

0.419

915

–3

3.961

38,109

44

1.562

4,544

91

0.408

889

–2

3.917

36,182

45

1.521

4,370

92

0.396

861

–1

3.873

34,367

46

1.480

4,203

93

0.386

836

0

3.828

32,654

47

1.439

4,042

94

0.375

811

1

3.781

31,030

48

1.400

3,889

95

0.365

787

2

3.734

29,498

49

1.362

3,743

96

0.355

764

3

3.686

28,052

50

1.324

3,603

97

0.345

742

4

3.637

26,686

51

1.288

3,469

98

0.336

721

5

3.587

25,396

52

1.252

3,340

99

0.327

700

6

3.537

24,171

53

1.217

3,217

100

0.318

680

7

3.485

23,013

54

1.183

3,099

101

0.310

661

8

3.433

21,918

55

1.150

2,986

102

0.302

643

9

3.381

20,883

56

1.117

2,878

103

0.294

626

10

3.328

19,903

57

1.086

2,774

104

0.287

609

11

3.274

18,972

58

1.055

2,675

105

0.279

592

12

3.220

18,090

59

1.025

2,579

106

0.272

576

13

3.165

17,255

60

0.996

2,488

107

0.265

561

14

3.111

16,464

 

61

0.968

2,400

 

 

 

 

Table 37 — 86K Thermistor vs Resistance (DTT)

TEMP

TEMP

RESISTANCE

(C)

(F)

(Ohms)

-40

-40

2,889,600

-35

-31

2,087,220

-30

-22

1,522,200

-25

-13

1,121,440

-20

-4

834,720

-15

5

627,280

-10

14

475,740

-5

23

363,990

0

32

280,820

5

41

218,410

10

50

171,170

15

59

135,140

20

68

107,440

25

77

86,000

30

86

69,280

35

95

56,160

40

104

45,810

45

113

37,580

50

122

30,990

55

131

25,680

60

140

21,400

70

158

15,070

TEMP

TEMP

RESISTANCE

(C)

(F)

(Ohms)

75

167

12,730

80

176

10,790

85

185

9,200

90

194

7,870

95

203

6,770

100

212

5,850

105

221

5,090

110

230

4,450

115

239

3,870

120

248

3,350

125

257

2,920

130

266

2,580

135

275

2,280

140

284

2,020

145

293

1,800

150

302

1,590

155

311

1,390

160

320

1,250

165

329

1,120

170

338

1,010

175

347

920

180

356

830

57

Page 57
Image 57
Carrier 30RAP010-060 specifications 86K Thermistor vs Resistance DTT, Drop

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.