Carrier 30RAP010-060 specifications Alarm and Alert Codes cont

Models: 30RAP010-060

1 124
Download 124 pages 40.33 Kb
Page 68
Image 68

Table 42 — Alarm and Alert Codes (cont)

ALARM/

ALARM

 

WHY WAS THIS

ACTION TAKEN

RESET

PROBABLE

ALERT

OR

DESCRIPTION

ALARM

BY CONTROL

METHOD

CAUSE

CODE

ALERT

 

GENERATED?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If the compressors are off

 

 

 

T110

Alert

Circuit A Loss of Charge

and discharge pressure

Circuit not allowed to

Manual

Refrigerant leak or

reading is < 26 psig for

start.

transducer failure

 

 

 

 

 

 

 

30 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

If the compressors are off

 

 

 

T111

Alert

Circuit B Loss of Charge

and discharge pressure

Circuit not allowed to

Manual

Refrigerant leak or

reading is < 26 psig for

start.

transducer failure

 

 

 

 

 

 

 

30 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit saturated suction

 

 

Faulty Expansion valve,

T112

Alert

Circuit A High Saturated

temperature pressure

Circuit shut down

Manual

faulty suction pressure

Suction Temperature

transducer > 70 F (21.1 C)

transducer or high entering

 

 

 

 

 

 

 

for 5 minutes

 

 

fluid temperature.

 

 

 

 

 

 

 

 

 

Circuit B High Saturated

Circuit saturated suction

 

 

Faulty Expansion valve,

T113

 

temperature pressure

 

 

faulty suction pressure

Alert

Suction Temperature

Circuit shut down

Manual

transducer > 70 F (21.1 C)

transducer or high entering

 

 

 

 

 

 

 

 

for 5 minutes

 

 

fluid temperature.

 

 

 

 

 

Automatic restart

Faulty expansion valve,

T114

 

Circuit A Low Suction

Suction superheat is

 

after first daily

faulty suction pressure

Alert

less than 5° F (2.8 C) for 5

Circuit A shut down.

occurrence.

transducer, faulty suction gas

Superheat

 

 

minutes.

 

Manual restart

thermistor, circuit

 

 

 

 

 

 

 

 

 

thereafter.

overcharged

 

 

 

 

 

 

 

 

 

 

 

 

Automatic restart

Faulty expansion valve,

T115

 

Circuit B Low Suction

Suction superheat is

 

after first daily

faulty suction pressure

Alert

less than 5° F (2.8 C) for 5

Circuit B shut down.

occurrence.

transducer, faulty suction

Superheat

 

 

minutes.

 

Manual restart

gas thermistor, circuit

 

 

 

 

 

 

 

 

 

thereafter.

overcharged

 

 

 

 

 

 

 

 

 

 

Mode 7 caused the com-

 

 

Faulty expansion valve, low

T116

 

Circuit A Low Cooler

pressor to unload 6 consecu-

 

 

refrigerant charge, plugged

Alert

tive times with less than a

Circuit shut down

Manual

filter drier, faulty suction

Suction Temperature

 

 

30-minute interval between

 

 

pressure transducer, low

 

 

 

 

 

 

 

 

each circuit shutdown.

 

 

cooler fluid flow

 

 

 

Mode 8 caused the com-

 

 

Faulty expansion valve, low

T117

 

Circuit B Low Cooler

pressor to unload 6 consecu-

 

 

refrigerant charge, plugged

Alert

tive times with less than a

Circuit shut down

Manual

filter drier, faulty suction

Suction Temperature

 

 

30-minute interval between

 

 

pressure transducer, low

 

 

 

 

 

 

 

 

each circuit shutdown.

 

 

cooler fluid flow

T118

 

High Discharge Gas

Discharge Thermistor (DTT)

Compressor A1 shut

 

Refrigerant charge, plugged

Alert

Automatic

filter drier, head pressure

Temperature Alert

reading is greater than 250 F

down

 

 

 

control.

 

 

 

 

 

 

 

 

 

 

 

 

 

A118

 

High Discharge Gas

3 Discharge Gas Tempera-

Compressor A1 shut

 

Refrigerant charge, plugged

Alarm

ture alarms occur within a

Manual

filter drier, head pressure

Temperature

down

 

 

day

 

control.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic, only

 

 

 

 

 

 

after first 3 daily

 

 

 

 

 

 

occurrences.

Faulty transducer/high

 

 

 

 

 

Manual reset

T126

 

Circuit A High

Compressor operation out-

 

pressure switch, low/

Alert

Circuit shut down

thereafter. Read-

Discharge Pressure

side of operating envelope.

restricted condenser

 

 

 

ing from OAT sen-

 

 

 

 

 

airflow

 

 

 

 

 

sor must drop 5 F

 

 

 

 

 

 

 

 

 

 

 

(2.8 C) before

 

 

 

 

 

 

restart

 

 

 

 

 

 

Automatic, only

 

 

 

 

 

 

after first 3 daily

Faulty transducer/high

 

 

 

 

 

occurrences. Man-

T127

Alert

Circuit B High

Compressor operation out-

Circuit shut down

ual reset thereafter.

pressure switch, low/

Discharge Pressure

side of operating envelope.

Reading from OAT

restricted condenser

 

 

 

 

 

 

 

 

sensor must drop

airflow

 

 

 

 

 

5 F (2.8 C) before

 

 

 

 

 

 

restart

 

 

 

 

 

 

Automatic

 

T133

 

Circuit A Low Suction

Suction pressure below

 

restart after first

Faulty or sticking EXV, low

Alert

34 psig for 8 seconds or

Circuit shut down

daily occurrence.

refrigerant charge, plugged

Pressure

 

 

below 23 psig

 

Manual restart

filter drier.

 

 

 

 

 

 

 

 

 

thereafter.

 

 

 

 

 

 

Automatic

 

T134

 

Circuit B Low Suction

Suction pressure below

 

restart after first

Faulty or sticking EXV, low

Alert

34 psig for 8 seconds or

Circuit shut down

daily occurrence.

refrigerant charge, plugged

Pressure

 

 

below 23 psig

 

Manual restart

filter drier.

 

 

 

 

 

 

 

 

 

thereafter.

 

A140

 

Reverse Rotation

Incoming chiller power leads

Chiller not allowed to

 

Reverse any two incoming

Alert

Manual

power leads to correct. Check

Detected

not phased correctly

start.

 

 

 

for correct fan rotation first.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chiller shutdown

Automatic once

 

A150

 

 

CCN emergency stop

CCN command for

CCN Network

Alarm

Emergency Stop

without going through

command received

EMSTOP returns to

command.

 

 

 

pumpdown.

 

 

 

 

normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A151

 

 

One or more illegal

Chiller is not allowed to

Manual once

Configuration error.

Alarm

Illegal Configuration

configuration errors

configurations exists.

start.

Check unit settings.

 

 

 

are corrected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic once

 

A152

 

Unit Down Due to

Both circuits are down due

Chiller is unable

alarms/alerts are

Alarm notifies user

Alarm

cleared that pre-

that chiller is 100%

Failure

to alarms/alerts.

to run.

 

 

vent the chiller from

down.

 

 

 

 

 

 

 

 

 

 

starting.

 

 

 

 

 

 

 

 

68

Page 68
Image 68
Carrier 30RAP010-060 specifications Alarm and Alert Codes cont