Table 5 — Temperature Mode and Sub-Mode Directory
KEYPAD | ITEM | DISPLAY | ITEM | COMMENT | ||||
ENTRY | EXPANSION | |||||||
|
|
|
| |||||
UNIT |
|
|
|
|
| ENT AND LEAVE UNIT TEMPS |
| |
|
|
|
| CEWT | XXX.X °F | COOLER ENTERING FLUID |
| |
|
| ENTER |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| CLWT | XXX.X °F | COOLER LEAVING FLUID |
| |
|
|
|
|
|
|
|
| |
|
|
|
| OAT | XXX.X °F | OUTSIDE AIR TEMPERATURE |
| |
|
|
|
|
|
|
|
| |
|
|
|
| SPT | XXX.X °F | SPACE TEMPERATURE |
| |
|
|
|
|
|
|
|
| |
|
|
|
| DLWT | XXX.X °F | LEAD/LAG LEAVING FLUID |
| |
|
|
|
|
|
|
|
| |
CIR.A |
|
|
|
|
| TEMPERATURES CIRCUIT A |
| |
|
|
| SCT.A | XXX.X °F | SATURATED CONDENSING TMP |
| ||
|
| ENTER |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| SST.A | XXX.X °F | SATURATED SUCTION TEMP |
| |
|
|
|
|
|
|
|
| |
|
|
|
| RGT.A | XXX.X °F | COMPR RETURN GAS TEMP |
| |
|
|
|
|
|
|
|
| |
|
|
|
| D.GAS | XXX.X °F | DISCHARGE GAS TEMP |
| |
|
|
|
|
|
|
|
| |
|
|
|
| SH.A | XXX.X ^F | SUCTION SUPERHEAT TEMP |
| |
|
|
|
|
|
|
|
| |
CIR.B |
|
|
|
|
| TEMPERATURES CIRCUIT B | See Note | |
|
|
| SCT.B | XXX.X °F | SATURATED CONDENSING TMP | See Note | ||
|
| ENTER |
| |||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| SST.B | XXX.X °F | SATURATED SUCTION TEMP | See Note | |
|
|
|
|
|
|
|
| |
|
|
|
| RGT.B | XXX.X °F | COMPR RETURN GAS TEMP | See Note | |
|
|
|
|
|
|
|
| |
|
|
|
| SH.B | XXX.X ^F | SUCTION SUPERHEAT TEMP | See Note | |
|
|
|
|
|
|
|
|
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 6 — Pressure Mode and Sub-Mode Directory
KEYPAD | ITEM | DISPLAY | ITEM | COMMENT | ||||
ENTRY | EXPANSION | |||||||
|
|
|
| |||||
PRC.A |
|
|
|
|
| PRESSURES CIRCUIT A |
| |
|
|
|
| DP.A | XXX.X PSIG | DISCHARGE PRESSURE |
| |
|
| ENTER |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| SP.A | XXX.X PSIG | SUCTION PRESSURE |
| |
|
|
|
|
|
|
|
| |
PRC.B |
|
|
|
|
| PRESSURES CIRCUIT B | See Note | |
|
|
| DP.B | XXX.X PSIG | DISCHARGE PRESSURE | See Note | ||
|
| ENTER |
| |||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| SP.B | XXX.X PSIG | SUCTION PRESSURE | See Note | |
|
|
|
|
|
|
|
|
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 7 — Set Points Mode and Sub-Mode Directory
KEYPAD | ITEM | DISPLAY | ITEM | COMMENT | ||||
ENTRY | EXPANSION | |||||||
|
|
|
| |||||
COOL |
|
|
|
|
| COOLING SETPOINTS |
| |
|
|
|
| CSP.1 | XXX.X °F | COOLING SETPOINT 1 | Default: 44 F | |
|
| ENTER |
| |||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| CSP.2 | XXX.X °F | COOLING SETPOINT 2 | Default: 44 F | |
|
|
|
|
|
|
|
| |
|
|
|
| CSP.3 | XXX.X °F | ICE SETPOINT | Default: 32 F | |
|
|
|
|
|
|
|
| |
HEAD |
|
|
|
|
| HEAD PRESSURE SETPOINTS |
| |
|
|
| H.DP | XXX.X °F | HEAD SETPOINT | Default: 95 F | ||
|
| ENTER |
| |||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| F.ON | XXX.X °F | FAN ON SETPOINT | Default: 95 F | |
|
|
|
|
|
|
|
| |
|
|
|
| F.OFF | XXX.X °F | FAN OFF SETPOINT | Default: 72 F | |
|
|
|
|
|
|
|
| |
|
|
|
| B.OFF | XXX.X °F | BASE FAN OFF DELTA TEMP | Default: 23 F | |
|
|
|
|
|
|
|
| |
|
|
|
| F.DLT | XXX.X °F | FAN STAGE DELTA | Default: 15 F | |
|
|
|
|
|
|
|
| |
FRZ |
|
|
|
|
| BRINE FREEZE SETPOINT |
| |
|
|
| BR.FZ | XXX.X °F | BRINE FREEZE POINT | Default: 34 F | ||
|
| ENTER |
| |||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
9