Table 10 — Configuration Mode and Sub-Mode Directory (cont)

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

 

COMMENT

ENTRY

EXPANSION

 

 

 

 

 

 

OPT2

 

 

 

 

 

 

 

UNIT OPTIONS 2 CONTROLS

 

 

 

 

 

 

 

 

CTRL

X

CONTROL METHOD

Default: Switch

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

0

= Enable/Off/Remote Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

= Occupancy

 

 

 

 

 

 

 

 

 

3

= CCN Control

 

 

 

 

 

 

LOAD

X

LOADING SEQUENCE SELECT

Default: Equal

 

 

 

 

 

 

 

 

 

1

= Equal

 

 

 

 

 

 

 

 

 

2

= Staged

 

 

 

 

 

 

LLCS

X

LEAD/LAG CIRCUIT SELECT

Default: Automatic

 

 

 

 

 

 

 

 

 

1

= Automatic

 

 

 

 

 

 

 

 

 

2

= Circuit A Leads

 

 

 

 

 

 

 

 

 

3

= Circuit B Leads

 

 

 

 

 

 

LCWT

XX.X ΔF

HIGH LCW ALERT LIMIT

Default: 60

 

 

 

 

 

 

Range: 2 to 60 °F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DELY

XX

MINUTES OFF TIME

Default: 0 Minutes

 

 

 

 

 

 

Range: 0 to 15 Minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ICE.M

ENBL/DSBL

ICE MODE ENABLE

Default: Disable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LS.MD

X

LOW SOUND MODE SELECT

Default: 0

 

 

 

 

 

 

 

 

 

0

= Mode Disable

 

 

 

 

 

 

 

 

 

1

= Fan Noise Only

 

 

 

 

 

 

 

 

 

2

= Fan/Compressor Noise

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LS.ST

00:00

LOW SOUND START TIME

Default: 00:00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LS.ND

00:00

LOW SOUND END TIME

Default: 00:00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LS.LT

XXX %

LOW SOUND CAPACITY LIMIT

Default: 100%

 

 

 

 

 

 

Range: 0 to 100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN

 

 

 

 

 

 

 

CCN NETWORK CONFIGURATION

 

 

 

 

 

 

 

 

CCNA

XXX

CCN ADDRESS

Default: 1

 

 

 

ENTER

 

 

Range: 1 to 239

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCNB

XXX

CCN BUS NUMBER

Default: 0

 

 

 

 

 

 

Range: 0 to 239

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAUD

X

CCN BAUD RATE

Default: 9600

 

 

 

 

 

 

 

 

 

1

= 2400

 

 

 

 

 

 

 

 

 

2

= 4800

 

 

 

 

 

 

 

 

 

3

= 9600

 

 

 

 

 

 

 

 

 

4

= 19,200

 

 

 

 

 

 

 

 

 

5

= 38,400

HP.A

 

 

 

 

 

 

 

HEAD PRESSURE CMP DELTA

 

 

 

 

 

 

A1.DT

XX

SCT DELTA FOR COMP A1

Range: 0 - 50 Default: 12

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A2.DT

XX

SCT DELTA FOR COMP A2

Range: 0 - 50 Default: 12

 

 

 

 

 

 

 

 

 

 

 

HP.B

 

 

 

 

 

 

 

HEAD PRESSURE CMP DELTA

 

 

 

 

 

 

B1.DT

XX

SCT DELTA FOR COMP B1

Range: 0 - 50 Default: 12

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2.DT

XX

SCT DELTA FOR COMP B2

Range: 0 - 50 Default: 12

 

 

 

 

 

 

 

 

 

 

 

13

Page 13
Image 13
Carrier 30RAP010-060 specifications SUB-MODE Keypad Display Comment, OPT2

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.