Carrier 30RAP010-060 Cooling Set Point Select, a30-4970, 30RAP Condenser Fan Layout, Fan Stages

Models: 30RAP010-060

1 124
Download 124 pages 40.33 Kb
Page 33
Image 33
a30-4970

CONTROL BOX

OFM1

 

Top View

Sizes 010,015

BOX

OFM1

 

CONTROL

OFM3

 

 

OFM2

 

Top View

 

Sizes 035-050

 

OFM1

 

a30-4970

BOX

 

CONTROL

OFM2

 

Top View

Sizes 018-030

CONTROL BOX

OFM1

OFM3

OFM2

OFM4

 

Top View

Sizes 055,060

Fig. 15 — 30RAP Condenser Fan Layout

Table 20 — Fan Stages

30RAP UNIT SIZE

 

FAN STAGES

 

Fan Stage

Contactor Energized

Fans Operating

 

010,015

Stage 1

OFM1

018-030

Stage 1

FC1

OFM1

Stage 2

FC1,2

OFM1,2

 

035-050

Stage 1

FC1

OFM3

Stage 2

FC2

OFM1,2

 

Stage 3

FC1,2

OFM1,2,3

 

Stage 1

FC3

OFM4

055,060

Stage 2

FC1,3

OFM4,3

Stage 3

FC3,2

OFM4,1,2

 

 

Stage 4

FC1,2,3

OFM1,2,3,4

Two other control methods are available for Machine On/ Off control:

OCCUPANCY SCHEDULE (ConfigurationOPT2 CTRL = 2) — The main base board will use the operating schedules as defined under the Time Clock mode in the scroll- ing marquee display. These schedules are identical. The sched- ule number must be set to 1 for local schedule.

The schedule number can be set anywhere from 65 to 99 for operation under a CCN global schedule. The Enable/Off/ Remote Contact must be in the Enable or Remote Contact posi- tion. The control mode (Operating ModesMODE) will be 1 when the switch is Off. The control mode will be 3 when the Enable/Off/Remote Contact switch input is On and the time of day is during an unoccupied period. Similarly, the control mode will be 7 when the time of day is during an occupied period.

CCN CONTROL (ConfigurationOPT2CTRL = 3) — An external CCN device such as Chillervisor System Manager controls the On/Off state of the machine. This CCN device forces the variable ‘CHIL_S_S’ between Start/Stop to control the chiller. The control mode (Operating ModesMODE) will be 1 when the switch is Off. The control mode will be 2 when the Enable/Off/Remote Contact switch input is On and

33

the CHIL_S_S variable is ‘Stop.’ Similarly, the control mode will be 6 when the CHIL_S_S variable is ‘Start.’

Table 20 illustrates how the control method and cooling set point select variables direct the operation of the chiller and the set point to which it controls. The illustration also shows the ON/OFF state of the machine for the given combinations.

Cooling Set Point Select

SINGLE — Unit operation is based on Cooling Set Point 1 (Set PointsCOOLCSP.1).

DUAL SWITCH — Unit operation is based on Cooling Set Point 1 (Set PointsCOOLCSP.1) when the Dual Set Point switch contacts are open and Cooling Set Point 2 (Set PointsCOOLCSP.2) when they are closed.

DUAL CCN OCCUPIED — Unit operation is based on Cooling Set Point 1 (Set PointsCOOLCSP.1) during the Occupied mode and Cooling Set Point 2 (Set PointsCOOLCSP.2) during the Unoccupied mode as configured under the local occupancy schedule accessible only from CCN. Schedule Number in Table SCHEDOVR (See Ap- pendix B) must be configured to 1. If the Schedule Number is set to 0, the unit will operate in a continuous 24-hr Occupied mode. Control method must be configured to 0 (switch). See Table 21.

Page 33
Image 33
Carrier 30RAP010-060 specifications Cooling Set Point Select, a30-4970, 30RAP Condenser Fan Layout, Fan Stages