Table 42 — Alarm and Alert Codes (cont)

ALARM/

ALARM

 

WHY WAS THIS

ACTION TAKEN

RESET

PROBABLE

ALERT

OR

DESCRIPTION

ALARM

BY CONTROL

METHOD

CAUSE

CODE

ALERT

 

GENERATED?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All compressors shut

 

 

 

 

 

 

down. Pump 2 turned

 

 

 

 

 

Cooler flow switch contacts

off. Pump 1 will be

 

Wiring error, pump

T197

 

Flow Lost While Pump 2

started if available.

Manual

circuit breaker

Alert

open for 3 seconds after

Running

Chiller allowed to run if

tripped, contactor

 

 

initially made

 

 

 

 

Pump 1 successfully

 

failure

 

 

 

 

 

 

 

 

 

starts and flow switch

 

 

 

 

 

 

is closed.

 

 

 

 

 

 

 

 

 

T198

 

Cooler Pump 1 Aux

Pump 1 Auxiliary Contacts

Chiller not allowed to

Automatic when

Wiring error, faulty

Alert

Contacts Closed While

closed for 26 seconds

pump contactor

start

aux contacts open

 

 

Pump Off

when pump state is off

(welded contacts)

 

 

 

 

 

 

 

 

 

 

 

T199

 

Cooler Pump 2 Aux

Pump 2 Auxiliary Contacts

Chiller not allowed to

Automatic when

Wiring error, faulty

Alert

Contacts Closed While

closed for 26 seconds

pump contactor

start

aux contacts open

 

 

Pump Off

when pump state is off

(welded contacts)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooler flow switch contacts

Chiller not allowed to

 

Wiring error, pump

 

 

 

failed to close within

 

T200

 

Cooler Flow/Interlock

1 minute (if cooler pump

start. For models with

 

circuit breaker

Alert

Contacts Failed to Close

control is enabled) or

dual pumps, the

Manual

tripped, contactor

 

 

at Start-Up

within 5 minutes (if cooler

second pump will be

 

failure, faulty flow

 

 

 

pump control is not

started if available

 

switch or interlock

 

 

 

enabled) after start-up

 

 

 

 

 

Cooler Flow/Interlock

 

All compressors shut

 

Cooler pump failure,

 

 

Flow switch opens for at

down. For models with

 

faulty flow switch or

A201

 

Contacts Opened

 

Alarm

least 3 seconds after

dual pumps, the

Manual

interlock, pump

During Normal

 

 

being initially closed

second pump will be

 

circuit breaker

 

 

Operation

 

 

 

 

started if available

 

tripped

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooler Pump Interlock

If configured for cooler

 

 

 

A202

 

pump control and flow

 

Automatic when

Wiring error, faulty

Alarm

Closed When Pump is

switch input is closed for

Chiller shut down

pump contactor

aux contacts open

 

 

Off

5 minutes while pump

 

(welded contacts)

 

 

 

 

 

 

 

output(s) are off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wiring error, faulty

 

 

 

Master chiller MBB

Dual chiller control

 

wiring, failed Slave

T203

 

Loss of Communication

disabled. Chiller runs

 

chiller MBB module,

Alert

loses communication

Automatic

with Slave Chiller

as a stand-alone

power loss at slave

 

 

with slave chiller MBB

 

 

 

 

machine.

 

chiller, wrong slave

 

 

 

 

 

 

 

 

 

 

 

address.

 

 

 

 

 

 

 

 

 

 

 

Dual chiller control

 

Wiring error, faulty

 

 

 

Slave chiller MBB loses

 

wiring, failed master

T204

 

Loss of Communication

disabled. Chiller runs

 

Alert

communication with

Automatic

chiller MBB module,

with Master Chiller

as a stand-alone

 

 

master chiller MBB

 

power loss at Master

 

 

 

machine

 

 

 

 

 

 

chiller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN Address for

 

 

 

 

 

 

both chillers is the

 

 

 

Master and slave chiller

Dual chiller routine

 

same. Must be

T205

 

Master and Slave Chiller

disabled. Master/slave

 

different. Check

Alert

have the same CCN

Automatic

with Same Address

run as stand-alone

CCN.A under the

 

 

address (CCN.A)

 

 

 

 

chillers.

 

OPT2 sub-mode in

 

 

 

 

 

 

 

 

 

 

 

Configuration at both

 

 

 

 

 

 

chillers.

 

 

 

 

 

 

 

 

 

 

LWT read is greater than

 

 

Building load greater

 

 

 

 

 

than unit capacity,

 

 

 

LCW Alert Limit, Total

 

 

T206

 

High Leaving Chilled

Alert only. No action

 

low water/brine flow

Alert

capacity is 100% and LWT

Automatic

Water Temperature

taken.

or compressor fault.

 

 

is greater than LWT

 

 

 

 

 

 

Check for other

 

 

 

reading one minute ago

 

 

 

 

 

 

 

alarms/alerts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chiller shutdown

Both EWT and LWT

 

 

 

 

 

must be at least 6 F

 

 

 

 

 

without going through

 

 

 

 

 

(3.3 C) above Brine

 

 

 

 

 

pumpdown. Cooler

 

A207

 

Cooler Freeze

Cooler EWT or LWT is less

Freeze point

Faulty thermistor,

Alarm

pump continues to

Protection

than Brine Freeze (BR.FZ)

(BR.FZ).

low water flow.

 

 

run a minimum of

 

 

 

 

Automatic for first,

 

 

 

 

 

5 minutes (if control

 

 

 

 

 

Manual reset thereaf-

 

 

 

 

 

enabled).

 

 

 

 

 

ter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooler EWT is less than

Chiller shutdown.

 

Faulty cooler pump,

A208

Alarm

EWT or LWT

LWT by 3° F (1.7° C) for

 

low water flow,

Cooler pump shut off

Manual

Thermistor failure

1 minute after a circuit is

plugged fluid

 

 

(if control enabled).

 

 

 

 

started

 

strainer.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pump 1 Service

 

 

 

 

 

 

Countdown (P.1.DN)

 

 

 

T300

 

Cooler Pump 1

expired. Complete pump 1

 

 

Routine pump

Alert

Scheduled

maintenance and enter

None

Automatic

maintenance

 

 

Maintenance Due

'YES' for Pump 1

 

 

required

 

 

 

Maintenance Done

 

 

 

 

 

 

(P.1.MN) item.

 

 

 

 

 

 

Pump 2 Service

 

 

 

 

 

 

Countdown (P.2.DN)

 

 

 

T301

 

Cooler Pump 2

expired. Complete pump 2

 

 

Routine pump

Alert

Scheduled

maintenance and

None

Automatic

maintenance

 

 

Maintenance Due

enter 'YES' for Pump 1

 

 

required

 

 

 

Maintenance Done

 

 

 

 

 

 

(P.2.MN) item.

 

 

 

70

Page 70
Image 70
Carrier 30RAP010-060 specifications T197

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.