Table 42 — Alarm and Alert Codes (cont)
ALARM/ | ALARM |
| WHY WAS THIS | ACTION TAKEN | RESET | PROBABLE | |
ALERT | OR | DESCRIPTION | ALARM | ||||
BY CONTROL | METHOD | CAUSE | |||||
CODE | ALERT |
| GENERATED? | ||||
|
|
|
| ||||
|
|
|
|
|
|
| |
|
|
|
| All compressors shut |
|
| |
|
|
|
| down. Pump 2 turned |
|
| |
|
|
| Cooler flow switch contacts | off. Pump 1 will be |
| Wiring error, pump | |
T197 |
| Flow Lost While Pump 2 | started if available. | Manual | circuit breaker | ||
Alert | open for 3 seconds after | ||||||
Running | Chiller allowed to run if | tripped, contactor | |||||
|
| initially made |
| ||||
|
|
| Pump 1 successfully |
| failure | ||
|
|
|
|
| |||
|
|
|
| starts and flow switch |
|
| |
|
|
|
| is closed. |
|
| |
|
|
|
|
|
|
| |
T198 |
| Cooler Pump 1 Aux | Pump 1 Auxiliary Contacts | Chiller not allowed to | Automatic when | Wiring error, faulty | |
Alert | Contacts Closed While | closed for 26 seconds | pump contactor | ||||
start | aux contacts open | ||||||
|
| Pump Off | when pump state is off | (welded contacts) | |||
|
|
|
| ||||
|
|
|
|
|
|
| |
T199 |
| Cooler Pump 2 Aux | Pump 2 Auxiliary Contacts | Chiller not allowed to | Automatic when | Wiring error, faulty | |
Alert | Contacts Closed While | closed for 26 seconds | pump contactor | ||||
start | aux contacts open | ||||||
|
| Pump Off | when pump state is off | (welded contacts) | |||
|
|
|
| ||||
|
|
|
|
|
|
| |
|
|
| Cooler flow switch contacts | Chiller not allowed to |
| Wiring error, pump | |
|
|
| failed to close within |
| |||
T200 |
| Cooler Flow/Interlock | 1 minute (if cooler pump | start. For models with |
| circuit breaker | |
Alert | Contacts Failed to Close | control is enabled) or | dual pumps, the | Manual | tripped, contactor | ||
|
| at | within 5 minutes (if cooler | second pump will be |
| failure, faulty flow | |
|
|
| pump control is not | started if available |
| switch or interlock | |
|
|
| enabled) after |
|
|
| |
|
| Cooler Flow/Interlock |
| All compressors shut |
| Cooler pump failure, | |
|
| Flow switch opens for at | down. For models with |
| faulty flow switch or | ||
A201 |
| Contacts Opened |
| ||||
Alarm | least 3 seconds after | dual pumps, the | Manual | interlock, pump | |||
During Normal | |||||||
|
| being initially closed | second pump will be |
| circuit breaker | ||
|
| Operation |
| ||||
|
|
| started if available |
| tripped | ||
|
|
|
|
| |||
|
|
|
|
|
|
| |
|
| Cooler Pump Interlock | If configured for cooler |
|
|
| |
A202 |
| pump control and flow |
| Automatic when | Wiring error, faulty | ||
Alarm | Closed When Pump is | switch input is closed for | Chiller shut down | pump contactor | |||
aux contacts open | |||||||
|
| Off | 5 minutes while pump |
| (welded contacts) | ||
|
|
|
| ||||
|
|
| output(s) are off |
|
|
| |
|
|
|
|
|
|
| |
|
|
|
|
|
| Wiring error, faulty | |
|
|
| Master chiller MBB | Dual chiller control |
| wiring, failed Slave | |
T203 |
| Loss of Communication | disabled. Chiller runs |
| chiller MBB module, | ||
Alert | loses communication | Automatic | |||||
with Slave Chiller | as a | power loss at slave | |||||
|
| with slave chiller MBB |
| ||||
|
|
| machine. |
| chiller, wrong slave | ||
|
|
|
|
| |||
|
|
|
|
|
| address. | |
|
|
|
|
|
|
| |
|
|
|
| Dual chiller control |
| Wiring error, faulty | |
|
|
| Slave chiller MBB loses |
| wiring, failed master | ||
T204 |
| Loss of Communication | disabled. Chiller runs |
| |||
Alert | communication with | Automatic | chiller MBB module, | ||||
with Master Chiller | as a | ||||||
|
| master chiller MBB |
| power loss at Master | |||
|
|
| machine |
| |||
|
|
|
|
| chiller. | ||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
|
|
|
| CCN Address for | |
|
|
|
|
|
| both chillers is the | |
|
|
| Master and slave chiller | Dual chiller routine |
| same. Must be | |
T205 |
| Master and Slave Chiller | disabled. Master/slave |
| different. Check | ||
Alert | have the same CCN | Automatic | |||||
with Same Address | run as | CCN.A under the | |||||
|
| address (CCN.A) |
| ||||
|
|
| chillers. |
| OPT2 | ||
|
|
|
|
| |||
|
|
|
|
|
| Configuration at both | |
|
|
|
|
|
| chillers. | |
|
|
|
|
|
|
| |
|
|
| LWT read is greater than |
|
| Building load greater | |
|
|
|
|
| than unit capacity, | ||
|
|
| LCW Alert Limit, Total |
|
| ||
T206 |
| High Leaving Chilled | Alert only. No action |
| low water/brine flow | ||
Alert | capacity is 100% and LWT | Automatic | |||||
Water Temperature | taken. | or compressor fault. | |||||
|
| is greater than LWT |
| ||||
|
|
|
|
| Check for other | ||
|
|
| reading one minute ago |
|
| ||
|
|
|
|
| alarms/alerts. | ||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
|
| Chiller shutdown | Both EWT and LWT |
| |
|
|
|
| must be at least 6 F |
| ||
|
|
|
| without going through |
| ||
|
|
|
| (3.3 C) above Brine |
| ||
|
|
|
| pumpdown. Cooler |
| ||
A207 |
| Cooler Freeze | Cooler EWT or LWT is less | Freeze point | Faulty thermistor, | ||
Alarm | pump continues to | ||||||
Protection | than Brine Freeze (BR.FZ) | (BR.FZ). | low water flow. | ||||
|
| run a minimum of | |||||
|
|
|
| Automatic for first, |
| ||
|
|
|
| 5 minutes (if control |
| ||
|
|
|
| Manual reset thereaf- |
| ||
|
|
|
| enabled). |
| ||
|
|
|
| ter. |
| ||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
| Cooler EWT is less than | Chiller shutdown. |
| Faulty cooler pump, | |
A208 | Alarm | EWT or LWT | LWT by 3° F (1.7° C) for |
| low water flow, | ||
Cooler pump shut off | Manual | ||||||
Thermistor failure | 1 minute after a circuit is | plugged fluid | |||||
|
| (if control enabled). |
| ||||
|
|
| started |
| strainer. | ||
|
|
|
|
| |||
|
|
|
|
|
|
| |
|
|
| Pump 1 Service |
|
|
| |
|
|
| Countdown (P.1.DN) |
|
|
| |
T300 |
| Cooler Pump 1 | expired. Complete pump 1 |
|
| Routine pump | |
Alert | Scheduled | maintenance and enter | None | Automatic | maintenance | ||
|
| Maintenance Due | 'YES' for Pump 1 |
|
| required | |
|
|
| Maintenance Done |
|
|
| |
|
|
| (P.1.MN) item. |
|
|
| |
|
|
| Pump 2 Service |
|
|
| |
|
|
| Countdown (P.2.DN) |
|
|
| |
T301 |
| Cooler Pump 2 | expired. Complete pump 2 |
|
| Routine pump | |
Alert | Scheduled | maintenance and | None | Automatic | maintenance | ||
|
| Maintenance Due | enter 'YES' for Pump 1 |
|
| required | |
|
|
| Maintenance Done |
|
|
| |
|
|
| (P.2.MN) item. |
|
|
|
70