Table 23 — Dual Chiller Configuration (Slave Chiller Example)

SUB-MODE

ITEM

KEYPAD ENTRY

DISPLAY

ITEM EXPANSION

COMMENTS

DISP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPT1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CTRL

CONTROL METHOD

 

 

 

 

ENTER

 

 

 

OPT2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CTRL

 

 

 

 

0

SWITCH

DEFAULT 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPT2

 

 

 

 

 

ESCAPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCNA

 

 

 

 

 

 

 

 

 

 

 

 

CCNA

 

 

1

CCN ADDRESS

SCROLLING STOPS

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

VALUE FLASHES

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

SELECT 2

 

 

 

 

 

 

 

(SEE NOTE 1)

CCN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCNA

 

 

 

 

2

CCN ADDRESS

CHANGE ACCEPTED

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN

 

 

 

 

 

ESCAPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCNB

 

 

 

 

0

CCN BUS NUMBER

DEFAULT 0

 

 

ENTER

 

 

 

 

 

(SEE NOTE 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN

 

 

 

 

 

ESCAPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RSET

 

PROCEED TO

 

 

 

 

 

 

 

SUBMODE RSET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRST

COOLING RESET TYPE

 

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LLEN

LEAD/LAG CHILLER ENABLE

15 ITEMS

 

 

 

 

 

 

 

 

 

 

LLEN

 

 

DSBL

 

SCROLLING STOPS

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DSBL

 

VALUE FLASHES

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENBL

 

SELECT ENBL

 

 

 

 

 

 

 

 

 

 

LLEN

 

 

ENBL

LEAD/LAG CHILLER ENABLE

CHANGE ACCEPTED

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LLEN

 

 

 

 

 

ESCAPE

 

 

 

RSET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MSSL

MASTER /SLAVE SELECT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MSSL

 

 

MAST

 

SCROLLING STOPS

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAST

 

VALUE FLASHES

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLVE

 

SELECT SLVE

 

 

 

 

 

 

 

 

 

 

MSSL

 

 

SLVE

MASTER /SLAVE SELECT

CHANGE ACCEPTED

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MSSL

 

 

 

 

 

ESCAPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RSET

 

SLAVE COMPLETE

 

 

 

ESCAPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Slave Control Method (CTRL) must be configured for 0.

2.Slave CCN Address (CCNA) must be different than Master.

3.Slave CCN Bus Number (CCNB) must be the same as Master

4.Slave does not require SLVA, LLBL, LLBD, or LLDY to be configured.

39

Page 39
Image 39
Carrier 30RAP010-060 specifications Dual Chiller Configuration Slave Chiller Example, Rset Slave Complete

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.