APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
ITEM | DISPLAY |
| ITEM DESCRIPTION | COMMENT | |
|
| UNIT OPTIONS 2 CONTROLS |
| ||
|
|
|
|
| Default: 0 |
| CTRL | X |
| Control Method | 0 = Enable/Off/Remote Switch |
|
| 2 = Occupancy | |||
|
|
|
|
| |
|
|
|
|
| 3 = CCN Control |
|
|
|
|
| Default: 1 |
| LOAD | X |
| Loading Sequence Select | 1 = Equal |
|
|
|
|
| 2 = Staged |
|
|
|
|
| Default: 1 |
| LLCS | X |
| Lead/Lag Circuit Select | 1 = Automatic |
|
| 2 = Circuit A Leads | |||
|
|
|
|
| |
|
|
|
|
| 3 = Circuit B Leads |
OPT2 | LCWT | XX |
| High LCW Alert Limit | Default: 60 |
| Range: 2 to 60 F | ||||
|
|
|
|
| |
| DELY | XX |
| Minutes Off Time | Default: 0 Minutes |
|
| Range: 0 to 15 Minutes | |||
|
|
|
|
| |
| ICE.M | ENBL/DSBL |
| Ice Mode Enable | Default: Disable |
| LS.MD | X |
| Low Sound Mode Select | Default: 0 |
|
|
|
|
| 0 = Mode Disable |
|
|
|
|
| 1 = Fan Noise Only |
|
|
|
|
| 2 = Fan/Compressor Noise |
| LS.ST | 00:00 |
| Low Sound Start Time | Default: 00:00 |
| LS.ND | 00:00 |
| Low Sound End Time | Default: 00:00 |
| LS.LT | XXX % |
| Low Sound Capacity Limit | Default: 100% |
|
| Range: 0 to 100% | |||
|
|
|
|
| |
|
|
| CCN NETWORK CONFIGS |
| |
| CCNA | XXX |
| CCN Address | Default: 1 |
|
| Range: 0 to 239 | |||
|
|
|
|
| |
| CCNB | XXX |
| CCN Bus Number | Default: 1 |
|
| Range: 0 to 239 | |||
CCN |
|
|
|
| |
|
|
|
| Default: 3 | |
|
|
|
|
| |
|
|
|
|
| 1 = 2400 |
| BAUD | X |
| CCN Baud Rate | 2 = 4800 |
|
| 3 = 9600 | |||
|
|
|
|
| |
|
|
|
|
| 4 =19,200 |
|
|
|
|
| 5 =38,400 |
|
| HEAD PRESSURE CMP. DELTA |
| ||
HP.A | A1.DT | XX |
| SCT Delta For Comp A1 | Default:12 |
| Range: 0 to 50 | ||||
|
|
|
| ||
| A2.DT | XX |
| SCT Delta For Comp A2 | Default:12 |
|
| Range: 0 to 50 | |||
|
|
|
|
| |
|
| HEAD PRESSURE CMP. DELTA |
| ||
HP.B | B1.DT | XX |
| SCT Delta For Comp B1 | Default:12 |
| Range: 0 to 50 | ||||
|
|
|
| ||
| B2.DT | XX |
| SCT Delta For Comp B2 | Default:12 |
|
| Range: 0 to 50 | |||
|
|
|
|
|
80