APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table G — Network Points List (cont)
POINT DESCRIPTION | POINT NAME | READ/ | UNITS | DEFAULT | RANGE | BACNET | BACNET |
|
| WRITE |
| VALUE |
| OBJECT ID | OBJECT NAME |
Cooling Setpoint 2 | CSP2 | R/W | °F | 44.0 | AV:54 | csp2_1 | |
CSM Controlling Chiller | MODE_1 | R |
|
|
| BV:30 | mode_1_1 |
Demand Level 1 |
| R | % |
|
| AV:75 | dmv_lvl_1_perct_1 |
Demand Level 2 |
| R | % |
|
| AV:76 | dmv_lvl_2_perct_1 |
Demand Level 3 |
| R | % |
|
| AV:77 | dmv_lvl_3_perct_1 |
Demand Limit Switch 1 | DMD_SW1 | R |
|
|
| BV:25 | dmd_sw1_1 |
Demand Limit Switch 2 | DMD_SW2 | R |
|
|
| BV:26 | dmd_sw2_1 |
Demand/Sound Limited | MODE_15 | R |
|
|
| BV:41 | mode_15_1 |
Discharge Gas Temp | DISGAS | R | °F |
|
| AV:15 | disgas_1 |
Discharge Pressure | DP_A | R | psig |
|
| AV:13 | dp_a_1 |
Discharge Pressure | DP_B | R | psig |
|
| AV:23 | dp_b_1 |
Dual Setpoint | MODE_13 | R |
|
|
| BV:39 | mode_13_1 |
Dual Setpoint Switch | DUAL_IN | R |
|
|
| BV:29 | dual_in_1 |
Element Comm Status |
| R |
|
|
| BV:2999 | element_stat_1 |
Element Communications |
| R |
|
|
| BV:58 | comm_lost_alm_1 |
Alarm |
|
|
|
| |||
|
|
|
|
|
|
| |
Emergency Stop | EMSTOP | R/W |
| Enabled | Enabled/Emstop | BV:6 | emstop_1 |
Entering Fluid Temp | EWT | R | °F |
|
| AV:6 | ewt_1 |
EXV % Open | EXV_A | R | % |
|
| AV:18 | exv_a_1 |
EXV % Open | EXV_B | R | % |
|
| AV:27 | exv_b_1 |
Fan 1 Relay | FAN_1 | R |
|
|
| BV:22 | fan_1_1 |
Fan 2 Relay | FAN_2 | R |
|
|
| BV:23 | fan_2_1 |
Head Setpoint | HSP | R | °F |
|
| AV:29 | hsp_1 |
Heat Request | HEAT_REQ | R |
|
|
| BV:28 | heat_req_1 |
High SCT Circuit A | MODE_21 | R |
|
|
| BV:47 | mode_21_1 |
High SCT Circuit B | MODE_22 | R |
|
|
| BV:48 | mode_22_1 |
High Temperature Cooling | MODE_18 | R |
|
|
| BV:44 | mode_18_1 |
Ice Done | ICE_DONE | R |
|
|
| BV:27 | ice_done_1 |
Ice Setpoint | CSP3 | R/W | °F | 32.0 | AV:55 | csp3_1 | |
Lead/Lag Circuit Select |
|
|
|
| 1 = Automatic |
|
|
LEAD_TYP | R/W |
| 1 | 2 = Circuit A Leads | AV:43 | lead_typ_1 | |
|
|
|
|
| 3 = Circuit B Leads |
|
|
Lead/Lag Circuit Select | LEAD_TYP | R |
|
|
| MSV:6 | lead_typ_msv_1 |
Lead/Lag Leaving Fluid | DUAL_LWT | R | °F |
|
| AV:32 | dual_lwt_1 |
Leadpump | LEADPUMP | R |
|
|
| MSV:9 | leadpump_msv_1 |
Leaving Fluid Temp - Prime | LWT | R | °F |
|
| AV:7 | lwt_1 |
Variable |
|
| |||||
|
|
|
|
|
|
| |
Loading Sequence Select | SEQ_TYPE | R |
|
|
| AV:74 | seq_type_1 |
Local Schedule |
| R |
|
|
| BV:1 | schedule_1 |
Low Cooler Suction Temp A | MODE_7 | R |
|
|
| BV:35 | mode_7_1 |
Low Cooler Suction Temp B | MODE_8 | R |
|
|
| BV:36 | mode_8_1 |
Low Sound Active | LSACTIVE | R |
|
|
| BV:2 | lsactive_1 |
Low Sound Mode | MODE_25 | R |
|
|
| BV:51 | mode_25_1 |
Low Temperature Cooling | MODE_17 | R |
|
|
| BV:43 | mode_17_1 |
Machine Operating Hours | HR_MACH | R | hr |
|
| AV:57 | hr_mach_1 |
Machine Starts | CY_MACH | R |
|
|
| AV:58 | cy_mach_1 |
Making ICE | MODE_19 | R |
|
|
| BV:45 | mode_19_1 |
Master/Slave Control | MODE_3 | R |
|
|
| BV:32 | mode_3_1 |
Minimum Comp. On Time | MODE_23 | R |
|
|
| BV:49 | mode_23_1 |
Minimum Load Valve Relay | MLV_RLY | R |
|
|
| BV:15 | mlv_rly_1 |
Minimum OFF Time Active | MODE_10 | R |
|
|
| BV:38 | mode_10_1 |
Minutes Off Time | DELAY | R/W | min | 0 | 0 - 15 | AV:42 | delay_1 |
Occupied | OCC | R |
|
|
| BV:3 | occ_1 |
Outside Air Temperature | OAT | R | °F |
|
| AV:34 | oat_1 |
Override Modes in Effect | MODE | R |
|
|
| BV:5 | mode_1 |
Percent Available Cap. | CAP_A | R | % |
|
| AV:12 | capa_a_1 |
Percent Available Cap. | CAPB_A | R | % |
|
| AV:22 | capb_a_1 |
LEGEND
R— Read
W — Write