APPENDIX A — DISPLAY TABLES
Run Status Mode and Sub-Mode Directory
ITEM | DISPLAY | ITEM DESCRIPTION | COMMENT | |
|
| AUTO VIEW OF RUN STATUS |
| |
| EWT | xxx.x ºF | Entering Fluid Temp |
|
| LWT | xxx.x ºF | Leaving Fluid Temp |
|
| SETP | xxx.x ºF | Active Set Point |
|
| CTPT | xxx.x ºF | Control Point |
|
| LOD.F | xxx | Load/Unload Factor |
|
|
|
|
| 0=Service Test |
|
|
|
| 1=Off Local |
|
|
|
| 2=Off CCN |
| STAT |
| Control Mode | 3=Off Time |
|
| 4=Off Emrgcy | ||
|
|
|
| |
|
|
|
| 5=On Local |
|
|
|
| 6=On CCN |
VIEW |
|
|
| 7=On Time |
LD.PM |
| Lead Pump |
| |
|
|
| ||
| OCC | YES/NO | Occupied |
|
| LS.AC | YES/NO | Low Sound Active |
|
| MODE | YES/NO | Override Modes in Effect |
|
| CAP | xxx | Percent Total Capacity |
|
| STGE | x | Requested Stage |
|
| ALRM | xxx | Current Alarms & Alerts |
|
| TIME | xx.xx | Time of Day | |
| MNTH | xx | Month of Year | 1 - 12 (1 = January, |
| 2 = February, etc.) | |||
|
|
|
| |
| DATE | xx | Day of Month | |
| YEAR | xx | Year of Century |
|
|
| UNIT RUN HOUR AND START |
| |
| HRS.U | xxxx HRS | Machine Operating Hours |
|
RUN | STR.U | xxxx | Machine Starts |
|
| HR.P1 | xxxx HRS | Pump 1 Run Hours |
|
| HR.P2 | xxxx HRS | Pump 2 Run Hours |
|
|
| CIRC AND COMP RUN HOURS |
| |
| HRS.A | xxxx HRS | Circuit A Run Hours |
|
| HRS.B | xxxx HRS | Circuit B Run Hours |
|
HOUR | HR.A1 | xxxx HRS | Compressor A1 Run Hours |
|
| HR.A2 | xxxx HRS | Compressor A2 Run Hours |
|
| HR.B1 | xxxx HRS | Compressor B1 Run Hours |
|
| HR.B2 | xxxx HRS | Compressor B2 Run Hours |
|
74