MINIMUM LOAD VALVE — On units equipped with the
The amount of capacity reduction achieved by the mini- mum load valve is not adjustable. The total unit capacity with the minimum load valve is shown in Table 19.
PRESSURE RELIEF DEVICES — All units have one pres- sure relief device per circuit located in the liquid line which re- lieves at 210 F (100 C).
Check Unit Safeties
The
Table 32 — Factory Settings, High-Pressure
Switch (Fixed)
UNIT | CUTOUT |
| |||
Psig | kPa | Psig |
| kPa | |
|
| ||||
30RA | 650 | 4482 | 500 |
| 3447 |
Clear the alarm using the scrolling marquee display as de- scribed on page 63. The unit should restart after the compressor
PRESSURE TRANSDUCERS — Each refrigerant circuit is equipped with a suction and discharge pressure transducer. These inputs to the MBB are not only used to monitor the sta- tus of the unit, but to also maintain operation of the chiller within the compressor manufacturer's specified limits. The in- put to the MBB from the suction pressure transducer is also used to protect the compressor from operating at low pressure conditions and low superheat conditions. In some cases, the unit may not be able to run at full capacity. The control module will automatically reduce the capacity of a circuit as needed to maintain specified maximum/minimum operating pressures.
COOLER
WARNING
On medium temperature brine units, the
The main base board (MBB) monitors leaving fluid temper- ature at all times. The MBB will rapidly remove stages of ca- pacity as necessary to prevent freezing conditions due to the rapid loss of load or low cooler fluid flow.
When the cooler is exposed to lower ambient temperatures (34 F [1° C] or below),
HEATER CABLE — Optional
The input from the low pressure transducer provides a back- up cooler freeze protection package. The MBB shuts down the unit when a low pressure condition exists that could cause the cooler to freeze up.
CAUTION
Do not disconnect main unit power when servicing com- pressor(s) if ambient temperature is below 40 F (4.4 C). The compressors have either a single circuit breaker or multiple circuit breakers which can be used to shut off power to the compressors. If power to the unit must be off for a prolonged period, drain the cooler, hydronic package (if installed) and internal piping. Add glycol according to Winter Shutdown Step 2 below.
WINTER SHUTDOWN — At the end of the cooling season:
1.Drain the fluid from the cooler, hydronic package (if in- stalled) and internal piping.
2.Fill the cooler and hydronic package with at least 2 gal- lons (7.6 L) of inhibited propylene glycol or other suit- able inhibited antifreeze solution to prevent any residual water in the cooler and hydronic package/piping from freezing.
3.At the beginning of the next cooling season, refill the cooler and add the recommended inhibitor.
Thermistors — Electronic control uses up to five 5 kΩ thermistors to sense temperatures used to control operation of the chiller. Thermistors EWT, LWT, RGTA, RGTB, and OAT are identical in their temperature and voltage drop perfor- mance. The SPT space temperature thermistor has a 10 kΩ in- put channel and it has a different set of temperature vs. resis- tance and voltage drop performance. Resistance at various tem- peratures are listed in Tables
REPLACING THERMISTORS (EWT, LWT, RGT) — Add a small amount of thermal conductive grease to the thermistor well and end of probe. For all probes, tighten the retaining nut ¼ turn past finger tight. See Fig. 28.
THERMISTOR/TEMPERATURE SENSOR CHECK — A high quality digital
1.Connect the digital voltmeter across the appropriate the- mistor terminals at the J8 terminal strip on the Main Base Board (see Fig. 29).
2.Using the voltage reading obtained, read the sensor tem- perature from Tables
3.To check thermistor accuracy, measure temperature at probe location with an accurate
If a more accurate check is required, unit must be shut down and thermistor removed and checked at a known temperature (freezing point or boiling point of water) using either voltage drop measured across thermistor at the J8 terminal, by deter- mining the resistance with chiller shut down and thermistor
52