Table 39 — Motormaster® V Program Parameters for Operating Modes

PARAMETERS

DESCRIPTION

MODE

MODE

MODE

MODE

5

6

7

8

 

 

 

 

P01

Line Voltage: 01 = low line, 02 = high line

01

02

01

02

 

P02

Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz

01

01

01

01

 

P03

Startup mode: flying restart

06

06

06

06

 

P04

Stop mode: coast to stop

01

01

01

01

 

P05

Standard Speed source: 01= keypad,

04

04

04

04

 

04=4-20mA (NO PI), 05= R22, 06=R134a

 

 

 

 

 

 

 

P06

TB-14 output: 01 = none

01

01

01

01

 

P08

TB-30 output: 01 = none

01

01

01

01

 

P09

TB-31 Output: 01 = none

01

01

01

01

 

P10

TB-13A function sel: 01 = none

01

01

01

01

 

P11

TB-13B function sel: 01 = none

01

01

01

01

 

P12

TB-13C function sel: 01 = none

01

01

01

01

 

P13

TB-15 output: 01 = none

01

01

01

01

 

P14

Control: 01 = Terminal strip

01

01

01

01

 

P15

Serial link: 02 = enabled 9600,8,N,2 with timer

02

02

02

02

 

P16

Units editing: 02 = whole units

02

02

02

02

 

P17

Rotation: 01 = forward only, 03 = reverse only

01

01

01

01

 

P19

Acceleration time: 10 sec

10

10

10

10

 

P20

Deceleration time: 10 sec

10

10

10

10

 

P21

DC brake time: 0

0

0

0

0

 

P22

DC BRAKE VOLTAGE 0%

0

0

0

0

 

P23

Min freq = 8 Hz ~ 100 – 160 rpm

8

8

8

8

 

P24

Max freq

60

60

50

50

 

P25

Current limit: (%)

125

110

125

110

 

P26

Motor overload: 100

100

100

100

100

 

P27

Base freq: 60 or 50 Hz

60

60

50

50

 

P28

Fixed boost: 0.5% at low frequencies

0.5

0.5

0.5

0.5

 

P29

Accel boost: 0%

0

0

0

0

 

P30

Slip compensation: 0%

0

0

0

0

 

P31

Preset spd #1: speed if loss of control signal

57

57

47

47

 

P32

Preset spd #2: 0

0

0

0

0

 

P33

Preset spd #3: 0

0

0

0

0

 

P34

Preset spd 4 default — R22 set point.

18.0

18.0

18.0

18.0

 

TB12-2 open

 

 

 

 

 

 

 

P35

Preset spd 5 default — R134a set point.

12.6

12.6

12.6

12.6

 

TB12-2 closed

 

 

 

 

 

 

 

P36

Preset spd 6 default

0

0

0

0

 

P37

Preset spd 7 default

0

0

0

0

 

P38

Skip bandwidth

0

0

0

0

 

P39

Speed scaling

0

0

0

0

 

P40

Frequency scaling 50 or 60 Hz

60

60

50

50

 

P41

Load scaling: default (not used so NA)

200

200

200

200

 

P42

Accel/decel #2: default (not used so NA)

60

60

60

60

 

P43

Serial address

1

1

1

1

 

P44

Password:111

111

111

111

111

 

P45

Speed at min signal: 8 Hz; used when PID

8

8

8

8

 

mode is disabled and 4-20mA input is at 4 mA

 

 

 

 

 

 

 

P46

Speed at max feedback: 60 or 50 Hz. Used

60

60

50

50

 

when PID disabled and 4-20mA input is at 20 mA

 

 

 

 

 

 

 

P47

Clear history? 01 = maintain. (set to 02 to clear)

01

01

01

01

 

P48

Program selection: Program 1 – 12

05

06

07

08

 

P61

PI Mode: 05= reverse, 0-5V, 01 = no PID

01

01

01

01

 

P62

Min feedback = 0 (0V *10)

0

0

0

0

 

P63

Max feedback = 50 (5V * 10)

50

50

50

50

 

P64

Proportional gain = 4%

4

4

4

4

 

P65

Integral gain = .2

.2

.2

.2

.2

 

P66

PI acell/decel (set point change filter) = 5

5

5

5

5

 

P67

Min alarm

0

0

0

0

 

P68

Max alarm

0

0

0

0

 

LEGEND

 

 

 

 

NA

Not Applicable

 

 

 

 

PID

Proportional Integral Derivative

 

 

 

 

TB

Terminal Block

 

 

 

 

62

Page 62
Image 62
Carrier 30RAP010-060 specifications Motormaster V Program Parameters for Operating Modes, Parameters Description Mode, Pid

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.