CHAPTER 8 PARAMETER SUMMARY

 

 

 

 

 

VFD-F Series

CHAPTER 8 PARAMETER SUMMARY

 

 

 

Group 0 AC Drive Status Parameter

 

 

 

 

 

 

 

 

 

 

 

 

Parameters

Functions

Settings

Factory

Customer

 

Setting

 

00-00

Software Version

Read only

 

 

 

 

00-01

AC Drive Status Indication 1 00: No Fault occurred

Read

 

 

01:oc (over current)

02:ov (over voltage)

03:oH (over temperature)

04:oL (overload)

05:oL1 (electronic thermal relay)

06:EF (External Fault)

07:occ (AC drive IGBT fault)

08:cF3 (CPU failure)

09:HPF (Hardware Protection Failure)

10:ocA (current exceed during Acceleration)

11:ocd (current exceed during Deceleration)

12:ocn (current exceed during Steady State)

13:GFF (Ground Fault)

14:Lv (Low voltage)

15:cF1 (input data abnormal)

16:cF2 (output data abnormal)

17:bb (base block)

18:oL2 (over load2)

19:Reserved

20:codE (software or password protection)

21:EF1 (external emergency stop)

22:PHL (phase loss)

23:Lc (Low current)

24:FbL (Feedback loss)

25:Reserved

26:FAnP (Fan Power Fault)

27:FF1 (Fan 1 fault)

28:FF2 (Fan 2 fault)

29:FF3 (Fan 3 fault)

30:FF123 (Fan 1, 2, 3 fault)

31:FF12 (Fan 1, 2 fault)

32:FF13 (Fan 1, 3 fault)

33:FF23 (Fan 2, 3 fault)

34:Fv (Gate Drive Low Voltage Protect)

8