Delta Electronics VFD-F Series manual PLC program operation

Models: VFD-F Series

1 161
Download 161 pages 45.18 Kb
Page 120
Image 120
37: PLC program operation

 

 

 

 

 

 

VFD-F Series

 

 

 

 

 

 

 

 

 

Parameters

Functions

Settings

Factory

Customer

 

 

 

 

 

Setting

 

 

 

 

 

37: PLC program operation

 

 

 

 

 

 

Paused

 

 

 

 

03-08

Master Frequency Attained 1

0.00~120.00 Hz

0.00

 

 

 

 

 

 

 

 

 

 

03-09

Master Frequency Attained 2

0.00~120.00 Hz

0.00

 

 

 

 

 

 

 

 

 

 

03-10

Analog Output 1, (AFM1)

00: Output frequency

00

 

 

 

 

0~10Vdc

01: Output current

 

 

 

 

03-11

Analog Output 2, (AFM2)

02: Output voltage

01

 

 

 

 

0/4~ 20mA

03: Frequency command

 

 

 

 

 

 

04: Power factor loading

 

 

 

 

03-12

Analog Output Gain 1

01~200%

100

 

 

 

 

 

 

 

 

 

 

03-13

Analog Output Gain 2

01~200%

100

 

 

 

03-14

Analog Output 2 Selection

00: 0~20mA

01

 

 

 

 

(AFM2 Definition)

01: 4~20mA

 

 

 

 

03-15

DC Fan Control

00: Fan runs on power up.

00

 

 

 

 

 

01: Fan begins upon a RUN

 

 

 

 

 

 

command. Fan stops 1

 

 

 

 

 

 

minute after a STOP

 

 

 

 

 

 

command.

 

 

 

 

 

 

02: Fan begins upon a RUN

 

 

 

 

 

 

command. Fan stops

 

 

 

 

 

 

after a STOP command

 

 

 

 

 

 

03: Fan is controlled by

 

 

 

 

 

 

temperature.

 

 

 

 

 

 

Approximately a 60°C

 

 

 

 

 

 

temperature will start the

 

 

 

 

 

 

fan.

 

 

8

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

8-7

Page 120
Image 120
Delta Electronics VFD-F Series manual PLC program operation