Delta Electronics VFD-F Series manual Control Terminals

Models: VFD-F Series

1 161
Download 161 pages 45.18 Kb
Page 20
Image 20
3.4 Control Terminals

VFD-F Series

3.4 Control Terminals

SINK/NPN Mode

SOURCE/PNP Mode

+24V

DCM

Multi-function

Multi-function

 

Input Terminal

Input Terminal

 

Internal Circuit

+24V

Internal Circuit

DCM

 

 

 

Terminal symbols and functions

Terminal Symbols

Terminal Functions

 

Factory Settings

FWD

Forward-Stop command

 

 

REV

Reverse-Stop command

 

 

EF

External fault

 

 

MI1

Multi-function Input 1

 

Factory setting: Multi-step speed command 1

MI2

Multi-function Input 2

 

Factory setting: Multi-step speed command 2

MI3

Multi-function Input 3

 

Factory setting: Multi-step speed command 3

MI4

Multi-function Input 4

 

Factory setting: Multi-step speed command 4

MI5

Multi-function Input 5

 

Factory setting: RESET

MI6

Multi-function Input 6

 

Factory setting: JOG

MI7

Multi-function Input 7

 

Factory setting: Accel/Decel prohibit

MI8

Multi-function Input 8

 

Factory setting: Accel/Decel time switch 1

+24V

DC Voltage Source

 

(+24V, 20mA), used for source mode.

DCM

Digital Signal Common

 

Used as common for digital inputs and used

 

for sink mode.

 

 

 

RA 1

Multi-function Relay1

 

 

output (N.O.) a

 

 

 

 

 

RB 1

Multi-function Relay1

 

 

output (N.C.) b

 

 

 

 

 

RC 1

Multi-function Relay1

 

1.5A(N.O.)/1A(N.C.) 240VAC

common

 

 

 

1.5A(N.O.)/1A(N.C.) 24VDC

RA 2

Multi-function Relay2

 

 

Refer to Pr.03-00 to Pr.03-01

output (N.O.) a

 

 

 

 

RB 2

Multi-function Relay2

 

 

output (N.C.) b

 

 

 

 

 

RC 2

Multi-function Relay2

 

 

common

 

 

 

 

 

 

 

 

 