Delta Electronics VFD-F Series manual B.3 AC Reactor, AC Input Reactor Recommended Value

Models: VFD-F Series

1 161
Download 161 pages 45.18 Kb
Page 145
Image 145
B.3 AC Reactor

AC Input Reactor Recommended Value VFD-F Series

B.3 AC Reactor

AC Input Reactor Recommended Value

460V, 50/60Hz, 3-Phase

KW

HP

0.751

1.52

2.23

3.75

5.57.5

7.510

11

15

15

20

18.525

22

30

30

40

37

50

45

60

55

75

75

100

90

125

110

150

132

175

160

215

185250

220300

460V DC Choke

Fundamental

Max. Continuous

Amps

Amps

4

6

4

6

8

12

8

12

12

18

18

27

25

37.5

35

52.5

35

52.5

45

67.5

55

82.5

80

120

80

120

100

150

130

195

160

240

200

300

250

375

320

480

400

560

500

700

Inductance (mh)

3% impedance

5% impedance

9

12

6.5

9

5

7.5

3

5

2.5

4.2

1.5

2.5

1.2

2

0.8

1.2

0.8

1.2

0.7

1.2

0.5

0.85

0.4

0.7

0.4

0.7

0.3

0.45

0.2

0.3

0.15

0.23

0.11

0.185

0.09

0.15

0.075

0.125

0.06

0.105

0.05

0.085

Input Voltage

kW

HP

DC Amps

Inductance (mh)

 

0.75

1

4

25.00

 

1.5

2

9

11.50

 

2.2

3

9

11.50

 

3.7

5

12

6.00

 

5.5

7.5

18

3.75

 

7.5

10

25

4.00

 

11

15

32

2.68

 

15

20

50

2.00

Manual backgroundManual backgroundManual backgroundManual backgroundNOTE

18.5kW~132kW models: built-in DC choke

160kW~220kW models: built-in AC reactor

B-10

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

Page 145
Image 145
Delta Electronics VFD-F Series manual B.3 AC Reactor, AC Input Reactor Recommended Value