Delta Electronics VFD-F Series manual Group 11 Fan and Pump Control Parameters

Models: VFD-F Series

1 161
Download 161 pages 45.18 Kb
Page 132
Image 132
Group 11 Fan and Pump Control Parameters

 

 

 

 

 

 

VFD-F Series

Group 11 Fan and Pump Control Parameters

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameters

Functions

Settings

Factory

 

Customer

 

 

Setting

 

 

 

11-00

V/F Curve Selection

00: Determined by group 01

00

 

 

 

 

 

 

01: 1.5 power curve

 

 

 

 

 

 

 

02: 1.7 power curve

 

 

 

 

 

 

 

03: 2 power curve

 

 

 

 

 

 

 

04: 3 power curve

 

 

 

 

 

11-01

Circulative Control

00: No function

00

 

 

 

 

 

 

01: Time circulation (by time)

 

 

 

 

 

 

 

02: Fixed amount circulation

 

 

 

 

 

 

 

(by PID)

 

 

 

 

 

 

 

03: Fixed amount control (an

 

 

 

 

 

 

 

AC drive runs with 4

 

 

 

 

 

 

 

motors)

 

 

 

 

 

11-02

Multiple Motors Control

01~04

01

 

 

 

 

11-03

Time Circulation Time Setting

00~65500 Min

00

 

 

 

 

 

 

 

 

 

 

 

 

11-04

Motor Switch Delay Time

0.0~3600.0 sec

1.0

 

 

 

 

 

 

 

 

 

 

 

11-05

Motor Switch Delay Time during

0.0~3600.0 sec

10.0

 

 

 

 

 

Fixed Amount Circulation

 

 

 

 

 

 

11-06

Motor Switch Frequency during

0.00 to 120.00 Hz

60.00

 

 

 

 

 

Fixed Amount Circulation

 

 

 

 

 

 

11-07

Enter Sleep Process Time

0.0~3600.0sec

0.0

 

 

 

 

 

 

0.0: Sleep function disable

 

 

 

 

 

11-08

Sleep Frequency of Sleep

0.00 to 11-09

0.0

 

 

 

 

 

Process

(Wake up Frequency)

 

 

 

 

 

11-09

Wake Up Frequency of Sleep

0.00 to 120.0Hz

0.0

 

 

 

 

 

Process

 

 

 

 

 

 

11-10

Treatment of Fixed Amount

00: Turn off all motors

00

 

 

 

 

 

Circulation Malfunction

01: Turn off AC drive

 

 

 

 

 

11-11

Stop Frequency of Auxiliary

0.00~120.00Hz

0.00

 

 

 

 

 

Motor

 

 

 

 

8

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

8-19

Page 132
Image 132
Delta Electronics VFD-F Series manual Group 11 Fan and Pump Control Parameters