Group 6 Protection Function Parameters (Twice the value for 460V class)

Manual background VFD-F Series

Group 6 Protection Function Parameters (Twice the value for 460V class)

 

Parameters

Functions

Settings

Factory

Customer

 

Setting

 

06-00

Over-voltage Stall Prevention

230V: 330.0~410.0VDC

390.0

 

 

 

 

460V: 660.0~820.0VDC

780.0

 

 

 

 

00: Disable

 

 

 

06-01

Over-current Stall Prevention

20~150%

120

 

 

 

during Acceleration

00: Disable

 

 

 

06-02

Over-current Stall Prevention

20~150%

120

 

 

 

during operation

00: Disable

 

 

 

06-03

Over-torque Detection

00: Over-torque detection

00

 

 

 

Selection

disabled.

 

 

 

 

 

01: Over-torque detection enabled

 

 

 

 

 

during constant speed

 

 

 

 

 

operation (OL2), and operation

 

 

 

 

 

continues.

 

 

 

 

 

02: Over-torque detection enabled

 

 

 

 

 

during constant speed

 

 

 

 

 

operation (OL2), and operation

 

 

 

 

 

halted.

 

 

 

 

 

03: Over-torque detection enabled

 

 

 

 

 

during operation (OL2), and

 

 

 

 

 

operation continues.

 

 

 

 

 

04: Over-torque detection enabled

 

 

 

 

 

during operation (OL2), and

 

 

 

 

 

operation halted.

 

 

 

06-04

Over-torque Detection Level

30~150%

110

 

 

06-05

Over-torque Detection Time

0.1~60.0 Sec

0.1

 

 

06-06

Electronic Thermal Relay

00: Operate disabled.

02

 

 

 

Selection

01: Operate with a standard motor.

 

 

 

 

 

02: Operate with a special motor.

 

 

 

06-07

Electronic Thermal

30~600 Sec

60

 

 

 

Characteristic

 

 

 

 

06-08

Low Current Detection Level

00~100% (00 disabled)

00

 

 

06-09

Low Current Detection Time

0.1~ 3600.0 Sec

10.0

 

 

 

 

 

 

 

 

06-10

Low Current Detection

00: Warn and ramp to stop

01

 

 

 

Treatment

01: Warn and coast to stop

 

 

 

 

 

02: Warn and keep operating

 

 

 

06-11

Present Fault Record

00: No fault

00

 

 

06-12

Second Most Recent Fault

01: Oc (over-current)

00

 

 

 

Record

02: Ov (over-voltage)

 

 

 

06-13

Third Most Recent Fault

03: OH (over temperature)

00

 

 

 

Record

04: OL (over load)

 

 

8-12